Incon TS-STS Quick Start Manual Download Page 5

Setup>System menu

 Continued...

COLD BOOT

(Replaces 

all

 custom-setup data with default values)

IF YOU CONTINUE, ALL SYSTEM PROGRAMMING

AND DATA WILL BE LOST...

:

PRESS ENTER IF YOU ARE SURE THAT

YOU WANT TO CONTINUE WITH COLD BOOT

Setup>Sumps menu

SUMPS

DATA

N = Sump number

SUMP DATA

SUMP 1

Select sump and program new name

SUMP 2

:

SUMP 4

SUMP DATA N

NAME

(Rename the sump using a

SUMP NAME N

 Code-Name for each Sump)

SUMP N

 code-names can be up to 7
 alphanumeric characters long

(e.g. ULD SMP, SUP SMP, DSP 1-2)

Setup Menu

EXIT

SYSTEM

SUMPS

CLK/CAL

COM PORTS

Setup>System menu

SYSTEM INFO

SYSTEM ID

(customize the Site ID information)

LINE 1

LOCATION LINE 1

(input 24 characters Max)

INCON

Enter the Business Name

LINE 2

LOCATION LINE 2

(input 24 characters Max)

INTELLIGENT CONTROLS INC

Enter other Business data

LINE 3

LOCATION LINE 3

(input 24 characters Max)

P.O. BOX 638

Enter the Street Address

LINE 4

LOCATION LINE 4

(input 24 characters Max)

SACO ME 04072

Enter the City and Zip code

LINE 5

LOCATION LINE 5

(input 24 characters Max)

1-800-984-6266

Enter the Business Number

NO. SUMPS

(enter total number of sumps [4 max.])

NUMBER OF SUMPS

1

SUMP TST

(sump leak test, start time + leak limit)

START TIME

(Do not set when tests are started from the front panel)

SUMP TEST START TIME

Tests are 15 minutes in length

00.28.00

(12:28 am in 24 hour format)

Input time in 24 hour format...

 Add 12 to pm times from 1 to 11:59 pm

LEAK LIM

LEAK LIMIT

0.002

(

There is a fixed threshold of .002 level units.

)

NOTE: The Leak Limit Threshold of 0.002 is

 

not 

an adjustable setting.This is a fixed

 

value.

Pg 5

Summary of Contents for TS-STS

Page 1: ...Federal and State regulations for leak limit and test time requirements Recommendations for locating the TS STS console outside of the Class I Division 1 Group D Hazardous Areas during testing are based on NFPA 30 NFPA 30A and NFPA 70 NEC TS STS Sump Test System Quick Start Guide INCON P N 000 3004 Rev D Feb 2009 www fraklinfueling com This document may change without prior notice INCON is a Regis...

Page 2: ... DISPENSOR SUMPS IN GROUPS SO OTHER DISPENSORS ARE LEFT IN SERVICE DURING TESTING GROUNDED 3 PRONG EXTENSION CORD REQ D SAFETY CONES DISPENSER 7 8 DISPENSER 5 6 Pg 2 SPLIT RING TS STS SUMP TEST SYSTEM SUMP TEST SYSTEM FLAT METAL ANGLE IRON REQUIRED TO SUSPEND PROBE SIDE VIEW TS STS STS PRB 12 LEAK TESTING PROBE WITH TSP SSP STAINLESS STEEL FLOAT DISPENSER SUMP WITH TEST SOLUTION Side View RECEPTAC...

Page 3: ...TH TSP SSP STAINLESS STEEL FLOAT TURBINE SUMP WITH TEST SOLUTION Side View POWER CORD WITH A GROUNDED 3 PRONGED PLUG 3 RECEPTACLES FOR FOUR SCREW IN PROBE CABLE PLUGS 1 2 4 SUMP TAPE WEIGHT DOWN CABLE TO PREVENT ACCIDENTAL MOVEMENT DURING LEAK TESTING PROBE CABLE PN 600 0200 50 FEET Turbine Sump 2 TS STS SUMP TEST SYSTEM GROUNDED 3 PRONG EXTENSION CORD REQ D SAFETY CONES BUILDING SUMP TEST SYSTEM ...

Page 4: ... left Use M2 to move the cursor to the right Use M4 to backspace delete text to the left of the cursor Follow the highlighted sequence at left to program the console Menus are in indented format lower levels to the right The setup program factory default settings are shown in ITALIC TEXT The console will auto exit the setup mode if no key is pressed after 3 minutes Minimum Setup Requirements 1 Fro...

Page 5: ...r the Business Name LINE 2 LOCATION LINE 2 input 24 characters Max INTELLIGENT CONTROLS INC Enter other Business data LINE 3 LOCATION LINE 3 input 24 characters Max P O BOX 638 Enter the Street Address LINE 4 LOCATION LINE 4 input 24 characters Max SACO ME 04072 Enter the City and Zip code LINE 5 LOCATION LINE 5 input 24 characters Max 1 800 984 6266 Enter the Business Number NO SUMPS enter total ...

Page 6: ...EEK Select the current day SUNDAY MONDAY TUESDAY WEDNESDAY THURSDAY FRIDAY SATURDAY 3 SYSTEM SUMP OKAY OKAY SYSTEM SUMP WARNING OKAY SYSTEM SUMP NO PAPER OKAY SYSTEM SUMP OKAY OKAY SYSTEM SUMP OKAY TEST LEVEL SUMP 1 SUMP 2 SUMP 3 SUMP 4 INCHES 2 01 3 09 1 76 3 12 SELECT FUNCTION 10 39 08 AM 10 29 2001 DISPLAY PRINTER SYSTEM SUMP OKAY LEAK Displays 1 Normal Display 2 Press the Check key to check th...

Page 7: ...on demand from the keypad The Sump Leak Test and Alarm Reports print automatically The other reports such as the Sump Level Reports Alarm Reports and Sump Test Reports can be printed on demand Press the menu select keys and choose the type of report that you wish to printout Alarm reports will print as soon as an alarm is detected Leak test reports print automatically after the leak test is finish...

Page 8: ...rt can be retrieved from the TS STS console through the communications port Comm Port 1 This port is located at the bottom side As with the printed reports this data is overwritten when a new test is run so it must be collected after each test The data can be stored in a database as opposed to saving the printouts For more information on this feature contact INCON Technical Service at 1 800 984 62...

Reviews: