Imron Corporation S0-16 Installation And Specification Download Page 5

 

 

Imron Corporation   15375 Barranca Pkwy, Suite B-106

Irvine, CA 92618  Phone 949-341-0947  Fax 949-341-0949

 

 

INTEGRATED SYSTEM 2000  

 

SO-16 OUTPUT PROCESSOR

 

System Control Processor

 

7. Specification: 

 

The sub-controller is for use in low voltage, class 2 circuit only. 

 

Primary power:   

(DC or AC) 

 

DC input: 

12Vdc±10%, 350mA 

 

AC input: 

12Vac±15%, 500mA RMS 

 

Relay Contacts:  

16 form C, 5A 28Vdc, Resistive. 

 

Inputs:   

 

2 non-supervised, normally closed contacts for Tamper and power fault 

Wire requirement: 

 

Power:   

1 twisted pair, 18 AWG 

 

RS-485: 

24AWG, 4,000ft (1,200m) max., twisted pair(s) with shield. 

 

Alarm input: 

1 twisted pair, 30 ohms max. 

 

Output:  

As required for the load 

 

 

Environmental: 

 

Temperature:  0 to 70 °C, operating 

 

 

 

-55 to +85 °C, storage 

 

Humidity: 

0 to 95% RHNC 

 

Mechanical: 

 

Dimension: 

6 in. (152mm) W x 8 in. (203mm) L x 1 in. (25mm) H 

 

Weight:  

10 oz (290 gm) nominal 

 

 

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: 

(1)  This  device  may  not  cause  harmful  interference,  and  (2)  this  device  must  accept  any  interference 

received, including interference that may cause undesired operation. 

 

Summary of Contents for S0-16

Page 1: ...rocessor Installation and Specification 1 General The SO 16 sub controller provides output controls for system integrators in security access control and other application The controller has 16 form C contacts for load switching In addition 2 digital inputs may be used for tamper and UPS status monitoring The sub controller requires either 12Vdc or 12Vac for power ...

Page 2: ...to the unit as possible Connect power with minimum of 18AWG wires Observe POLARITY for 12Vdc application 3 Communication Wiring The SO 16 communicates to host via a RS 485 interface which may be configured for either 2 wire or 4 wire operation The interface allows multi drop communication on a single bus of up to 4 000 feet 1 200 m Use twisted pair s minimum 24 AWG with shield for the communicatio...

Page 3: ...r s If these inputs are not used install a short piece of wire at the input to indicated safe condition 5 Relay Outputs The following show typical use of the relay outputs DC source is recommended whenever it is possible Transient clamping must be provided to protect the contact and to reduce EMI emission Use sufficiently large wires for the load current to avoid voltage loss 6 DIP Switch Usage Sw...

Page 4: ... ON OFF ON OFF ADDRESS 10 OFF ON OFF ON ON ADDRESS 11 OFF ON ON OFF OFF ADDRESS 12 OFF ON ON OFF ON ADDRESS 13 OFF ON ON ON OFF ADDRESS 14 OFF ON ON ON ON ADDRESS 15 ON OFF OFF OFF OFF ADDRESS 16 ON OFF OFF OFF ON ADDRESS 17 ON OFF OFF ON OFF ADDRESS 18 ON OFF OFF ON ON ADDRESS 19 ON OFF ON OFF OFF ADDRESS 20 ON OFF ON OFF ON ADDRESS 21 ON OFF ON ON OFF ADDRESS 22 ON OFF ON ON ON ADDRESS 23 ON ON ...

Page 5: ...and power fault Wire requirement Power 1 twisted pair 18 AWG RS 485 24AWG 4 000ft 1 200m max twisted pair s with shield Alarm input 1 twisted pair 30 ohms max Output As required for the load Environmental Temperature 0 to 70 C operating 55 to 85 C storage Humidity 0 to 95 RHNC Mechanical Dimension 6 in 152mm W x 8 in 203mm L x 1 in 25mm H Weight 10 oz 290 gm nominal This device complies with part ...

Page 6: ...horize any agent or representative to make any other warranties or implied warranties and expressly excludes and disclaims all implied warranties of merchantability or fitness for a particular purpose Returned units are repaired or replaced from a stock of reconditioned units Returns must be accompanied by a return authorization number RMA obtained from customer service and prepaid postage and ins...