background image

31

  In case of ΔT > 35 °C, the boiler lowers the 

power to avoid surpassing that value. When 

this status is on, the flow temperature symbol 

flashes.

3.8  CONTROL FUNCTION AIR FLOW 

RATE.

With ignition request, before the start of the fan, 

the condition of the pressure switch contact is ve-

rified. If this is detected closed, the continuation 

of the cycle is prevented.

After a delay time of about 50 seconds, there is 

a permanent block and fault “0A4” is signalled.

If the detected contact is open, the fan activates 

at the “air pressure switch control” speed (3300 

rpm). When the pressure switch is closed, the fan 

switches to the ignition speed, and the ignition 

cycle continues ignoring the pressure switch 

condition.

If during operation at the “air pressure switch 

control” speed (3300 rpm) the pressure switch 

does not close, after a time of about 50 seconds 

there is a permanent block and the fault “0A4” 

is signalled.

3.9  PROGRAMMING THE BOILER P.C.B.

The boiler is prepared for possible programming 

of several operation parameters. By modifying 

these parameters as described below, the boiler 

can be adapted according to specific needs.
- Access programming by pressing and holding 

down buttons “B” and “C”.

3-3

3.7 TROUBLESHOOTING.

N.B.:

 maintenance interventions must be carried 

out by an authorised company (e.g. Immergas 

After-Sales Technical Assistance Service).

-  Smell of gas. Caused by leakage from gas circuit 

pipelines. Check sealing efficiency of gas intake 

circuit.

- Repeated ignition blocks. No gas, check the 

presence of pressure in the network and that 

the gas adduction valve is open. Incorrect 

adjustment of the gas valve, check the correct 

calibration of the gas valve.

- Irregular combustion or noisiness. It may be 

caused by: a dirty burner, incorrect combustion 

parameters, intake-exhaust terminal not cor-

rectly installed. Clean the above components 

and ensure correct installation of the terminal, 

check correct setting of the gas valve (Off-Set 

setting) and correct percentage of CO

2

 in flue 

gases.

- The over temperature safety thermostat, the 

flow probe or the return probe are triggered 

frequently. It can depend on the lack of water in 

the boiler, little water circulation in the system 

or blocked pump. Check on the manometer 

that the system pressure is within established 

limits. Check that the radiator valves are not 

closed and also the functionality of the pump.

   In addition:
  - check that the exchanger safety thermostat 

has not intervened. If it has, check the integrity 

of the module and ceramic fibre panel, replace 

the cover gasket of the manifold and reset the 

thermostat by pressing the specific button.

  - check that the exchanger safety thermostat 

has not intervened. If it has, check the integrity 

of the module and ceramic fibre panel, replace 

the cover gasket of the manifold and reset the 

thermostat by pressing the specific button

Also check the integrity of the thermofuse, and 

if it has been triggered it will be necessary 

to check the integrity of the module and the 

flue circuit.

- Drain trap clogged. This may be caused by 

dirt or combustion products deposited inside. 

Check, by means of the condensate drain cap, 

that there are no residues of material blocking 

the flow of condensate.

-  Heat exchanger clogged. This may be caused by 

the trap being blocked. Check, by means of the 

condensate drain cap, that there are no residues 

of material blocking the flow of condensate.

-  Noise due to air in the system. Check opening 

of the special air vent valve cap (Fig. 1-25 Ref. 

23). Check that system filling and air bleeding 

has been performed according to the require-

ments.

- Noise due to air inside the condensation 

module. Use the manual air vent valve (Fig. 

1-25 Ref. 13) to eliminate any air present in the 

condensation module. When the operation has 

been performed, close the manual vent valve.

- No DHW is produced. The boiler is equipped 

with a function that automatically recognises 

when there is an optional DHW probe, and an 

anomaly is reported if there is a failure affecting 

the DHW NTC probe. If there is a power out-

age, or if the boiler is switched off and back on 

again during the failure, it will not be possible 

to detect said failure, but it will, however, be 

recorded in the errors anomaly records.

- Scroll through the parameters by pressing the 

+ and - heating adjustment buttons, 

- Change the parameter by pressing the + and - 

DHW adjustment buttons.

- Save the parameters by switching from one 

parameter to the next or by pressing “B”.

- Exit the programming mode by pressing and 

holding down buttons “B” and “C”, or wait 

approximately 2 minutes without touching the 

buttons. The boiler will then run a self-diag-

nosis of the parameters by displaying “PARA” 

followed by “Auto”.

- While the value of a parameter is being dis-

played, press “B” quickly to see the code again.

3-4

3-5

3-6

Summary of Contents for VICTRIX PRO 35 2ErP

Page 1: ...IE Instruction and warning book VICTRIX PRO 35 55 2 ErP 1 041662ENG...

Page 2: ......

Page 3: ...in the regulations in force and principles of good practice In compliance with legislation in force the systems must be designed by qualified professionals within the dimensional limits established b...

Page 4: ...9 Restoring central heating system pressure 26 2 10 System drainage 26 2 11Anti freeze protection 26 2 12Case cleaning 26 2 13Decommissioning 26 3 Boiler commissioning initial check 27 3 1 Hydraulic...

Page 5: ...ts or fixing template to fix the appliance to the wall they only ensure adequate support if inserted correctly according to technical standards in walls made of solid or semi hollow brick or block In...

Page 6: ...temperature 5 C The boiler comes standard with an anti freeze function that ac tivates the pump and burner when the system water temperature in the boiler falls below 5 C The anti freeze function is...

Page 7: ...igned to operate with combustible gas free of impurities otherwise it is advisable to fit special filters upstream of the appliance to restore the purity of the fuel Storage tanks in case of supply fr...

Page 8: ...nce is reached only when it is correctly connected to an efficient earthing system as specified by current safety standards Attention Immergas S p A declines any respon sibility for damage or physical...

Page 9: ...s Thermoregulation electrical connection Fig 1 4 Thermoregulation electrical connections must be carried out on the boiler terminal board eliminating jumper X40 Thermostat or On Off environment chrono...

Page 10: ...pe C configuration sealed chamber and fan assisted The boiler leaves the factory with B23 configuration to change the configuration of the boiler to type C sealed chamber and fan assisted disassemble...

Page 11: ...mplete with vertical exhaust 80 Exhaust m 3 DUCT TYPE Equivalent length in m of concentric pipe 80 125 Concentric pipe 80 125 m 1 1 0 m Concentric bend 90 80 125 1 9 m Concentric bend 45 80 125 1 4 m...

Page 12: ...in order to ensure sufficient space to carry out the tests required by law upon commissioning External grid The intake exhaust terminal if properly installed is pleasant to look at on the outside of...

Page 13: ...ng the previously disassembled sheet steel plate 3 Installation of the fake aluminium tile replace the tiles with the aluminium sheet 5 shaping it to ensure that rainwater runs off Position the fixed...

Page 14: ...with this configuration can be extended up to a max measurement of 24 0 m with Victrix Pro 35 2ErP and 30 0 m with Victrix Pro 55 2ErP including the terminal Using the 80 vertical terminal for direct...

Page 15: ...has been fitted This will ensure sealing and joining of the elements making up the kit Horizontal kit 80 with exhaust in flue Kit assembly Fig 1 21 install the 80 bend 1 with the male side smooth full...

Page 16: ...compiled at the end of work and on commissioning of the ducted system The instructions in the project or technical report must likewise be followed in cases provided for by the standard and current te...

Page 17: ...pump always runs at maximum speed Pump release If after a prolonged period of inactivity the circulation pump is blocked unscrew the front cap and turn the motor shaft using a screwdriver Take great...

Page 18: ...ter 13 Ignition electrode 14 Air pressure switch 15 Flue probe 16 Condensing module air vent valve 17 Fumes hood 18 Sample points air A flue gas F 19 Heat exchanger safety thermal fuse 20 Manual air v...

Page 19: ...aker switches andofthethermometer notsuppliedasstandard with the boiler must be set up as described in the installation instructions in compliance with theprovisionsofthe R collection Wheneverthe gene...

Page 20: ...1 13 Zone 2 central heating circuit pump CMI 2 14 Zone 3 direct circuit pump CD 15 Storage tank unit feeding pump 16 Zone 1 safety thermostat CMI 1 17 Zone 2 safety thermostat CMI 2 19 Fuel shut off...

Page 21: ...anti freeze is not used b shut off all electrical water and gas supplies N B in the case of maintenance interventions on the boiler that lead to the closure of one or both system cut off cocks the boi...

Page 22: ...25 Summer mode 2 5 USING THE BOILER Before ignition make sure that the system is full of water checking that the manometer 5 indicates a base value at which the system has been designed and calculate...

Page 23: ...us setting 2 4 2 5 Stand by mode by pressing buttons A and C at the same time it is possible to place the boiler in stand by In this mode the boiler is considered powered on but not active Accordingly...

Page 24: ...ure detection incorrect in stand by With the boiler in stand by the board detects an anomalous difference between the NTC probe flow and return temperatures The error may be caused by a failure in one...

Page 25: ...probe 2 1 0E46 FlueNTCprobeoutside theoperatingrange The board detects an open contact on the flue NTC probe 2 1 0E81 Flow and return NTC probe temperature detection incorrect in stand by With the boi...

Page 26: ...frequently filling must be carried out with suitably treated water to eliminate hardness that can cause lime scale 2 12 CASE CLEANING Use damp cloths and neutral detergent to clean the boiler casing N...

Page 27: ...ll adjustment devices seal the gas flow rate regulation devices if settings are modified check sealing efficiency of water circuits check ventilation and or aeration of the instal lation room where pr...

Page 28: ...iler configuration jumper Y1 Gas valve Configure the corresponding parameters when connecting in simple cascade or when con necting in system side flow probe or D H W pump 1 External reset optional 2...

Page 29: ...ectronic board A4 Display board B1 Flow probe B1 2 System side flow probe optional B2 Domestic hot water probe optional B4 External temperature probe optional B5 Return probe B10 Flue probe B25 System...

Page 30: ...r probe NTC optional B4 External probe optional M2 Plant CH pump optional M30 3 way valve optional Note probe B1 2 B2 B4 Connection cable diameter 3 7 mm Cable section 0 5 1 5 mm2 1 External relay opt...

Page 31: ...at the radiator valves are not closed and also the functionality of the pump In addition check that the exchanger safety thermostat has not intervened If it has check the integrity of the module and c...

Page 32: ...io It defines the boiler s modulation ratio Do not modify 0 100 10 P13 Boiler power Used to calculate the boiler power in the event of simple cascade 0 255 kW 35 kW 35 55 kW 50 P14 External probe curv...

Page 33: ...nes the unit of measure on the display whether metric or Imperial 0 127 C kW 128 256 F kBTu h 0 P32 Set Resc Min Limits the minimum value of the heating set The parameter takes priority in relation to...

Page 34: ...tor To increase the CO2 value turn the adjustment screw 3 in a clockwise direction and vice versa to decrease it Calibration of maximum CO2 When you finish the minimum CO2 adjustment turn the boiler o...

Page 35: ...d to terminals S1 and S2 and parameter P38 must be set up whereas the pump must be connected to termi nals C and D If there is a DHW circuit it can be connected via an external 3 way to be connected t...

Page 36: ...every two years regardless of their state of wear Check that the burner is intact that it has no deformations or cuts and that it is properly fixed to the combustion chamber lid otherwise it must be r...

Page 37: ...the central hooks and then slide it downwards take the two clamping screws out 4 from the control panel with their rings 5 press the two side hooks 7 and tilt the control panel 6 remove the lower grid...

Page 38: ...38 3 15 1 6 8 9 9 12 12 10 11 13 13 13 13 A A Rif A 7 7 Ref A...

Page 39: ...690 2 38 4510 29 0 24940 3 13 4570 2 30 4380 28 5 24469 3 07 4500 2 26 4310 27 0 23220 2 92 4320 2 14 4120 26 0 22360 2 81 4200 2 06 4000 25 0 21500 2 71 4070 1 99 3870 24 0 20640 2 60 3950 1 91 3750...

Page 40: ...0 10 CO with 0 O2 at Nom Min Q Nom Min ppm 157 1 184 1 NOX at 0 of O2 at Q Nom Min mg kWh 43 17 43 21 Flue temperature at nominal output C 52 53 Flue temperature at minimum output C 48 48 METHANE G20...

Page 41: ...4 4 4 4 Central heating circuit max operating temperature C 90 90 Adjustable central heating temperature C 20 85 20 85 Head available with 1000 l h flow rate kPa m H2 O 60 1 6 13 60 1 6 13 Weight of f...

Page 42: ...N Serial Number CHK Check Cod PIN PIN code Type applianceconfiguration ref CENTR1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn max CH maximum heat i...

Page 43: ...ns 60 C on return and 80 C on flow Low temperature mode for condensation Boilers means 30 C for low temperature boilers 37 C and for other appliances 50 C of return temper ature Model s Victrix Pro 55...

Page 44: ...easonal room heating yield s 91 Domestic hot water production yield wh Parameter value Yearly energy consumption for the heating function QHE 86 7 GJ Yearly electricity consumption for the domestic ho...

Page 45: ...r Supplementary heat pump From fiche of heat pump Solar contribution and Supplementary heat pump Select smaller value Boiler and supplementary heat pump installed with low temperature heat emitters at...

Page 46: ...che of heat pump The energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once installed in a building as the efficiency is influe...

Page 47: ...contribution From fiche of solar device 1 I 2 1 1 x I 10 x II III I Auxiliary electricity 3 G F E D C B A A A A 27 27 27 28 27 27 27 28 30 30 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100...

Page 48: ...gy efficiency under colder and warmer climate conditions Colder 0 2 x Warmer 0 4 x Declared load profile Solar contribution From fiche of solar device 1 ___ 2 1 1 x ___ 10 x ___ ____ ____ Auxiliary el...

Page 49: ...49...

Page 50: ...50...

Page 51: ...51...

Page 52: ...mmergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 041662ENG rev ST 003517 000 12 18 Inglese p...

Reviews: