4. Function
The unit displays the current system pressure.
It generates output signals according to the operating mode and the parameter setting.
It moreover provides the process data via IO-Link.
The unit is laid out for fully bidirectional communication. So, the following options are possible:
o
Remote display: reading and display of the current system pressure.
o
Remote parameter setting: reading and changing the current parameter setting.
4.1 Communication, parameter setting, evaluation
OUT1 (Pin 4)
Switching signal for system pressure limit value
Communication via IO-Link
OUT2 (Pin 2)
Analog signal 4 ... 20mA / 0 ... 10V
4.2 Switching function
OUTx changes its switching state if it is above or below the set switching limits (SP1, rP1). The
following switching functions can be selected:
Hysteresis function / normally open: [ou1] = [Hno] (→ fig. 1)
Hysteresis function / normally closed: [ou1] = [Hnc] (→ fig. 1)
First the set point (SP1) is set, then the reset point (rP1). The hysteresis defined remains even if
SPx is changed again.
Window function / normally open: [ou1] = [Fno] (→ fig. 2).
Window function / normally closed: [ou1] = [Fnc] (→ fig. 2).
The width of the window can be set by means of the difference b
etween FH1 and FL1. FH1 =
upper value, FL1 = lower value.
P = system pressure; HY = hysteresis; FE = window
t
P
SP
rP
1
0
1
0
Hno
Hnc
HY
FH
FL
1
2