4

 

ui5 = “ Li” -> liquid sensor visualized  (temperature can be visualized up to a value around 75°C. If water temperatu-

re sensor is upper 75°C the message “97.0” is visualized)

4 pipe systems operating mode

bPH

 

Proportional heating band

:

 

The proportional heating band is the part of heating output that changes proportionally with error signal. The setpoint 

is at the beginning of the proportional heating band.

 

Setting range: 

 

1,0

...

30,0 

 °C 

default value: 

5,0 

°C

bPC

 

Proportional cooling band

:

 

The proportional cooling band is the part of cooling output that changes proportionally with error signal. The setpoint 

for cooling is the setpoint added to neutral zone and is at the beginning of the proportional cooling band.

 

Setting range: 

 

1,0

...

30,0 

 °C 

default value: 

5,0 

°C

 

 

Output with only proportional action 

(without integral action)

tI

 

integral time

:

 

The integral time is the speed at which a corrective increase or decrease in ouput is made to compensate for offset 

which usually accompanies proportional only processes. The more integral time entered, the slower the action. The 

less integral time entered, the faster the action. A too small integral time can make the system oscillating. 

 

To exclude integral action and make the unit a proportional regulator set the value of parameter to 

noi

 with key +.

 

Setting range: 

 

1,0

...

30,0 

 minutes (with integral action) 

 

noI

 

(without integral action)

 

default value: 

20,0 

minutes

dEZ

 

Dead zone

:

 

It defines the dead zone between heat and cool where there is not any regulation (only for proportional action) 

Setting range: 

 

0,5

...

4,0 

°C 

default value: 

1,0 

°C

COr

 

Correction of temperature

:

 

It allows to add a value to the measured temperature to increase precision (let the unit switch on for 45 minutes before 

setting the parameter when the internal sensor is used)

 

Setting range:

 

-5,0

...

5,0 

°C 

default value: 

0,0 

°C

PoE

 

Method of regulation

 

It defines if unit operates with PI or P regulation or if the unit operates in manual test mode 

for doing some 

 

test on the system to regulate in open loop mode. This type of test can be used only if one has a measuring system 

for temperature. In order to see how to use this parameter see APPENDIX 2, page 9, method 3.

 

Setting range: 

 

0

...

10,0 

-> manual operating 

 

Pi

 -> 

proportional integral regulation 

default value: 

Pi 

ofS

 

Offset for economy function

:

 

It allows the change of setpoint position for economy function. The unit works with main setpoint if the contact ECO 

connected between terminals 3 and 12 is open. If contact is closed, the unit works with modified setpoint and increased 

neutral zone. See diagram below for more details.

 

Setting range: 

 

0

...

5,0 

°C 

default value: 

5,0 

°C

 

Summary of Contents for DB-TA-33A

Page 1: ......

Page 2: ...ay Wait for another 4 s until is visualized the room temperature on the display The parameters are then saved and the unit is ready to do the regulation Instruction for other parameters setting level 2 or 3 To access the parameters of level 2 or 3 proceed with the following procedure Push until the message PAS is visualized on the display several seconds Push the value 6 0 appears on the display P...

Page 3: ...n direct action tI Integral time The integral time is the speed at which a corrective increase or decrease in ouput is made to compensate for offset which usually accompanies proportional only processes The more integral time entered the slower the action The less integral time entered the faster the action A too small integral time can make the system oscillating To exclude integral action and ma...

Page 4: ... setpoint for economy function in cooling mode independently of main setpoint SEt The unit works with main setpoint if the contact ECO connected between terminals 3 and 12 is open If contact is closed the unit works with economy cooling setpoint if cooling mode is selected Setting range 6 0 45 0 C default value 25 0 C SoH Economy setpoint for heatin It defines the setpoint for economy function in ...

Page 5: ...e the unit a proportional regulator set the value of parameter to noI with key Setting range 1 0 30 0 minutes with integral action noI without integral action default value 20 0 minutes dEZ Dead zone It defines the dead zone between heat and cool where there is not any regulation only for proportional action Setting range 0 5 4 0 C default value 1 0 C COr Correction of temperature It allows to add...

Page 6: ... 0 10 V heating output if at the beginning of autotuning cycle temperature is lower than setpoint On this case autotuning is done in heating If temperature is upper than the setpoint at the beginning of the autotuning cycle the active 0 10 V output is the cooling output The autotuning is done on this case in cooling Choose a level that avoid high oscillations Setting range 0 10 0 V default value 5...

Page 7: ... or minimum value of para meter calculated is assigned For instance if Ti calculated is upper than 30 minutes Ti max Ti is set to 30 If Ti calculated is lower than 1 minute the value 1 minute is set to parameter Ti Setting range no YES default value no TECHNICAL FEATURES Power supply 24 Vac 10 50 60 Hz Sensor internal NTC 10K or remote sensor NT0220 NTC10 02 code Measuring range 0 55 C Setpoint ra...

Page 8: ...unting or H05VC F otherwise APPENDIX 1 Autotuning The regulator calculates optimum parameters PI for the room regulated and save them in EEPROM so that when the controller is powered up after being shut down the controller does not need to be autotuned again The regulator use the same parameters until the cycle is again initiated The autotune parameters are only good for the process the autotune f...

Page 9: ...on A proportional band with is correct in width approaches the setpoint as fast as possible while minimizing overshoot If a faster approach to setpoint is desired and process overshoot is not a problem a smaller or narrower proportional band may be used If process overshoot cannot be tolerated and the approach to setpoint does not have to be quick a larger proportional band can be choosen Integral...

Page 10: ...the value in half Change the setpoint a little and observe how the system is reacting If the system is still sluggish and does not oscillate tighten by decrease the value in half again 5 Repeat the point 4 until the system begins to oscillate constantly 6 Multiply last proportional band set by 2 Integral time added 1 Set a large integral time 2 Change the setpoint a little and observe how the syst...

Page 11: ...et parameter POE to PI in order to use the unit as an automatic regulator T2 T1 K POE2 POE1 Subject to change without notice Tight the screws on the wall box MOUNTING OF THE UNIT AND CLOSING OF THE COVER OPENING THE COVER MOUNTING ON THE WALL SURFACE 1 tight the screws on the wall box 2 connect cables 3 push on the cover MOUNTING 1 2 3 110 DB TA_33A_EN_210715 ...

Page 12: ......

Reviews: