M5 menu
(the password must be entered)
1
st
Level
2
nd
Level
Options
Description
Default value
Value
set
by the
technician
P50
25
÷
50
Set the boiler power in the ignition stage. The value is in percentage
with respect to parameter P62.
(See par. 3.6)
P53
P53.1
Identifies the power of the boiler on which the P.C.B. is installed
P53.1 = Not used
P53.2 = 26 kW
P53.3 = 32 kW.
Equal to boiler
power
Equal to
boiler
power
P53.2
P53.3
P54
P54.1
Displays the temperature read on the domestic hot water probe on
entry to the boiler.
-
-
P54.2
Displays the temperature read on the domestic hot water probe on exit
from the boiler.
-
-
P54.3
Displays the temperature read on the return probe.
-
-
P54.4
Displays the temperature read on the system flow probe.
-
-
P55
Displays the central heating flow temperature at which the boiler
functions, calculated by the controls active on the system heat
adjustment.
-
-
SERVICE
P57
AUTO
- DT = 0: proportional head (see par. 1.23).
- DT = 5
÷
25 K: constant ∆T (see par. 1.23).
AUTO
0
FIX
Fixed circulator pump speed (adjustable between 100% and 54%).
P62
4000 ÷ 5900 Set the maximum output depending on the domestic hot water, setting
the speed of the fan (in RPM).
(See par. 3.6)
P63
900 ÷ 1500 Set the minimum output depending on the domestic hot water, setting
the speed of the fan (in RPM).
(See par. 3.6)
P64
≤ P62
Set the maximum output depending on room heating. The value must
be less than or equal to P62.
(See par. 3.6)
P65
≥ P63
Set the minimum output according to room heating. The value must
be greater than or equal to P63.
(See par. 3.6)
P66
P66/A
With the external probe present it defines the minimum flow
temperature corresponding to operation with maximum external
temperature (see graph Fig. 1-5) (it can be set between 20°C and 50°C).
N.B.:
to continue one must confirm the parameter (press “D” or exit
adjustment “P66” by pressing “C”).
25 °C
P66/B
With the external probe present it defines the maximum flow
temperature corresponding to operation with minimum external
temperature (see graph Fig. 1-5) (it can be set between 50°C and 85°C).
N.B.:
to continue one must confirm the parameter (press “D” or exit
adjustment “P66” by pressing “C”).
55 °C
P66/C
With the external probe present it defines at which minimum external
temperature the boiler must operate at the maximum flow temperature
(see graph Fig. 1-5) (can be set between -20°C and 0°C).
N.B.:
to continue one must confirm the parameter (press “D” or exit
adjustment “P66” by pressing “C”).
-5°C
P66/D
With the external probe present it defines at which maximum external
temperature the boiler must operate at the minimum flow temperature
(see graph Fig. 1-5) (can be set between 5°C and +25°C).
N.B.:
to continue one must confirm the parameter (press “D” or exit
adjustment “P66” by pressing “C”).
25°C
3.9 PROGRAMMING THE P.C.B.
The Magis Victrix boiler is prepared for possible
programming of several operating parameters. By
modifying these parameters as described below, the
boiler can be adapted according to specific needs.
By pressing the button "D" it is possible to access
the main menu, divided into three main parts:
- Information“M1” (See “User” Chapter).
- Customisations “M3” (See “User” Chapter).
- “M5” configurations, menu reserved for
the technician and for which a password is
required.
To access programming, press button “D”, turn
the heating temperature selector switch (3) and
scroll through the menu items until reaching
“M5”, press button “D”, enter the password and
set the parameters according to requirements.
Listed below are the items in the“M5” menu
with default parameters and possible options
indicated.
By turning the heating temperature selector
switch (3) scroll through the menu items. By
pressing button “D” access the various levels
of the menu and the choice of parameters is
confirmed. Press button “C” to go back one level.
(The first item of the various options that appears
inside the parameter is that selected by default).