background image

11

1-11

1-10

1-9

INS

T

ALLER

US

ER

MAINTEN

AN

CE TECHNI

CI

AN

The cover kit includes:
 N° 1    Thermoformed cover
 N°1    Gasket clamping plate
 N°1    Gasket
 N°1    Gasket tightening strap
 N°1    Intake hole covering plate

The terminal kit includes:
N° 1    Gasket
N° 1    Discharge flange Ø 80
N° 1    Bend 90° Ø 80
N° 1    Drain pipe Ø 80
N° 1    Wall sealing plate

1.11  OUTDOOR INSTALLATION IN A 

PARTIALLY PROTECTED AREA.

N.B.:

 

a partially protected location is one in which 

the appliance is not exposed to the direct action of 
the weather (rain, snow, hail, etc..).

This  type  of  installation  is  only  possible  when 
permitted by the laws in force in the appliance's 
country of destination.

• Configuration  type  B,  open  chamber  and 

forced draught.

Using the special coverage kit one can achieve 
direct air intake (Fig. 1-9) and fumes exhaust in 
a single flue or directly outside. In this configura-
tion it is possible to install the boiler in a partially 
protected place. In this configuration the boiler 
is classified as type B.
With this configuration:
-  air intake takes place directly from the envi-

ronment  in  which  the  appliance  is  installed 
(outside);

-  the fumes exhaust must be connected to its own 

single flue (B23) or ducted directly outside via 
a vertical terminal for direct exhaust (B

53

) or 

via an Immergas ducting system (B

53

).

The  technical  regulations  in  force  must  be 
respected.

• 

Coverage  kit  assembly  (Fig.  1-10).

  Remove 

the  two  plugs  and  the  gaskets  present  from 
the two lateral holes with respect to the central 
one. Now cover the right intake hole using the 
relevant plate, fixing it onto the left side using 
the  2  previously-removed  screws.  Install  the 

Ø

  80  outlet  flange  on  the  central  hole  of  the 

boiler, taking care to insert the gasket supplied 
with the kit and tighten by means of the screws 

provided. Install the upper cover, fixing it using 
the 4 screws present in the kit, positioning the 
relevant  gaskets.  Engage  the  90

°

 

Ø

  80  bend 

with the male end (smooth) in the female end 
(with lip seal) of the 

Ø

 80 flange unit until it 

stops. Introduce the gasket, making it run along 
the bend. Fix it using the sheet steel plate and 
tighten by means of the straps present in the 
kit, making sure to block the 4 gasket flaps. Fit 
the male end (smooth) of the exhaust terminal 
into the the female end of the bend 90

°

 

Ø

 80, 

making sure that the relevant wall sealing plate 
is already fitted; this will ensure hold and join-
ing of the elements making up the kit.

Max. length of exhaust duct.

 The flue pipe (both 

vertical or horizontal) can be 

extended to a max. 

length of 30 linear metres

.

• 

Coupling  of  extension  pipes.  To  install  any 
push-fit  extensions  with  other  flue  elements, 
it is necessary to act as follows: install the pipe 
or elbow with the male side (smooth) into the 
female section (with lip seal) to the end stop 
on the previously installed element. This will 
ensure correct sealing and joining of the ele-
ments.

• Configuration without cover kit in a partially 

protected location (type C boiler)

  By  leaving  the  side  plugs  fitted  it  is  possible 

to install the appliance externally without the 
cover  kit.  Installation  takes  place  using  the 

Ø

60/100, 

Ø

  80/125  and  separator 

Ø

  80/80 

concentric  intake/  exhaust  kits.  Refer  to  the 
paragraph  relative  to  indoor  installation.  In 
this configuration the upper cover kit guaran-
tees  additional  protection  for  the  boiler.  It  is 
recommended but not compulsory.

Summary of Contents for VICTRIX EXA 24 X 1 ErP

Page 1: ...VICTRIX EXA 24 X 1 ErP IE Instruction and recommendation booklet 1 038507ENG ...

Page 2: ......

Page 3: ...be designed by qualified professionals within the dimensional limits established by the Law Installation and maintenance must be performed in compliance with the regulations in force according to the manufacturer s instructions and by an authorised company which has specific technical expertise in the system sector as required by Law Improper installation or assembly of the Immergas appliance and ...

Page 4: ...ns 21 2 1 Cleaning and maintenance 21 2 2 General warnings 21 2 3 Control panel 21 2 4 Using the boiler 21 2 5 Troubleshooting 22 2 6 Information menu 24 2 7 Boiler shutdown 24 2 8 Restoring central heating system pressure 24 2 9 System draining 24 2 10Anti freeze protection 24 2 11Case cleaning 24 2 12Decommissioning 24 3 Boiler commissioning initial check 25 3 1 Boiler hydraulic diagram 25 3 2 W...

Page 5: ... paper rags plastic polystyrene etc Do not place household appliances underneath the boiler as they could be damaged if the safety valve intervenes with an obstructed conveying system the safety valve must be conveyed away by a draining funnel or if there are leaks from the hydraulic connections on the contrary the manufacturer cannot be held responsible for any damage caused to the household appl...

Page 6: ...at carefully read the installation instructions contained in the ac cessory kit pack In these conditions the boiler is protected against freezing to temperature of 15 C Boiler antifreeze protection both 5 C and 15 C is thus ensured only if the boiler is correctly connected to gas and elec tricity power supply circuits the boiler is powered constantly the boiler is not in off mode the boiler is not...

Page 7: ... the liquid contained in it Before appliance ignition ensure that the condensate can be correctly removed After first ignition check that the drain trap is filled with condensate para 1 21 Also comply with national and local regulations on discharg ing waste waters 1 6 ELECTRICAL CONNECTION The Victrix EXA 24 X 1 ErP boiler has an IPX5D protection rating for the entire appliance Electrical safety ...

Page 8: ...e available as optional kits Fig 1 5 All Immergas chrono thermostats are connected with 2 wires only Carefully read the user and assembly instructions contained in the acces sory kit On Off Immergas digital chrono thermostat The chrono thermostat allows set two room temperature value one for daytime comfort temperature and one for night time reduced temperature set a weekly program with four daily...

Page 9: ...e resistance encountered with the maximum allowed pipe length for each type of Terminal Kit This information allows calculations to be made to verify the possibility of setting up various flue configurations Positioning the gaskets black for green range flue systems Position the gasket cor rectly for bends and extensions Fig 1 8 gasket A with notches to use for bends gasket B without notches to us...

Page 10: ...Intake and Exhaust 16 3 m 2 5 Intake m 18 7 Exhaust m 4 9 m 7 7 Exhaust m 13 6 Concentric vertical intake exhaust terminal Ø 60 100 Intake and Exhaust 9 m 1 4 Intake m 10 3 Exhaust m 2 7 m 4 3 Exhaust m 7 5 Pipe Ø 80 m 1 Intake 0 87 m 0 1 Intake m 1 0 Exhaust m 0 4 m 0 4 m 0 5 Exhaust 1 2 m 0 2 Exhaust m 1 0 Complete intake terminal Ø 80 m 1 Intake 3 m 0 5 Intake m 3 4 Exhaust m 0 9 m 1 4 Intake t...

Page 11: ... 2 previously removed screws Install the Ø 80 outlet flange on the central hole of the boiler taking care to insert the gasket supplied with the kit and tighten by means of the screws provided Install the upper cover fixing it using the 4 screws present in the kit positioning the relevant gaskets Engage the 90 Ø 80 bend with the male end smooth in the female end with lip seal of the Ø 80 flange un...

Page 12: ... during installation Horizontal intake exhaust kit Ø 60 100 Kit assembly Fig 1 12 install the bend with flange 2 on the central hole of the boiler positioning gasket 1 with the circular projections down wards in contact with the boiler flange and tighten using the screws present in the kit Fit the Ø 60 100 3 concentric terminal pipe with the male side smooth to the female side of the bend 2 up to ...

Page 13: ... flange 2 up to the end stop making sure that the wall sealing plate has been fitted 3 this will ensure sealing and joining of the elements making up the kit NOTE when the boiler is installed in areas where very cold temperatures can be reached a special anti freeze kit is available that can be installed as an alternative to the standard kit Extensions for vertical kit Ø 60 100 Fig 1 17 The kit wi...

Page 14: ...esent in the lateral hole with respect to the central one ac cording to needs and replace it with the flange 3 positioningthegasket 2 alreadypresentin the boiler and tighten using the supplied self threading screws Fit the male end smooth to the bends 5 in the female end of the flanges 3 and 4 Fit the intake terminal 6 with the male side smooth in the female side of the bend 5 up to the end stop e...

Page 15: ... the external pipe must be fitted on the adaptor until it stops 1 N B to encourage the removal of possible condensate forming in the exhaust pipe tilt the pipes towards the boiler with a minimum slope of 1 5 Mount the cover A complete with adaptor 1 and caps 6 on the wall and assemble the flue system to the ducting system N B version Ø 125 only before assembly check the gaskets are in the right po...

Page 16: ...ey technical slot The maximum possible length of the Ø 80 rigid ducting vertical section is equal to 30 m This length is obtained considering the complete Ø 80 exhaust terminal 1m of Ø 80 pipe in ex haust two 90 Ø 80 bends on the boiler outlet 1 17 CONFIGURATION TYPE B OPEN CHAMBER AND FAN ASSISTED FOR INDOORS The appliance can be installed inside buildings in 23 or B53 mode in this case all techn...

Page 17: ... the boiler flue gas may come out the condensate drain after a few minutes operation check that this no longer occurs This means that the drain trap is filled with conden sate to the correct level preventing the passage of flue gas 1 22 GAS SYSTEM START UP To start up the system refer to the technical standard in force This divides the systems and therefore the start up operations into three categ...

Page 18: ...on status During normal operation thestatusLED 2 isongreen flashing FL when it is in stand by the four yellow LEDs 3 indicate circulator absorption according to the following table Circulating pump LED Absorption G Y Y Y Y FL Off Off Off Off Circulator in stand by G Y Y Y Y On On Off Off Off 0 25 G Y Y Y Y On On On Off Off 25 50 G Y Y Y Y On On On On Off 50 75 G Y Y Y Y On On On On On 75 100 Selec...

Page 19: ... The boiler is prepared for the installation of a relay card that allows to increase the features of the appliance and therefore functioning possibilities Cover kit on request If installed outdoors in a partially protected place with direct air intake it is compulsory to mount the appropriate top protection cover for the correct functioning of the boiler and to protect it from adverse weather cond...

Page 20: ...densation module 12 System expansion vessel 13 Flue probe 14 Manual air vent valve 15 Sample points air A flue gas F 16 Negative signal pressure point 17 Positive signal pressure point 18 Heat exchanger safety thermal fuse 19 Burner 20 Ignition electrode 21 Air intake pipe 22 Igniter 23 Fan 24 Vent valve 25 Return probe 26 Boiler circulator pump 27 3 bar safety valve 28 3 way valve motorised 29 By...

Page 21: ...oved by a professionally authorised company Contact the manufacturer for disposal instructions 2 3 CONTROL PANEL Key 1 Off Stand by On button 2 Summer Winter Button 3 Reset button 4 Information button 5 Domestic hot water temperature selector 6 Central heating temperature selector 7 Boiler manometer 8 DHW production phase operating mode active 9 Boiler in block requiring unblock via RESET button 1...

Page 22: ...a parameter T3 in the P C B customisation menu 2 5 TROUBLESHOOTING The Victrix EXA 24 X 1 ErP boiler reports any anomalies using a code shown on the boiler display 14 listed in the table below On the remote control the error code will be displayed by means of the same numeric code represented according to the following example e g CARV2 Exx Error Code Anomaly signalled Cause Boiler status Solution...

Page 23: ...ited correctly and the burner flame goes out unexpectedly a new ignition attempt is performed and if normal con ditions are restored the boiler does not have to be reset this anomaly can only be checked in the list of errors present in the Information menu If normal conditions are restored the boiler restarts without having to be reset 1 43 Block due to loss of continuous flame signal This occurs ...

Page 24: ...ormal pressure via the cock located at the bottom of the boiler Fig 1 3 N B close the cock after the operation If pressure values reach around 3 bar the safety valve may be activated In this case remove water from an air vent valve of a radiator until 1 bar is reached or ask for as sistance from an authorised company If frequent pressure drops should occur ask an authorised company for assistance ...

Page 25: ...t tings are modified checkthe production ofDHW whenthe boiler is connected to an external storage tank unit check sealing efficiency of water circuits check ventilation and or aeration of the instal lation room where provided If even only a single safety check offers a negative result do not commission the system 3 1 BOILER HYDRAULIC DIAGRAM Key 1 Condensate drain trap 2 3 bar safety valve 3 Gas v...

Page 26: ... low temperature connection jumper 4 Return probe function configuration jumper 5 Storage tank mode configuration jumper 6 N B the user interface is on the welding side of the boiler board 7 Orange 8 Black 9 Black DHW 10 Brown 11 Brown C H 12 Blue 13 Grey 14 White 15 Pink 16 Red 17 Green Storage tank unit the boiler is prepared for con nection to a storage tank unit which must be connected to clam...

Page 27: ...different gas type to that specified on the data nameplate request the relative conversion kit for quick and easy conversion The gas conversion operation must be carried out by an authorised company e g Authorised After Sales Technical Assistance Service To convert to another type of gas the following operations are required disconnect the appliance replace the nozzle located between the gas pipe ...

Page 28: ...possible programming of several operation parameters By modifying these parameters as described below the boiler can be adapted according to specific needs To access the programming phase position the DHW selector 5 on position 6 the CH selector 6 on position 9 and press the Reset 3 and Summer Winter buttons for about 8 seconds 2 Once the menu has been accessed it is possible to scroll through the...

Page 29: ...0 Off 1 General alarm 2 CH phase active 3 External gas valve power supply 4 Secondary zone control from TA on relay P C B contact 5 Heat pump 0 5 0 P5 Relay 3 optional The boiler is set up for functioning with the relay P C B optional which can be configured 0 Off 1 Chiller remote activation 2 General alarm 3 CH phase active 4 External gas valve power supply 5 heat pump 6 activation of storage tan...

Page 30: ... be interrupted by pressing the reset button 4 In the second case it has duration of 18 hours and it can be interrupted by simply switching the boiler on Activation of the function is signalled by the countdown shown on the indicator 14 3 16 APPLIANCE CHECK AND MAINTENANCE The following checks and maintenance should be performed at least once a year Clean the flue side of the heat exchanger Clean ...

Page 31: ...move the grid 1 Front panel Fig 3 4b 3 Remove the cover caps 3 and loosen the screws 4 4 Tilt the control panel 5 towards you Casing Fig 3 4c 5 Remove the screws 6 that lock the front casing 7 and the two sides 9 6 Pull the front casing slightly 7 in the lower part towards yourself and push upwards at the same time 7 Loosen the screws 8 on the sides 9 8 Remove the sides by pulling them towards you...

Page 32: ...t a tem perature of 15 C 3 19 COMBUSTION PARAMETERS METHANE G20 BUTANE G30 PROPANE G31 THERMAL POWER BURNER GAS FLOW RATE PRESS BURNER NOZZLES BURNER GAS FLOW RATE PRESS BURNER NOZZLES BURNER GAS FLOW RATE PRESS BURNER NOZZLES kW kcal h m3 h mbar mm H2 O kg h mbar mm H2 O kg h mbar mm H2 O MAX 23 7 20382 2 56 2 41 24 6 1 91 2 57 26 2 1 88 2 99 30 5 OUTPUT 5 5 4730 0 60 0 17 1 7 0 45 0 18 1 8 0 44 ...

Page 33: ... Min 107 2 107 8 Casing losses with burner On Off 80 60 C 0 55 0 20 Heat loss at flue with burner On Off 80 60 C 0 01 1 70 Central heating circuit max operating pressure bar 3 0 Maximum heating temperature C 90 Adjustable central heating temperature max operation field C 20 85 System expansion vessel total volume l 5 0 Expansion vessel factory set pressure bar 1 0 Appliance water content l 3 0 Hea...

Page 34: ...Sr N Serial Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn max CH maximum heat input Pn min Minimum heat output Pn max Maximum heat output PMS Maximum system pressure PMW Maximum domestic hot water pressure D Specific flow rate TM Maximum operating temperature NOx Class NOx Cl...

Page 35: ...umption Other items At full load elmax 0 039 kW Heat loss in standby Pstby 0 078 kW At partial load elmin 0 019 kW Ignition burner energy consumption Pign 0 000 kW In standby mode PSB 0 006 kW Emissions of nitrogen oxides NOX 40 mg kWh For mixed central heating appliances Stated load profile Domestic hot water production efficiency ηWH Daily electrical power consumption Qelec kWh Daily gas consump...

Page 36: ...ERLOHU 1 7HPSHUDWXUH FRQWURO URP FKH RI WHPSHUDWXUH FRQWURO 6XSSOHPHQWDU ERLOHU URP FKH RI ERLOHU 6XSSOHPHQWDU KHDW SXPS URP FKH RI KHDW SXPS 6RODU FRQWULEXWLRQ DQG 6XSSOHPHQWDU KHDW SXPS 6HOHFW VPDOOHU YDOXH RLOHU DQG VXSSOHPHQWDU KHDW SXPS LQVWDOOHG ZLWK ORZ WHPSHUDWXUH KHDW HPLWWHUV DW URP FKH RI KHDW SXPS 7KH HQHUJ HI FLHQF RI WKH SDFNDJH RI SURGXFWV SURYLGHG IDU LQ WKLV FKH PD QRW FRUUHVSRQG ...

Page 37: ...QWDU KHDW SXPS LQVWDOOHG ZLWK ORZ WHPSHUDWXUH KHDW HPLWWHUV DW URP FKH RI KHDW SXPS 7KH HQHUJ HI FLHQF RI WKH SDFNDJH RI SURGXFWV SURYLGHG IDU LQ WKLV FKH PD QRW FRUUHVSRQG WR LWV DFWXDO HQHUJ HI FLHQF RQFH LQVWDOOHG LQ D EXLOGLQJ DV WKH HI FLHQF LV LQÀXHQFHG E IXUWKHU IDFWRUV VXFK DV KHDO ORVV LQ WKH GLVWULEXWLRQ V VWHP DQG WKH GLPHQVLRQLQJ RI WKH SURGXFWV LQ UHOD WLRQ WR EXLOGLQJ VL H DQG FKDUDF...

Page 38: ...DQG ZDUPHU FOLPDWH FRQGLWLRQV ROGHU DUPHU HFODUHG ORDG SUR OH 6RODU FRQWULEXWLRQ URP FKH RI VRODU GHYLFH 1 µ 2 µ µ µ µ X LOLDU HOHFWULFLW 3 G F E D C B A A A A M L XL XXL 3 2 3 2 7KH HQHUJ HI FLHQF RI WKH SDFNDJH RI SURGXFWV SURYLGHG IDU LQ WKLV FKH PD QRW FRUUHVSRQG WR LWV DFWXDO HQHUJ HI FLHQF RQFH LQVWDOOHG LQ D EXLOGLQJ DV WKH HI FLHQF LV LQÀXHQFHG E IXUWKHU IDFWRUV VXFK DV KHDW ORVV LQ WKH GL...

Page 39: ...LQJ HQHUJ HI FLHQF FODVV RI SDFNDJH XQGHU DYHUDJH FOLPDWH DWHU KHDWLQJ HQHUJ HI FLHQF XQGHU FROGHU DQG ZDUPHU FOLPDWH FRQGLWLRQV ROGHU DUPHU HFODUHG ORDG SUR OH 6RODU FRQWULEXWLRQ URP FKH RI VRODU GHYLFH 1 BBB 2 BBB BBB BBBB BBBB X LOLDU HOHFWULFLW 3 G F E D C B A A A A M L XL XXL 3 2 3 2 7KH HQHUJ HI FLHQF RI WKH SDFNDJH RI SURGXFWV SURYLGHG IDU LQ WKLV FKH PD QRW FRUUHVSRQG WR LWV DFWXDO HQHUJ H...

Page 40: ...immergas com Immergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 038507ENG rev ST 001630 000 07 15 Inglese per IRLANDA IE ...

Reviews: