25
- Building dimension and inertia (BUILDG), adjustable
from 1 to 20, standard setting is 10. It establishes the
system’s reaction speed depending on the type of system.
For example:
Value
System type
5
system with little thermal inertia
10
system of a normal size with radiators
20
system with a lot of thermal inertia (e.g.
floor system)
- Minimum outside temperature (TE MIN), it defines at
what minimum outside temperature you want to have
the maximum delivery temperature which can be set from
-20°C to 0°C, set at -5°C (see fig. 19) (on boilers with
evolved electronics such as Superior kW visualisation only,
settable on the boiler).
- Maximum outside temperature (TE MAX), it defines at
what maximum outside temperature you want to have the
minimum delivery temperature which can be set from +5°C
to +25°C, set at 25°C (see fig. 19) (on boilers with evolved
electronics such as Superior kW visualisation only, settable
on the boiler).
- Self-learning (AUTO A), it defines when the self-learning
function is to be activated, ON is the standard setting. This
function allows the Super CAR to adapt the adjustment of
the speed at which room temperature, delivery temperature,
etc., is reached, adapting itself to the room in which it is
installed.