background image

161

GR

CZ

HU

ES

IE

PT

3.2  WIRING DIAGRAM.

Fig. 3-2

Remote control: the boiler is set-up for the appli-

cation of the Comando Amico Remoto remote 

control

V2

  (CAR

V2

)  which  must  be  connected 

to clamps 41 and 44 of the X15 connector on 

the P.C.B. respecting polarity and eliminating 

jumper X40.
Room thermostat: the boiler is designed to use 

the Room Thermostat (S20). Connect it to clamps 

40 – 41 eliminating jumper X40.
The X5 connector is also used for the connection 

with three relay board (optional) by removing the 

connection to the relay board.
The connector X6 is for connection to a personal 

computer.
The connector X8 is used for software updating 

operations.

3.3  TROUBLESHOOTING.
N.B.: 

Maintenance must be carried out by a 

qualified technician (e.g. Immergas Technical 

After-Sales Assistance Service).
- Smell of gas. Caused by leakage from gas circuit 

pipelines. Check sealing efficiency of gas intake 

circuit.

- The fan works but ignition discharge does not 

occur on the burner ramp. The fan may start 

but the safety air pressure switch does not 

switch the contact over. Make sure:

1)  the intake/exhaust duct is not too long (over 

allowed length).

2)   the intake/exhaust duct is not partially blo-

cked (on the exhaust or intake side).

3)  the diaphragm of the flue exhaust is adequate 

for the length of the intake-exhaust duct.

4)  that the sealed chamber is kept in good con-

ditions.

5)  the fan power supply voltage is not less than 

196 V.

- Irregular combustion (red or yellow flame). 

This may be caused by: dirty burner, incorrect 

combustion parameters, intake - exhaust ter-

minal not correctly installed. Clean the above 

components and ensure correct installation of 

the terminal.

- Frequent interventions of the over heating 

safety thermostat. It can depend on reduced 

water pressure in the boiler, little circulation 

in the heating system, the blocked pump or 

an anomaly of the boiler P.C.B. Check on the 

manometer that the system pressure is within 

established limits. Check that radiator valves 

are not all closed.

- Presence  of  air  in  the  system.  Check  ope-

ning of the hood of the special air vent valve 

(Fig. 1-34). Make sure the system pressure and 

expansion vessel pre-charge values are within 

the set limits; the factory-set pressure value 

for the expansion vessel must be 1.0 bar, and 

system pressure between 1 and 1.2 bar.

- Ignition block see par. 2.5 and 1.4 (electric 

connection).

6

7

7

10

5

6

7

1

2

11

4

3

7

8

6

9

6

7
6

12

8

12

8

11

11

8 8

11 13 13

14 14

15 15

14 14

8 8

6

7

Key:

  A9  - P.C.B. to a relay

  B1  - Flow probe

  B2  - Domestic hot water probe

  B4  - External probe (optional)

  B9  - DHW inlet probe (optional)

 CAR

V2

  - Comando Amico Remoto remote control Version 2 

(optional)

  DS1  - Display

  E3  - Ignition and detection electrodes

  E4  - Safety thermostat

  E11  - Aqua Celeris Resistance

  F1  - Phase fuse

  M1  - Boiler pump

  M20  - Fan

  M30  - Three-way valve

  R5  - Domestic hot water temperature 

trimmer

  R6  - Central heating temperature 

trimmer

  S2  - Selector switch functioning

  S3  - Reset block keys

  S4  - Domestic hot water flow switch

  S5  - System pressure switch

  S6  - Flue gas pressure switch

  S20  - Room thermostat (optional)

  S32  - Boost Button (Aqua Celeris activation)

  S31  - On/Stand-by/Off Button

  T1  - Switch-on transformer

  T2  - Boiler board transformer

  X40  - Room thermostat jumper

  Y1  - Gas valve

  Y2  - Gas valve modulator

  U1  - Rectifier inside the gas valve 

connector (Only available on Ho-

neywell gas valves)

 

1  - Anti-freeze kit (optional)

 

2  - 230 Vac 50 Hz power supply

 

3  - N.B.: The user interface is on the 

welding side of the boiler board

 

4  - Zones control unit (optional)

 

5  - Yellow/Green

 

6  - Brown

 

7  - Blue

 

8  - Black

 

9  - Domestic hot water

  10  - Central heating

  11  - Red

  12  - Orange

  13  - White

  14  - Grey

  15  - Green

Summary of Contents for Maior Eolo 24 4E

Page 1: ...ble for any damage cau sed to the household appliances In the event of malfunctions faults or incorrect operation turn the appliance off immediately and contact a qualified technician e g the Immergas After Sales Assistance centre which has specifically trained staff and original spare parts Do not attempt to modify or repair the appliance alone Failure to comply with the above implies personal re...

Page 2: ...nt regulations in order to guarantee correct gas flow to the burner even in conditions of maximum generator output and to guarantee appliance efficiency technical specifications The coupling system must conform to standards Fuel gas quality The appliance has been desig ned to operate with gas free of impurities other wise it is advisable to fit special filters upstream from the appliance to restor...

Page 3: ...s shown in the diagram Fig 1 8 The electric con nection of the external probe must be made on clamps 38 and 39 on the boiler P C B Fig 3 2 1 5 REMOTE CONTROLS AND ROOM CHRONO THERMOSTATS OPTIONAL The boiler is prepared for the application of room chrono thermostats or remote controls which are available as optional kits All Immergas chrono thermostats are connec ted with 2 wires only Carefully rea...

Page 4: ...exhaust must be connected to its own individual flue or channelled directly into the external atmosphere The technical regulations in force must be respected Flue gas separator adjustment For correct functioning of the boiler in configuration with direct intake it is necessary to regulate the flue gas shutter according to that stated in the relative tables Fig 1 14 Cover kit assembly Fig 1 11 Remo...

Page 5: ...ried out using the relevant tables Intake diaphragm installation For correct boi lerfunctioningwithØ80separatorkitsanddrain measuring 1 m a diaphragm must be installed on the sealed chamber intake hole and before the intake pipe Fig 1 15 The choice of suitable diaphragm takes place on the basis of the type of pipe and its maximum extension this calculation can be carried out using the following ta...

Page 6: ...5 horizontal concentric kit Da 0 a 0 5 Da 0 5 a 4 6 Da 4 6 a 7 4 Ø 80 125 vertical concentric kit Da 0 a 5 4 Da 5 4 a 9 5 Da 9 5 a 12 2 Ø 80 vertical separator kit without bends Da 0 a 20 Da 20 a 40 Da 0 a 22 Da 22 a 32 Ø 80 horizontal separator kit with two bend Da 0 a 16 Da 16 a 35 Da 0 a 17 Da 17 a 28 Direct intake kit and Ø 80 drain in B22 configuration Da 0 a 1 Da 1 a 12 These maximum extensi...

Page 7: ... Terminal complete with intake exhaust vertical concentric Ø 80 125 Intake and Exhaust 33 m 2 0 m 5 5 Intake m 14 3 Exhaust m 11 0 Terminal complete with concentric vertical intake exhaust Ø 80 125 Intake and Exhaust 26 5 m 1 6 m 4 4 Intake m 11 5 Exhaust m 8 8 Terminal complete with concentric horizontal intake exhaust Ø 80 125 Intake and Exhaust 39 m 2 3 m 6 5 Intake m 16 9 Exhaust m 13 Terminal...

Page 8: ... N 1 extension Fig 1 19 Max distance between vertical boiler axis and external wall is 1855mm Connection with N 2 extensions Fig 1 20 Max distance between vertical boiler axis and external wall is 2805mm Horizontal intake exhaust kit Ø 80 125 Kit assembly Fig 1 21 install the bend with flange 2 onto the central hole of the boiler inserting the gasket 1 and tighten using the screws in the kit Fit t...

Page 9: ...d The terminal Ø 60 100 can also be used for vertical exhaust in conjunction with concentric flange code 3 011141 sold separately The height between the terminal cap and half shell 374 mm must always be respected The vertical kit with this configuration can be extended up to a maximum of 4 700 mm vertical rectilinear withtheterminalincluded Fig 1 25 SeparatorkitØ80 80 TheØ80 80separatorkit allowss...

Page 10: ...ion can be calculated by using a resistance factor for each component or the equivalent length The sum of these resistance factors must not exceed 100 Temperature loss in flue ducts To prevent problems of flue gas condensate in the exhaust pipe Ø 80 due to flue gas cooling through the wall the length of the pipe must be limited to just 5 m Fig 1 29 If longer distances must be covered use Ø 80 pipe...

Page 11: ... until it is taken up to stop on the flue gas exhaust flange a situation that takes the two intake flue gas exhaust outlets to the same height Temperature loss in insulated flue ducting To prevent problems of flue gas condensate in the exhaust pipe Ø 80 due to flue gas cooling through the wall the length of the pipe must be limited to 12 m The figure Fig 1 32 illustrates a typical insulation appli...

Page 12: ...em filling via the filling valve Fig 2 2 Filling is performed at low speed to ensure rele ase of air bubbles in the water via the boiler and heating system vents The boiler has a built in automatic venting valve on the pump Check if the cap is loose Open the radiator air vent valves Close radiator vent valves only when water escapes from them Closethefillingvalvewhentheboilermanometer indicates ap...

Page 13: ...it is recommended to use the pump at maximum speed The pump is already fitted with a condenser Pump release If after a prolonged period of inactivity the circulation pump is blocked unscrew the front cap and turn the motor shaft using a screwdriver Take great care during this operation to avoid damage to the motor By pass regulation part 25 Fig 1 34 If neces sary the by pass can be regulated accor...

Page 14: ...est Polyphosphatedispenserkit Thepolyphosphate dispenser reduces the formation of lime scale and preserves the original heat exchange and domestic hot water production conditions The boiler is prepared for application of the polyphosphate dispenser kit Cover kit For outdoor installations in partially protected areas and with direct air intake the top protection cover must be fitted for a correct f...

Page 15: ...enance contract with your zone technician 2 2 GENERAL WARNINGS Never expose the wall mounted boiler to direct vapours from a cooking surface Use of the boiler by unskilled persons or children is strictly prohibited Donottouchthefluegasexhaustterminal ifpre sent due to the high temperatures it can reach For safety purposes check that the concentric air intake flue exhaust terminal if fitted is not ...

Page 16: ...erature for room central heating is managed by the external probe depending on the external temperature measured Par 1 6 The flow temperature can be modified by selecting the functioning curve via selector 1 selecting a value from 0 to 9 Fig 1 8 With external probe present the relative symbol will appear on the display 19 In the central heating phase if the temperature of the water contained in th...

Page 17: ...ler is ignited correctly and the burner flame switches off unexpectedly a new attempt at ignition is performed and if normal conditions are restored the boiler does not have to be reset If this phenomenon occurs frequently contact a qualified technician for assistance e g Immergas After Sales Technical Assi stance Service Block due to loss of continuous flame signal This occurs if the Flame signal...

Page 18: ...check that the intake and or exhaust terminals are not blocked check activation of the no air safety pressure switch ensure activation of all adjustment devices seal the gas flow rate regulation devices if settings are modified check the production of domestic hot water 3 1 HYDRAULIC DIAGRAM Fig 3 1 check sealing efficiency of water circuits check ventilation and or aeration of the instal lation r...

Page 19: ...ty thermostat It can depend on reduced water pressure in the boiler little circulation in the heating system the blocked pump or an anomaly of the boiler P C B Check on the manometer that the system pressure is within established limits Check that radiator valves are not all closed Presence of air in the system Check ope ning of the hood of the special air vent valve Fig 1 34 Make sure the system ...

Page 20: ...type Establishes the boiler type and its functioning mode 0 combi 1 24 kW storage tank 2 28 kW storage tank 3 32kW storage tank 0 3 0 S4 Ignition power Establishes the power at which the boiler must switch on 0 50 30 Use the DHW regulator selector 2 to select the parameter and rotate the CH regulator 1 to modify the value according to the range available With the menu active on the indicator 17 th...

Page 21: ... The boiler is set up for functioning with the relay board optional which can be configured 0 Off 1 Chiller remote activation 2 General alarm 3 CH phase active 4 External gas valve power supply 5 Aquaceleris PTC control To be used on this boiler model if a three relay board is installed 0 5 0 Id Parameter ref 17 Parameter Description Range ref 21Fig 2 1 Default t0 Central heating ignitions timer T...

Page 22: ...ed in the tables Par 3 18 3 9 SLOW AUTOMATIC IGNITION FUNCTION In ignition phase the P C B supplies constant gas with pressure proportional to the parameter S4 set Fig 3 3 Key 1 Coil 2 Minimum power adjustment screw 3 Maximum power adjustment nut 4 Gas valve outlet pressure point 5 Gas valve inlet pressure point 6 Protection hood SIT 845 GAS Valve 3 6 CONVERTING THE BOILER TO OTHER TYPES OF GAS If...

Page 23: ...t Note for good functioning of the boiler the temperature selected on the solar valve must be 5 C greater with respect to the temperature selected on the boiler control panel In this condition parameter P0 DHW ther mostat must be set at 1 and the parameter P1 solar delay time at a temperature sufficient to receive water from a storage tank situated up stream from the boiler The greater the distanc...

Page 24: ...rs 2 Remove the decorative frame a from the casing c 3 Loosen the 2 front screws b for fixing the casing 4 Loosen the 2 lower screws b for fixing the casing 5 Pull the case towards yourself c 6 Push the case c upwards at the same time to release it from the upper hooks Installation drawings key Unmistakeable component identification Sequential identification of the operation to perform a 1 1 3 3 2...

Page 25: ...167 GR CZ HU ES IE PT Fig 3 5 4 4 5 6 6 d d c ...

Page 26: ...9 63 98 2 1 12 13 57 138 4 12 0 10320 1 42 3 62 36 9 1 06 8 44 86 0 1 04 11 93 121 7 11 0 9460 1 31 3 11 31 7 0 98 7 31 74 6 0 96 10 35 105 6 10 0 8600 1 20 2 63 26 9 0 89 6 26 63 8 0 88 8 83 90 0 9 3 7998 1 12 2 32 23 7 0 84 5 57 56 8 0 82 7 79 79 4 8 0 6880 D H W 0 97 1 79 18 2 0 73 4 37 44 6 0 71 5 93 60 5 7 0 6020 0 86 1 42 14 5 0 64 3 54 36 1 0 63 4 57 46 6 METHANE G20 BUTANE G30 PROPANE G31 ...

Page 27: ...89 88 METHANE G20 BUTANE G30 PROPANE G31 HEAT OUTPUT HEAT OUTPUT TIMER D H W BURNER GAS FLOW RATE PRESS NOZZLES PRESSURE BURNER GAS FLOW RATE PRESS NOZZLES PRESSURE BURNER GAS FLOW RATE PRESS NOZZLES PRESSURE kW kcal h m3 h mbar mm H2 O kg h mbar mm H2 O kg h mbar mm H2 O 32 0 27520 3 62 12 31 125 6 2 70 27 63 281 7 2 66 35 37 360 6 31 0 26660 3 51 11 68 119 1 2 62 26 05 265 6 2 58 33 48 341 4 30 ...

Page 28: ... 0 50 Heat loss at flue with burner On Off 6 0 0 02 5 60 0 06 6 30 0 04 Central heating circuit max operating pressure bar 3 0 3 0 3 0 Central heating circuit max operating temperature C 90 90 90 Adjustable central heating temperature C 35 85 35 85 35 85 System expansion vessel total volume l 8 0 7 4 8 0 Expansion vessel factory set pressure bar 1 0 1 0 1 0 Water content in generator l 5 0 4 5 4 0...

Page 29: ......

Page 30: ...www immergas com This instruction booklet is made of ecological paper Cod 1 028662 Rev 15 031977 000 02 10 ...

Reviews: