26
5. Replace the controller lid and tighten screws.
6. Reconnect power to the device.
If you want to use RuggedCable with twist-lock connectors, order a short length of stripped-and-
tinned RuggedCable with a male connector. This can be wired into the controller, then
connected to existing twist-lock cable connectors.
Figure 5.2 Earth ground
Current Loop Outputs
Danger—Make sure that power to the instrument is disconnected before making any wiring connections.
Danger—The maximum voltage that can be applied across the loop terminals is 36 V.
Sorties De Courant De Boucle
Danger—Débrancher toute alimentation à l'appareil avant de connecter les fils.
Danger—La tension maximum à travers la boucle ne doit pas excéder 36 V.
1. Disconnect power to the instrument.
2. Use a Phillips screwdriver to remove the controller lid.
3. Connect the stripped-and-tinned, twisted-pair shielded, 24-12 AWG, 4-20 mA wires to the terminal strip and
Protective Earth (ground) as follows.
LOOP2–
To negative (-) end of
customer-supplied device
LOOP2+
To positive (+) end of
customer-supplied device
LOOP1–
To negative (-) end of
customer-supplied device