3.3 INSTALLATION EXAMPLE HYDRAULIC DIAGRAM.
Key:
1 - Boiler
2 - External temperature probe
3 - Comando amico remoto remote control
V2
(CAR
V2
)
4 - Heat pump
AC - Domesic hot water outlet
AF - Domestic cold water inlet
RHT - Return to heat pump
MHT - Flow from heat pump
M - System flow
R - System return
3.4 TROUBLESHOOTING.
N.B.:
maintenance interventions must be carried
out by an authorised company (e.g. Immergas
After-Sales Technical Assistance Service).
- Smell of gas. Caused by leakage from gas circuit
pipelines. Check sealing efficiency of gas intake
circuit.
- Repeated ignition blocks. No gas, check the
presence of pressure in the network and that
the gas adduction valve is open. Incorrect
adjustment of the gas valve, check the correct
calibration of the gas valve.
- Irregular combustion or noisiness. It may be
caused by: a dirty burner, incorrect combustion
parameters, intake-exhaust terminal not
correctly installed. Clean the above components
and ensure correct installation of the terminal,
check correct setting of the gas valve (Off-Set
setting) and correct percentage of CO
2
in flue
gases.
- Frequent interventions of the over heating
safety thermostat. It can depend on the lack
of water in the boiler, little water circulation
in the system or blocked pump. Check on the
manometer that the system pressure is within
established limits. Check that the radiator
valves are not closed and also the functionality
of the pump.
- Drain trap clogged. This may be caused by
dirt or combustion products deposited inside.
Check, by means of the condensate drain cap,
that there are no residues of material blocking
the flow of condensate.
- Heat exchanger clogged. This may be caused by
the trap being blocked. Check, by means of the
condensate drain cap, that there are no residues
of material blocking the flow of condensate.
- Noise due to air in the system. Check opening
of the special air vent valve cap (Part. 28 Fig.
1-28). Make sure the system pressure and
expansion vessel pre-charge values are within
the set limits; The factory-set pressure values of
the expansion vessel must be 1.0 bar, the value
of system pressure must be between 1 and 1.2
bar.
- Noise due to air inside the condensation
module. Use the manual air vent valve (Part.
14 Fig. 1-28) to eliminate any air present in the
condensation module. When the operation has
been performed, close the manual vent valve.
- System low circulation. Check the boiler,
system and heat pump circulator pumps is
working properly.
- Heat pump not working. Check that the heat
pump is powered and the presence of errors
on the relative control panel (see heat pump
instructions manual).
WATER-DHW
NETWORK
HEATING
SYSTEM
COOLING