1.19 FLUES, CHIMNEYS, CHIMNEY POTS 

AND TERMINALS.

The flues, chimneys and chimney pots for the 

evacuation of combustion products must be in 

compliance with applicable standards. Chimneys 

and roof-installed exhaust terminals must com-

ply with the outlet height and with the distance 

from technical volumes set forth by the technical 

standards in force.

Positioning the wall flue exhaust terminals.

 The 

wall flue exhaust terminals must:

- be installed on external perimeter walls of the 

building;

- be positioned according to the minimum dis-

tances specified in current technical standards.

Combustion products exhaust of natural draught 

or fan assisted appliances in open-top closed 

environments. In spaces closed on all sides with 

open tops (ventilation pits, courtyards etc.), 

direct flue gas exhaust is allowed for natural or 

forced draught gas appliances with a heating 

power range from 4 to 35 kW, provided the 

conditions as per the current technical standards 

are respected.

1.20 SYSTEM FILLING.

Once the boiler is connected, proceed with 

system filling via the filling cock (Fig. 1-29 and 

2-8). Filling is performed at low speed to ensure 

release of air bubbles in the water via the boiler 

and heating system vents.

The boiler has a built-in automatic venting valve 

on the circulator. 

Check if the cap is loose.

 Open 

the radiator vent valves.

Close radiator vent valves when only water 

escapes from them.

Close the filling cock when the boiler pressure 

gauge indicates approx. 1.2 bar. 

N.B.:

 during these operations, turn on the circu-

lating pump at intervals using the main switch on 

the control panel. 

Vent the circulation pump by 

loosening the front cap and keeping the motor run-

ning.

 Screw the cap back on after the operation.

1.21 CONDENSATE TRAP FILLING.

On first lighting of the boiler, flue gas may come 

out the condensate drain; after a few minutes’ 

operation check that this no longer occurs. This 

means that the drain trap is filled with conden-

sate to the correct level preventing the passage 

of flue gas.

1.22 GAS SYSTEM START-UP.

To start up the system, refer to the technical 

standard in force. 

In particular, for new gas systems:

- open windows and doors;
- avoid presence of sparks or open flames;
- bleed all air from the pipelines;
-  check that the internal system is properly sealed 

according to the specifications set forth by 

technical regulations in force.

1.23 BOILER START UP (IGNITION).

To commission the boiler (the operations listed 

below must only be performed by qualified per-

sonnel and in the presence of professionals only):

-  check that the internal system is properly sealed 

according to the specifications set forth by 

technical regulations in force;

-  make sure that the type of gas used corresponds 

to boiler settings;

- Check that there are external factors that may 

cause the formation of fuel pockets; 

-  switch the boiler on and check correct ignition;
- make sure that the gas flow rate and relevant 

pressure values comply with those given in the 

manual (Par. 3.18);

- ensure that the safety device intervenes in the 

event of gas supply failure and check the relative 

intervention time;

- check the intervention of the main switch 

located upstream from the boiler and in the 

boiler;

- check that the intake/exhaust concentric ter-

minal (if fitted) is not blocked.

The boiler must not be started up even if only 

one of the checks should be negative.

Summary of Contents for VICTRIX ZEUS SUPERIOR 26 2 ERP

Page 1: ...VICTRIX ZEUS SUPERIOR 26 2 32 2 ERP Instruction and recommendation booklet IE 1 037935ENG...

Page 2: ......

Page 3: ...in the regulations in force and principles of good practice In compliance with legislation in force the systems must be designed by qualified professionals within the dimensional limits established b...

Page 4: ...e 20 2 2 General warnings 20 2 3 Control panel 20 2 4 Description of functioning states 21 2 5 Using the boiler 22 2 6 Troubleshooting 23 2 7 Parameters and information menu 25 2 8 Boiler shutdown 26...

Page 5: ...lve must be conveyed away by a draining funnel or if there are leaks from the hydraulic connections on the contrary the manufacturer cannot be held responsible for any damage caused to the household a...

Page 6: ...uid must be followed scrupulously regarding the percentage neces sary with respect to the minimum temperature at which the system must be kept An aqueous solution must be made with potential pollution...

Page 7: ...et the system requirements es tablished by the technical regulation in force in relation to the pollution of drinking water we recommend installing the IMMERGAS anti backflow kit to be used upstream o...

Page 8: ...be set to On Off mode CAR V2 Super CAR or On Off chrono ther mostat electrical connection Optional The operations described below must be performed after having removed the voltage from the appli ance...

Page 9: ...efore varies according to applica tions for air intake or flue exhaust Each single component has a resistance corresponding to a certain length in metres of pipe of the same diameter the so called equ...

Page 10: ...Intake and Exhaust 16 3 m 2 5 Intake m 18 7 Exhaust m 4 9 m 7 7 Exhaust m 13 6 Concentric intake exhaust terminal 60 100 vertical Intake and Exhaust 9 m 1 4 Intake m 10 3 Exhaust m 2 7 m 4 3 Exhaust m...

Page 11: ...in the female end with lip seal of the 80 flange unit until it stops Introduce the gasket making it run along the bend Fix it using the sheet steel plate and tighten by means of the straps present in...

Page 12: ...with the boiler flange and tighten using the screws supplied with the kit Fit the 60 100 3 concentric terminal pipe with the male side smooth to the female side of the bend 2 up to the end stop makin...

Page 13: ...cal length of 14 4 m including the terminal This configuration corresponds to a resistance factor of 100 In this case specific extensions must be requested Vertical kit with aluminium tile 80 125 Kit...

Page 14: ...oth in the female side of the bend 5 up to the end stop ensuring that the internal and external wall sealing plates are fitted Fit the exhaust pipe 9 with the male side smooth to the female side of th...

Page 15: ...ical data The dimensions of the shafts must ensure a minimum gap between the outer wall of the smoke duct and the inner wall of the shaft 30 mm for circular section shafts and 20 mm in the event of a...

Page 16: ...s length is obtained considering the complete 80 exhaust terminal 1m of 80 pipe in ex haust two 90 80 bends on the boiler outlet 1 17 CONFIGURATION TYPE B OPEN CHAMBER AND FAN ASSISTED FOR INDOORS The...

Page 17: ...ervals using the main switch on the control panel Vent the circulation pump by loosening the front cap and keeping the motor run ning Screw the cap back on after the operation 1 21 CONDENSATE TRAP FIL...

Page 18: ...speed varies to maintain the T constant between the system flow and return accord ing to set value K Fixed 100 65 in this mode the cir culator works at constant speed the operating range is defined b...

Page 19: ...e functioning possibilities Cover kit on request If installed outdoors in a partially protected place with direct air intake it is compulsory to mount the appropriate top protection cover for the corr...

Page 20: ...rect vapours from cooking hobs Use of the boiler by unskilled persons or children is prohibited For safety purposes check that the concentric air intake flue exhaust terminal if fitted is not blocked...

Page 21: ...uest for domestic hot water or central heating in order to evacuate residual flue gas F5 Postcirculation in progress Pump in function after a request for domestic hot water or central heating in order...

Page 22: ...ection it decreases During domestic hot water heating DHW ON appears on the display 24 on the status indicator 6 and at the same time as the burner ignites the flame presence indicator switches on 8 w...

Page 23: ...pressure is between 1 1 2 bar and restore the correct pressure if necessary 12 Storage tank probe anomaly The board detects an anomaly on the storage tank probe The boiler cannot produce domestic hot...

Page 24: ...flame signal This occurs when the boiler is ignited correctly and the burner flame switches off unexpectedly a new ignition attempt is performed and if normal conditions are restored the boiler does...

Page 25: ...vels of the menu and the choice of parameters is confirmed Press button C to go back one level M1 information menu This menu contains the various information relative to boiler functioning 1st Level B...

Page 26: ...i freezeliquidandinstallation of the Immergas Anti freeze Kit in the boiler In the case of prolonged inactivity second case we also recommend that disconnect the electric power supply fully drain the...

Page 27: ...efficiency of water circuits check ventilation and or aeration of the instal lation room where provided If even only a single safety check offers a negative result do not commission the system 3 1 PLU...

Page 28: ...ed by the drain trap being blocked Check by means of the condensate drain cap that there are no residues of material blocking the flow of condensate Noise due to air in the system Check open ing of th...

Page 29: ...casing mounted while the gas valve calibration operations must be carried out with the casing open and disconnecting the boiler from the power supply Calibration of the minimum CO2 minimum heating pow...

Page 30: ...on the domestic hot water probe on entry to the boiler P54 2 Displays the temperature read on the domestic hot water probe on exit from the boiler P54 3 Displays the temperature read on the return pr...

Page 31: ...in the cylinder falls by 3 C with respect to the temperature set Solar function deactivated P71 1 P71 2 5 C Boiler ignition for heating the domestic hot water occurs when the water contained in the cy...

Page 32: ...p at least once every 24 hours for the duration of 30 seconds in order to reduce the risk of the pump becoming blocked due to prolonged inactivity 3 11 THREE WAY ANTI BLOCK FUNCTION Both in domestic h...

Page 33: ...that it is properly fixed to the combustion chamber lid otherwise it must be replaced Visually check that the water safety drain valve is not clogged Check that after discharging system pressure and b...

Page 34: ...wer grid 1 by taking out the 4 fastening screws 2 Open the control panel door 3 remove the 2 white screw caps 4 and take out the 2 fasten ing screws 5 tilt the panel towards you Unscrew the 2 6 fasten...

Page 35: ...0 92 9 4 0 81 1 28 13 1 9 0 7740 1 00 0 73 7 4 0 75 0 77 7 9 0 73 1 09 11 1 8 0 6880 0 89 0 59 6 0 0 67 0 64 6 5 0 66 0 90 9 2 7 0 6020 0 78 0 46 4 7 0 59 0 52 5 3 0 58 0 73 7 5 6 0 5160 0 67 0 35 3...

Page 36: ...lue temperature at nominal output C 78 86 79 Flue temperature at minimum output C 73 82 75 Victrix Zeus Superior 32 2 ErP Gas nozzle diameter mm WITHOUT 6 00 6 00 Flue flow rate at nominal heat output...

Page 37: ...xpansion vessel pre charge bar 2 5 2 5 Appliance water content l 6 7 9 1 Head available with 1000 l h flow rate kPa m H2 O 26 0 2 65 29 0 2 95 Hot water production useful heat output kW kcal h 25 8 22...

Page 38: ...r N Serial Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn max CH maximum heat...

Page 39: ...s 60 C on return and 80 C on flow Low temperature mode for condensation Boilers means 30 C for low temperature boilers 37 C and for other appliances 50 C of return tempera ture Model s Victrix Zeus Su...

Page 40: ...mestic hot water function AFC 18 GJ Seasonal room heating yield s 92 Domestic hot water production yield wh 82 Parameter value Yearly energy consumption for the heating function QHE 61 2 GJ Yearly ele...

Page 41: ...ementary heat pump From fiche of heat pump Solar contribution and Supplementary heat pump Select smaller value Boiler and supplementary heat pump installed with low temperature heat emitters at 35 C F...

Page 42: ...35 C From fiche of heat pump The energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once installed in a building as the efficien...

Page 43: ...y electricity 3 G F E D C B A A A A 27 27 27 28 27 27 27 28 30 30 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100 115 123 131 130 150 160 170 163 188 200 213 M L XL XXL 3 2 3 2 The energy ef...

Page 44: ...Water heating energy efficiency under colder and warmer climate conditions Colder 0 2 x Warmer 0 4 x Declared load profile Solar contribution From fiche of solar device 1 I 2 1 1 x I 10 x II III I Aux...

Page 45: ...45...

Page 46: ...46...

Page 47: ...47...

Page 48: ...mmergas com Immergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 037935ENG rev ST 001312 003 12...

Reviews: