Functional description

The IMT-L4 provides automatic shutdown of multiple file servers supported by a single IMV
VICTRON UPS. Each file server must be running IMV VICTRON's shutdown software or
have its own integrated UPS monitoring and shutdown facility. To increase data security, the
UPS can be turned off after all the connected servers have been shut down safely.
In addition, the IMT-L4 is capable of supervising the connection between the UPS and
the IMT-L4. Please note that more than four servers can be supported by "daisy-chaining"
IMT-L4 units together. All signal connections are carried out free of potential.

Suitable uninterruptible power supplies (UPS)

The IMT-L4 is designed for use with all IMV VICTRON UPS with ComConnect interfaces.

Contents of the IMT-L4 kit and additional equipment

The IMT-L4 kit includes the following:

1 IMT-L4

1 AC-adaptor (230 V, 50 / 60 Hz)

1 UPS connecting cable (DB9 male to DB9 female)

 this manual

UPS connecting cables and daisy-chain cables are also available in lengths up to 100 m.
Please contact your distributor for details.

UPS connecting cable

Please connect the IMT-L4 and UPS using the interface cable. Connect the DB9 male
connector to the connector labeled 'UPS' on the back of the IMT-L4. Connect the DB9
female connector to the ComConnect interface connector on your IMV VICTRON UPS.
The connection cable(s) from the computer(s) to the IMT-L4 should be labeled VIC28 for
UNIX and VIC25 in all other cases.

ATTENTION ! : Use shielded cables only. Shield must be connected to your UPS' ground!

AC-adaptor

The IMT-L4 is delivered together with an AC/AC adaptor. This adaptor has a CEE22-plug and is de-
signed for input voltages of 230 Volts AC at 50 / 60 Hz. The adaptor is connected to the IMT-L4 by
the jack marked AC IN on the back of the IMT-L4.

NOTE: The AC-adaptor has to be plugged into the output circuit of the UPS