REFRIGERANT FILLING PROCEDURE
Before charging the system, (by means of the charge fittings on the condenser unit and compressor
block) run vacuum cycle for 30 minutes.
Disconnect the high-pressure attachment.
Charge the system with
17.6oz (500 grams) R-134a
into the circuit through the low-pressure
attachment.
Switch the Sleeping Well Arctic Plus on for 10 minutes before disconnecting the charging hose(s).
When the refrigerating charge cycle is over, check for leaks and proper operation of the system.
WARNING: Compressors use POE oil. DO NOT mix PAG oil from previous systems
when charging.
ATTENTION: If you cut the G6 refrigerant hose (kit comes with 13ft of G6 hose), consider that
for every 3 feet cut, you have to reduce the charging by 1.4oz (MINIMUM CHARGE = 14.1oz).