MOTOR TROUBLESHOOTING

This chart suggests common answers to electric motor problems. The information is not 

all-inclusive and does not necessarily apply in all cases. When unusual operating conditions, 

repetitive failures, or other problems occur, consult an electric motor service firm.

Symptom

Possible Cause(s)

Corrective Action

Motor fails to start

1.  Blown fuses

1.  Replace with time-delay fuses. 

Check for grounded winding

2.  Voltage too low at motor 

terminals due to line drop 

2.  Consult local power company.  

Increase wire size (refer to 
Tables A & B).  Check for poor 
connections

3.  Overload in motor starter tripped  3.  Check and reset overload 

relay in starter.  Check heater 
rating against motor nameplate 
current rating 

4.  Overload (internal thermal 

protector) tripped 

4.  Check motor load.  If motor 

has an automatic or manual 
reset thermal protector, check 
if tripped

5.  Improper line connections 

5.  Check connections against 

diagram supplied with motor

6.  Motor may be overloaded

6.  Reduce load or increase motor 

size 

Motor does not come up to

speed or takes too long to

accelerate

1.  Not applied properly

1. 

Consult motor service firm for 

proper type. Use larger motor

2.  Voltage too low at motor 

terminals

2.  Increase wire size (refer to 

Tables A & B).  Check for poor 
connections.  Check for voltage 
unbalance (3-Phase) 

3.  Starting load to high

3.  Check load motor is carrying at 

the start

4.  Excess loading; tight belts

4.  Reduce load; increase motor 

size. Adjust belts

Summary of Contents for AZTech 1500iP

Page 1: ...1 Owners Manual AZTech Model 1500iP PORTABLE INDOOR AIR PURIFIER Contents Safety Inspection 2 Specifications 3 Installation 4 Replacement Parts 5 Electrical 6 Troubleshooting Notes 11 Warranty 17...

Page 2: ...liability if the unit is not operated according to this manual Do not use the Air Cleaner for an application other than for which it was intended Consult your distributor Applicable Codes or call Indu...

Page 3: ...45 lbs Power 115 1 60 Switch 15 cord Air Volume 1500 CFM 1 W G Motor 3 4 HP 115 1 60 PSC 9 1 FLA Blower 10 x 8 forward curve direct drive blower Exhaust 4 way aluminum exhaust grille Filters Prefilter...

Page 4: ...Model 1500iP requires no mechanical installation The unit is ready for operation once it is safely uncrated and all packaging is removed Please see the appendix for any optional equipment purchased w...

Page 5: ...11 0010 1 4 WAY EXHAUST GRILLE 11 FRO2 2424 1 24 X 24 X 2 PAD FRAME OPTIONAL 12 ELCD 1415 1 15 FT POWER CORD 13 MT41 1013 1 3 4 115 V 3 SPEED MOTOR 14 BW10 DD08 1 10 X 8 DIRECT DRIVE BLOWER 15 62 10 3...

Page 6: ...r cleaner to avoid over amping the motor voiding warranty Motor Starters wiring overloads and thermal protection are NOT provided by the Manufacturer All Field wiring should be performed by a qualifie...

Page 7: ...0kcmil 4 0 3 600kcmil 400kcmil 1 0 1250kcmil 800kcmil 4 0 150 350kcmil 250kcmil 2 700kcmil 500kcmil 2 0 1500kcmil 900kcmil 250kcmil 200 500kcmil 350kcmil 1 0 1250kcmil 800kcmil 4 0 1750kcmil 1250kcmil...

Page 8: ...3 6 12 3 8 1 0 6 2 0 4 4 0 3 5 10 6 4 2 1 7 1 2 8 6 3 1 1 0 10 8 4 2 1 0 2 0 Table B Minimum Wire Sizes for Single Phase Motors Type S SO SJ SJO etc Flexible cable wire sizes See NEC Article 400 for...

Page 9: ...or serviced by a qualified motor repair shop before operating Recommended Maintenance Remove dirt accumulations in and around vent openings by vacuuming Dirt accumulations can cause motor overheating...

Page 10: ...onths Heavy duty use in dirty dusty locations high ambients moisture laden atmosphere constant vibration 4 Months 4 Months 3 Months NOTE 1 Motors operating faster than 1800 RPM should be relubricated...

Page 11: ...nd reset overload relay in starter Check heater rating against motor nameplate current rating 4 Overload internal thermal protector tripped 4 Check motor load If motor has an automatic or manual reset...

Page 12: ...loaded bearings 4 Replace bearings check loading and alignment 5 Defective winding Bent or bowed shaft 5 Repair or replace 6 Loose sheave or misaligned coupling 6 Tighten set screw s realign coupling...

Page 13: ...ate or terminal box cover 2 Follow motor manufacturer s instructions for motor lubrication Remove excess lubricant 3 Follow Replacement Parts Manual for blower bearing lubrication 4 Check wiring to ma...

Page 14: ...Too much air flow 1 Blower speed too high 1 Check for correct drives 2 Filter s not in place 2 Install filter s Unit fails to operate 1 Blown fuse or open circuit breaker 1 Replace fuse or reset circu...

Page 15: ...ramming in the field Once programmed the cycle is saved to internal memory regardless of power loss Maintenance The GPS FC24 AC is designed to be maintenance free thanks to the patent pending self cle...

Page 16: ...____ HP________________________ VOLTAGE____________________MFG DATE__________________ VOLTAGE L1_______________________L2________________________L3____________________ AMP DRAW L1_____________________...

Page 17: ...apply to covered defects in Components that are discovered by Owner within the respective thirty six 36 months or twelve 12 months following the Invoice Date the Warranty Period and are reported to I...

Page 18: ...or any third party to a properly handle transport and or store any Industrial Maid Components b properly select and prepare a location that is adequate for where the Industrial Maid Components will be...

Page 19: ...COST PAID BY OWNER AS TO SUCH NON CONFORMING COST OF SUCH NON CONFORMING GOODS OR SERVICES C Limitation on the Nature of Damages EXCEPT AS EXPRESSLY PROVIDED IN SECTION 4 ABOVE INDUSTRIAL MAID SHALL N...

Reviews: