background image

 

XOT300-0-0-GB-02 

July 2009 

Page 2 

 

INSTALLATION INFORMATION 

Accessories 

Find the following when unpacking the Terminal: 

 

An ImproX O16 16 Channel Output Terminal housed in a Black powder-coated 
Aluminium extruded Cabinet.  The Cabinet is sealed at each end with a Nylon End 
Plate, secured with 4 Allen Head Screws (M3 x 12 mm).   

 

Two Plastic Bushing Plugs (20.6 mm). 

 

A 2.5 mm Allen Key.  

 

Four Brass Wood Screws (3.5 mm x 25 mm). 

 

Four Wall Plugs (7 mm). 

 

An extra Fixed Address Label. 

General 

Remember the following when installing the Terminal: 

Communications Distance 

The RS485 communications distance between the first ImproX Controller and the LAST 
ImproX unit in a cable run, MUST NOT exceed 1 km (1 094 yd).  Achieve this by using 
good quality screened twisted pair cable, with the screen EARTHED at one end. 

Jumper Links 

Long transmission lines 

or multiple “star” connections, may cause communication 

problems.  Placing a Jumper Link across the jumper [LNK1] in the LAST UNIT AT THE 
END OF THE CABLE RUN should solve the problem. 

EARTH Connection 

Connect the Terminal to a good EARTH point.  Using the RS485 Port, connect the 
EARTH Lead to the 

„ETH‟ Terminal.  Mains EARTH can be used, but electrical noise 

may exist. 

 

 

 

 

 

 