Electric Fail-Safe Device Installation, Operation & Maintenance Manual, 3A
Page 5
UNIT SPECIFICATIONS:
Enclosure rating:
NEMA 4; NEMA 4X & NEMA 7
Operating Voltages:
24vdc
10A Fail-Safe Output Fuse:
10 Amp, 250VAC, Slow Blow, 5x20mm
30A Fail-Safe Output Fuse:
40 Amp, 32VDC, Slow Blow, MEGA Cartridge
Light Indicators:
Green = Power; Yellow = Battery; Red = Mains ON
The following chart shows the Standard Fail-Safe Device Part Numbers and the related Specifications for
each unit.
There are 2 – 12vdc batteries in each Fail-Safe Device.
Part Number
Output
Voltage
Current
Output
Output
(Watts)
Battery
AHr
NEMA
Rating
Enclosure Dimensions
Weight
– lbs.
322-10E-CS4
24
10A
240
2 - 5
4
12”L x 12”W x 6”D
24
322-10E-SS4X
24
10A
240
2 - 5
4X
12”L x 12”W x 6”D
26
322-10E-AL7
24
10A
240
2 - 5
7
12”L x 12”W x 6”D
86
322-30E-CS4
24
30A
720
2 - 14
4
16”L x 16”W x 6”D
63
322-30E-SS4X
24
30A
720
2 - 14
4X
16”L x 16”W x 6”D
64
322-30E-AL7
24
30A
720
2 - 14
7
18”L x 18”W x 6”D
335
** NEMA 4X Enclosures are Stainless Steel.
WIRE SIZING AND LENGTHS:
Indelac recommends the Installer follow the wire gauge chart shown below when connecting the Fail-Safe
Device to the actuator. The Fail-Safe Device should be mounted at the shortest distance possible to the
actuator to assure best possible performance. Indelac DOES NOT recommend that the Fail-Safe Device
be mounted any further than 50 feet from the actuator.
24vdc Fail-Safe Device
16
14
12
10
8
Amperage
MAXIMUM Distance in Feet From Fail-Safe
10 Amp
10
20
30
50
70
30 Amp
-
-
10
15
25
WIRE GAUGE
WARNING!
WIRING MUST CONFORM TO ALL STATE AND LOCAL ELECTRICAL WIRING CODES.
THIS DEVICE SHOULD BE INSTALLED BY A LICENSED ELECTRICIAN.
IMPROPER POWER CONNECTION CAN RESULT IN DAMAGE TO THE COMPONENTS OR SERIOUS
INJURY TO THE INSTALLER.
VERIFY THAT ALL WIRES ARE DE-ENERGIZED BEFORE MAKING ELECTRICAL CONNECTIONS!
Summary of Contents for NEMA 4
Page 17: ...Electric Fail Safe Device Installation Operation Maintenance Manual 3A Page 17 NOTES ...
Page 18: ...Electric Fail Safe Device Installation Operation Maintenance Manual 3A Page 18 ...
Page 19: ...Electric Fail Safe Device Installation Operation Maintenance Manual 3A Page 19 ...
Page 20: ...Electric Fail Safe Device Installation Operation Maintenance Manual 3A Page 20 ...