Immergas AVIO 24 2 ERP Instruction Booklet And Warning Download Page 5

5

INS

TALL

AT

O

R

US

ER

 MAINTEN

AN

CE TECHNI

CI

AN

1.5  GAS ATTACHMENT.

Our boilers are designed to operate with methane 

gas (G20) and LPG. Supply pipes must be the 

same as or larger than the 1/2”G boiler fitting. 

Before connecting the gas line, carefully clean 

inside all the fuel feed system pipes to remove 

any residue that could impair boiler efficiency. 

Also make sure the gas corresponds to that 

for which the boiler is prepared (see boiler 

data-plate). If different, the appliance must be 

converted for operation with the other type 

of gas (see converting appliance for other gas 

types). It is also important to check the dynamic 

pressure of the mains (methane or LPG) used 

to supply the boiler, which must comply with 

the technical standards in force, as insufficient 

levels may reduce generator output and cause 

discomfort to the user. Ensure correct gas cock 

connection. The gas supply pipe must be suitably 

dimensioned according to current regulations 

in order to guarantee correct gas flow to the 

boiler even in conditions of max. generator 

output and to guarantee appliance efficiency 

(technical specifications). The coupling system 

must conform to technical standards in force..

Combustible gas quality. 

The appliance has been 

designed to operate with gas free of impurities; 

otherwise it is advisable to fit special filters 

upstream from the appliance to restore the 

purity of the gas.

Storage tanks (in case of supply from LPG 

depot).

- New LPG storage tanks may contain residual 

inert gases (nitrogen) that degrade the mixture 

delivered to the appliance casing functioning 

anomalies.

- Due to the composition of the LPG mixture, 

layering of the mixture components may occur 

during the period of storage in the tanks. This 

can cause a variation in the heating power of 

the mixture delivered to the appliance, with 

subsequent change in its performance.

1.6  HYDRAULIC ATTACHMENT.

Important:

 In order not to void the warranty 

before making the boiler connections, carefully 

clean the heating system (pipes, radiators, etc.) 

with special pickling or de-scaling products to 

remove any deposits that could compromise 

correct boiler operation.
A treatment of the water of the heating and 

water system is required, in compliance with the 

technical standards in force, in order to protect 

the system and the appliance from deposits (e.g. 

limescale), slurry or other hazardous deposits.
Water connections must be made in a rational 

way. The boiler safety valve outlet must be 

connected to a discharge funnel. Otherwise, the 

manufacturer declines any responsibility in case 

of flooding if the drain valve cuts in.

Attention:

 Immergas declines all liability in 

the event of damage caused by the inclusion of 

automatic filling that is not of its own brand. 
In order to meet the system requirements 

established by the technical regulation in force 

in relation to the pollution of drinking water, 

we recommend installing the IMMERGAS 

anti-backflow kit to be used upstream of the 

cold water inlet connection of the boiler. It is also 

recommended that the heat transfer fluid (e.g. 

water + glycol) entered in the primary circuit 

of the boiler (heating circuit), complies with the 

local regulations in force. 

Important:

 to preserve the life and efficiency of the 

domestic hot water exchanger it is recommended 

to install the “polyphosphate proportioner” kit in 

the presence of water whose characteristics can 

give rise to scale deposits.

1.7  ELECTRICAL CONNECTION.

The “Avio 24 2 ErP” boiler has an IPX4D 

protection rating for the entire appliance. 

Electrical safety of the unit is reached when it 

is correctly connected to an efficient earthing 

system as specified by current safety standards.

Important:

 Immergas S.p.A. declines any 

responsibility for damage or physical injury 

caused by failure to connect the boiler to an 

efficient earthing system or failure to comply 

with the reference standards.
Also ensure that the electrical installation 

corresponds to maximum absorbed power 

specifications as shown on the boiler data-plate 

leads.

Boilers are supplied complete with an “X” type 

power cable without plug. 

The power supply cable must be connected to a 

230V ±10% / 50Hz mains supply respecting L-N 

polarity and earth connection;  , this network 

must also have a multi-pole circuit breaker with 

class III over-voltage category. When replacing 

the power supply cable, contact a qualified 

firm (e.g. the Authorised After-Sales Technical 

Assistance Service).

The power cable must be laid as shown.

In the event of mains fuse replacement on the 

control card, use a 3.15A quick-blow fuse. For 

the main power supply to the appliance, never 

use adapters, multiple sockets or extension leads.

case of walls made from hollow brick or block, 

partitions with limited static properties, or in any 

case walls other than those indicated, a static test 

must be carried out to ensure adequate support.

N.B.: the hex head screws supplied in the blister 

pack are to be used exclusively to fix the relative 

mounting bracket to the wall.
T

hese boilers are used to heat water to below 

boiling temperature in atmospheric pressure. 

They must be connected to a heating system 

and hot water circuit suited to their performance 

and capacity.

Anti-Legionella thermal treatment of the Im-

mergas storage tank (which can be activated 

through the specific function present on the set 

thermoregulation systems): during this phase, 

the water temperature inside the storage tank ex-

ceeds 60 °C resulting in burns hazards. Keep this 

DHW treatment under control (and inform the 

users), to prevent unexpected damage to persons, 

animals and objects. If required, a thermostatic 

valve must be installed at the DHW outlet to 

prevent burns.

1.3  ANTIFREEZE PROTECTION.

Minimum temperature -5°C. The boiler comes 

standard with an anti-freeze function that ac-

tivates the pump and burner when the system 

water temperature in the boiler falls below 4°C.

The antifreeze function is only guaranteed if:

- the boiler is correctly connected to gas and 

electricity power supply circuits;

- the boiler is powered constantly;
- the boiler is on and not in Stand-by;
- the boiler is not in ignition failure block (Par. 

2.7);

-  the boiler essential components are not faulty.

In these conditions the boiler is protected against 

freezing to an ambient temperature of -5°C.

N.B.

: if the boiler is installed in places where 

the temperature falls below 0°C the domestic 

hot water and central heating attachment pipes 

must be insulated.

The water in the storage tank unit is not protected 

against freezing when the boiler is switched off.

1.4  BOILER CONNECTION UNIT.

The connection unit consisting of all the nec-

essary parts to perform the hydraulic and gas 

system connections of the appliance comes as 

standard with the boiler.

Summary of Contents for AVIO 24 2 ERP

Page 1: ...tenance Technician IE 1 038455ENG Wall hung boiler with storage tank open chamber type B and natural draught The European regulation 813 2013 provides that this boiler can be installed only to replace...

Page 2: ...the regulations in force and principles of good practice In compliance with legislation in force the systems must be designed by qualified professionals within the dimensional limits established by t...

Page 3: ...s 13 2 7 Boiler shutdown 14 2 8 Restoring heating system pressure 14 2 9 Draining the system 14 2 10 Draining the boiler 14 2 11 Anti freeze protection 14 2 12 Case cleaning 14 2 13 Decomissioning 14...

Page 4: ...leaks from the hydraulic connections on the contrary the manufacturer cannot be held responsible for any damage caused to the household appliances For the aforementioned reasons we recommend not placi...

Page 5: ...nger it is recommended to install the polyphosphate proportioner kit in the presence of water whose characteristics can give rise to scale deposits 1 7 ELECTRICAL CONNECTION The Avio 24 2 ErP boiler h...

Page 6: ...nnot be used for plants divided into zones Electrical connection of the Remote Friend ControlV2 chronothermostat On Off Op tional or Mini The operations described below must be performed after having...

Page 7: ...eck if the cap is loose Open the radiator air vent valves Close vent valves only when water is delivered Close the filling valve when the boiler pressure gauge indicates approx 1 2 bar N B During thes...

Page 8: ...fficient to press button 1 once To change operation mode press the button for between 2 to 10 seconds until the current configuration flashing each time the button is pressed all possible functions ar...

Page 9: ...tal head available to the system with pump at speed 4 A2 Power absorbed by the pump at speed 2 A3 Power absorbed by the pump at speed 3 A4 Power absorbed by the pump at speed 4 Circulator pump absorbe...

Page 10: ...motorised 7 System filler tap 8 System expansion tank 9 Domestic water probe 10 Stainless steel boiler 11 3 bar safety valve 1 19 BOILER COMPONENTS 12 System emptying tap 13 8 bar safety valve 14 Boi...

Page 11: ...d dangerous to obstruct the air intake even partially for the ventilation of the room in which the boiler is installed Due to the danger operation is also prohibited in the same room as suction device...

Page 12: ...anti freeze function is activated 2 6 FAULT AND ANOMALY SIGNALS The Avio 24 2 ERP boiler signals ant anomaly by flashing of one of the LEDs from 4 to 8 or LEDs 1 and 2 coupled to LED 7 On any remote...

Page 13: ...tioned on Summer or Winter To avoid keeping the system switched on in case of a prolonged absence the system must be drained completely or antifreeze substances added to the heating system water In bo...

Page 14: ...e appliance combustion products check that there is no backflow of combustion products into the room even during functioning of fans 3 1 HYDRAULIC LAYOUT Key 1 Gas valve 2 Stainless steel coil for boi...

Page 15: ...out by an authorised company e g Authorised After Sales Technical Assistance Service Smell of gas Caused by leakage from gas circuit pipelines Check sealing efficiency of gas intake circuit Irregular...

Page 16: ...ases and in an anti clockwise direction it decreases Adjust the boiler minimum thermal input Fig 3 3 N B only proceed after having calibrated the nominal pressure Adjustment of the minimum thermal inp...

Page 17: ...ng Led 8 Heating switch on delay request from Room thermostat and Remote Friend ControlV2 The boiler is set to switch on immediately after a request In the case of particular plants e g area plants wi...

Page 18: ...ntion of electrical main electrical switch on boiler system control thermostat intervention domestic water control thermostat intervention Check that the internal system is properly sealed according t...

Page 19: ...at 0 of O2 at Q Nom Min ppm 177 81 279 115 240 108 Flue temperature at nominal heat output C 101 106 104 Flue temperature at minimum heat output C 74 77 76 METHANE G20 BUTANE G30 PROPANE G31 HEAT POW...

Page 20: ...2 40 0 57 Heat loss at flue with burner On Off 7 20 0 43 Heating circuit max working pressure bar 3 Heating circuit max working temperature C 90 Adjustable heating temperature C 35 85 Total volume sys...

Page 21: ...e technical data are shown on the boiler data plate ENG Model Model code Serial Number Check PIN code Type of installation ref CEN TR 1749 Minimum heating capacity domestic Minimum heating capacity he...

Page 22: ...partial load elmin 0 014 kW Ignition burner energy consumption Pign 0 000 kW In standby mode PSB 0 003 kW Emissions of nitrogen oxides NOX 132 mg kWh For mixed central heating appliances Stated load p...

Page 23: ...ntary heat pump From fiche of heat pump Solar contribution and Supplementary heat pump Select smaller value Boiler and supplementary heat pump installed with low temperature heat emitters at 35 C From...

Page 24: ...energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once installed in a building as the efficiency is influenced by further facto...

Page 25: ...contribution From fiche of solar device 1 I 2 1 1 x I 10 x II III I Auxiliary electricity 3 G F E D C B A A A A 27 27 27 28 27 27 27 28 30 30 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100...

Page 26: ...under colder and warmer climate conditions Colder 0 2 x Warmer 0 4 x Declared load profile Solar contribution From fiche of solar device 1 ___ 2 1 1 x ___ 10 x ____ ____ ____ Auxiliary electricity 3...

Page 27: ......

Page 28: ...mergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 038455ENG rev ST 002233 003 04 18 Irlandese...

Reviews: