4 / 4
AirTM-100NB
Warning
Technical parameters
* Values are calculated under ideal conditions and may vary depending on the type of sensor
connected
** Not included in the package
*** Multiple frequency bands of B1 / B3 / B5 / B8 / B20 / B28
**** Depending on network coverage
Read the operating instructions before installing the device and putting it into opera-
tion. Instruction manual is designated for mounting and also for user of the device. It is
always a part of its packing. Installation and connection can be carried out only by a per-
son with adequate professional qualifi cation upon understanding this instruction man-
ual and functions of the device, and while observing all valid regulations. Trouble-free
function of the device also depends on transportation, storing and handling. In case you
notice any sign of damage, deformation, malfunction or missing part, do not install this
device and return it to its seller. It is necessary to treat this product and its parts as elec-
tronic waste after its lifetime is terminated. Before starting installation, make sure that all
wires, connected parts or terminals are de-energized. While mounting and servicing ob-
serve safety regulations, norms, directives and professional, and export regulations for
working with electrical devices. Do not touch parts of the device that are energized – life
threat. To ensure the transmission of the radio signal, make sure that the devices in the
building where the installation is installed are correctly located. Unless otherwise stated,
the devices are not intended for installation in outdoor and damp areas, they must not
be installed in metal switchboards or in plastic cabinets with metal doors - this prevents
transmission of the radio frequency signal. iNELS Air is not recommended for control-
ling life-saving instruments or for controlling hazardous devices such as pumps, heaters
without thermostat, lifts, hoists, etc. - radio frequency transmission may be overshad-
owed by obstruction, interference, transmitter battery may be discharged etc., thereby
disabling the remote control.
1x 3.6V LS 14500 Li-SOCl
2
AA
1.9 years
3.2 years
3.6 years
3.6 years
5 – 12 V DC (on terminal)
+10 %; -15%
0.2 mW
850 mW
With a message from the server
using setting pins,
SET button, programming cable
message to the server
only when the battery is powered by a message
on the server
button SET
Tamper
IN1, IN2
LS (LED sensor)**
MS, WS (magnetic sensor)**
SO (Contact, open collector)
NB-IoT
LTE Cat NB1***
Approx. 30 km****
200 mW / 23 dBm
-30…+60°C (Pay attention to the operating
temperature of batteries)
-30…+70°C
any
glue / screws
IP65
terminals, wires 0.5 – 1 mm
2
terminals, wires 0.5 – 1 mm
2
M16 x 1.5 for cable ø max. 10 mm
136 x 62 x 34 mm
100 g (without battery)
Power supply
Battery power:
Battery life by frequency *:
1x 10 minutes
1x 60 minutes
1x 12 hours
1x 24 hours
External power supply:
Supply voltage tolerance:
Standby consumption:
Transmitting power consumption:
Setting
Setting:
Alarm Detection:
Battery status view:
Control
Control:
Digital inputs
Inputs:
Supported sensors for energy
measurements:
Communication
Protocol:
Transmitter frequency:
Range in open space:
Transmission power (max.):
Other parameters
Working temperature:
Storage temperature:
Operating position:
Mounting:
Protection degree:
Connecting External Power:
Connection of the sensor:
Cable gommet:
Dimension:
Weight:
The company ELKO EP, as the manufacturer, is entitled to make technical modifi cations to the product, in the technical specifi cation and product manual, without prior notifi cation.