Installation Manual
| DCIPS2B-S-00-B11 Power Supply System
20
21
+1 (208) 635-6400 | www.transtector.com
+1 (208) 635-6400 | www.transtector.com
3.2.5 Breakers
Maximum 45°C operating ambient:
1. UP to 32A CB maximum load must not exceed 80% of it’s rating.
2. 40A CB maximum load shall not exceed 30A.
3. 50-63A CB maximum load shall not exceed 35A.
Maximum 55°C operating ambient:
1. Up to 20A CB maximum load must not exceed 80% of it’s rating
2. 25A to 63A CB maximum load must not exceed 60% of it’s rating.
Maximum 65°C operating ambient:
1. Up to 20A CB maximum load must not exceed 80% of it’s rating
2. 25A to 63A CB maximum load must not exceed 50% of it’s rating.
CAUTION
Breakers should always be replaced with the same type and rating in order to
avoid damage to system components.
3.2.6 Hot Surfaces
CAUTION
Areas of the Power System may become hot. Take precautions and handle
with care to avoid bodily harm.
Chapter 4 Installation Guide
4.1 Preparation
4.1.1 Installation Overview
The following is the recommended sequence for the installation procedures. The sequence
may change according to job or actual configuration.
• Unpack and check that all the equipment and materials have been delivered.
• Obtain the recommended tools.
• Check the connecting cable size.
• Mount the power system subrack to a cabinet or an open frame.
• Remove the top cover and knockouts for cable entry (if Extended cover kit is ordered).
• Connect the earth grounding cable.
• Connect the AC input power.
• Connect the loads to the Distribution Unit as required.
• Connect the battery cables between power system and batteries.
• Connect the external alarm, symmetry cable and temperature sensor cable as required.
• Connect the RS232 communication cable (if RJ45-DB9 cable is ordered).
•
Insert the rectifiers into the rectifier frame.
• Reinstall the top cover (If cover kit is ordered)
4.1.2 Unpacking
Check that the received equipment is in accordance with the packing list. Ensure that the
cabinet and the equipment have not been damaged during transportation.
Report any parts that are damaged, missing or incorrect. If possible, correct the problem
before continuing.