Incon TS-STS Quick Start Manual Download Page 1

TS-STS 

Sump Test System

Quick Start Guide

TS-STS Overview

The TS-STS system includes a TS-STS console within a convenient
portable case, leak testing probes with 50 feet of cable, and probe
hanging hardware (slip rings and chain).

After all fittings within the sump are sealed, the sump is filled with a
water-based test solution that covers all sump penetration holes. The
probe is installed so the float is floating on the surface of the test solution.
The TS-STS console is quickly programmed with the site name and
address, number of sumps, the 7-digit code-names for each sump, and
the correct Time/Day/Date before leak testing.

Pressing the 

Test

key at the console keypad starts sump leak tests for

all sumps. The test time is 15 minutes and tests for a level change
greater than 0.002 inches.  If the level of a sump drops more than the
leak limit during the test, the Sump Leak Test Report will show a fail
result when the test  is finished.  Leak tests can also be programmed
(scheduled) to start at desired times.

When finished, leak test reports will automatically print out at the console
printer. Extra copies of this report can be printed using the report key. A
newly completed Sump Leak Test will overwrite the previous results
stored in memory.  Save sump leak test reports and provide copies as
evidence of compliance with regulations.

Recommendation:  Use a computer and the Tech version of

System Sentinel™ to record site data, sump code-names, and test

results. Test results can also be extracted from Comm Port 1 at

the bottom of the TS-STS console  (also see Section 4).
Reference Federal and State regulations for leak limit and test

time requirements.  Recommendations for locating the TS-STS

console outside of the (Class 

I

, Division 1, Group D) Hazardous Areas

during testing, are based on NFPA 30, NFPA 30A and NFPA 70 (NEC).

TS-STS 

Sump Test System

Quick Start Guide

INCON  P/N 000-3004 Rev.D  Feb. 2009  ©   

www.fraklinfueling.com

This document may change without prior notice.  

INCON

®

 is a Registered Trademark of Franklin Fueling Systems

TS-STS Installation

1

Pg 1

NOTE

1.)

Required Materials:

a.) Tape to secure the probe cable

b.) Safety cones &  signs

c.) Grounded, 3-pronged extension cord

d.) Flat pieces of metal to suspend leak testing probe over sumps

2.)

Work safely — install Safety Cones and Signs at the site

3.)

The probes are precision instruments — handle with care!

4.)

The STS probes are shipped with cables attached, do not remove
the cable from the probe end... remove at the console case 

only

.

5.)

Inspect probes for proper float movement before use, then install
probes as shown in Section 1

6.)

Connect the yellow probe cables to the receptacles at the TS-STS
case.

 Make sure to line up keyways before inserting cable and

tightening the screw-on connector.

7.)

Locate the TS-STS case outside of the Hazardous Area and tape
the cable down to prevent probe movement during the test and to
reduce tripping hazards

8.)

Setup / Program the TS-STS console per Section 2

9.)

Start sump leak test(s) on sumps that are ready

10.) Always clean, dry, and store probes in the probe carrying case after

each use

11.) Test each of the probes on a monthly basis to ensure its ability to

detect leaks. Install the probe in a test container and initiate a test.
After 5 minutes, remove about 0.12 inches of water. When the test
completes, the test report should show a 

Failed

 result if the probe

is working properly.

Summary of Contents for TS-STS

Page 1: ...Federal and State regulations for leak limit and test time requirements Recommendations for locating the TS STS console outside of the Class I Division 1 Group D Hazardous Areas during testing are based on NFPA 30 NFPA 30A and NFPA 70 NEC TS STS Sump Test System Quick Start Guide INCON P N 000 3004 Rev D Feb 2009 www fraklinfueling com This document may change without prior notice INCON is a Regis...

Page 2: ... DISPENSOR SUMPS IN GROUPS SO OTHER DISPENSORS ARE LEFT IN SERVICE DURING TESTING GROUNDED 3 PRONG EXTENSION CORD REQ D SAFETY CONES DISPENSER 7 8 DISPENSER 5 6 Pg 2 SPLIT RING TS STS SUMP TEST SYSTEM SUMP TEST SYSTEM FLAT METAL ANGLE IRON REQUIRED TO SUSPEND PROBE SIDE VIEW TS STS STS PRB 12 LEAK TESTING PROBE WITH TSP SSP STAINLESS STEEL FLOAT DISPENSER SUMP WITH TEST SOLUTION Side View RECEPTAC...

Page 3: ...TH TSP SSP STAINLESS STEEL FLOAT TURBINE SUMP WITH TEST SOLUTION Side View POWER CORD WITH A GROUNDED 3 PRONGED PLUG 3 RECEPTACLES FOR FOUR SCREW IN PROBE CABLE PLUGS 1 2 4 SUMP TAPE WEIGHT DOWN CABLE TO PREVENT ACCIDENTAL MOVEMENT DURING LEAK TESTING PROBE CABLE PN 600 0200 50 FEET Turbine Sump 2 TS STS SUMP TEST SYSTEM GROUNDED 3 PRONG EXTENSION CORD REQ D SAFETY CONES BUILDING SUMP TEST SYSTEM ...

Page 4: ... left Use M2 to move the cursor to the right Use M4 to backspace delete text to the left of the cursor Follow the highlighted sequence at left to program the console Menus are in indented format lower levels to the right The setup program factory default settings are shown in ITALIC TEXT The console will auto exit the setup mode if no key is pressed after 3 minutes Minimum Setup Requirements 1 Fro...

Page 5: ...r the Business Name LINE 2 LOCATION LINE 2 input 24 characters Max INTELLIGENT CONTROLS INC Enter other Business data LINE 3 LOCATION LINE 3 input 24 characters Max P O BOX 638 Enter the Street Address LINE 4 LOCATION LINE 4 input 24 characters Max SACO ME 04072 Enter the City and Zip code LINE 5 LOCATION LINE 5 input 24 characters Max 1 800 984 6266 Enter the Business Number NO SUMPS enter total ...

Page 6: ...EEK Select the current day SUNDAY MONDAY TUESDAY WEDNESDAY THURSDAY FRIDAY SATURDAY 3 SYSTEM SUMP OKAY OKAY SYSTEM SUMP WARNING OKAY SYSTEM SUMP NO PAPER OKAY SYSTEM SUMP OKAY OKAY SYSTEM SUMP OKAY TEST LEVEL SUMP 1 SUMP 2 SUMP 3 SUMP 4 INCHES 2 01 3 09 1 76 3 12 SELECT FUNCTION 10 39 08 AM 10 29 2001 DISPLAY PRINTER SYSTEM SUMP OKAY LEAK Displays 1 Normal Display 2 Press the Check key to check th...

Page 7: ...on demand from the keypad The Sump Leak Test and Alarm Reports print automatically The other reports such as the Sump Level Reports Alarm Reports and Sump Test Reports can be printed on demand Press the menu select keys and choose the type of report that you wish to printout Alarm reports will print as soon as an alarm is detected Leak test reports print automatically after the leak test is finish...

Page 8: ...rt can be retrieved from the TS STS console through the communications port Comm Port 1 This port is located at the bottom side As with the printed reports this data is overwritten when a new test is run so it must be collected after each test The data can be stored in a database as opposed to saving the printouts For more information on this feature contact INCON Technical Service at 1 800 984 62...

Reviews: