OVERVIEW
This device is an assembly of an
HFW
-
SIM
-
01
-
AS
Hyfire system interface module and a
HFC
-
WSR
-
03
conventional sounder /
HFC
-
SBR
-
23
-
03
conventional s visual alarm device. Sounder’s output is activated following an alarm condition of the Hyfire system.
INSTALLATION
-
IMPORTANT NOTES
-
The device must be installed following your national and/or international codes of practice and standards: check them before performing
the
installation of this device.
-
Test this device after installation.
HFW
-
SIM
-
01
-
AS + HFC
-
WSR
-
03
HFW
-
SIM
-
01
-
AS + HFC
-
SBR
-
23
-
03
HYFIRE TYPE B WALL SOUNDER
HYFIRE TYPE B WALL S VISUAL ALARM DEVICE
INSTALLATION
1)
Detach the front operating section from the sounder back box (→
SOUNDER OPENING PROCEDURE
).
2)
Extract the
HFW
-
SIM
-
01
-
AS
from the sounder’s back box (→
MODULE’S EXTRACTION
).
3)
Set the
HFW
-
SIM
-
01
-
AS
’s link switch to ON.
4)
Extract the
HFW
-
SIM
-
01
-
AS
’s battery covers.
5)
Insert both batteries into their
HFW
-
SIM
-
01
-
AS
holders, oriented as per polarity marks.
6)
Link the
HFW
-
SIM
-
01
-
AS
device to the Hyfire system (→
LINKING
).
7)
Reinstall the battery covers.
8)
Check the wireless link quality of the
HFW
-
SIM
-
01
-
AS
positioned in the final installation location (→
WIRELESS LINK QUALITY
CHECK
).
9)
Install the sealing pad if the sounder is to be installed outdoors and/or in damp environments (
not EN 54
-
3 approved
)
(→
OUTDOORS AND DAMP ENVIRONMENTS INSTALLATION
).
10)
Fix the sounder back box to the wall on the final installation location (→
WALL INSTALLATION
).
11)
Reinstall the
HFW
-
SIM
-
01
-
AS
into the sounder’s back box (→
MODULE’S INSTALLATION
).
12)
Set sounder’s tone and volume (→
OUTPUT TONE SETTING
, →
OUTPUT VOLUME SETTING
).
13)
Reinstall the front operating section onto the sounder back box (→
SOUNDER CLOSING PROCEDURE
).
14)
Test the
HFW
-
SIM
-
01
-
AS + HFC
-
WSR
-
03
/
HFC
-
SBR
-
23
-
03
to check if it works properly (→
TESTING
).
Summary of Contents for HFC-SBR-23-03