Electronic Pressure Sensor 34D
Operation manual
7503755000000050 05/2019
10. Operation
After power on, the unit is in the Run mode (= normal operating mode). It carries out its
measurement and evaluation functions and provides output signals according to the set
parameters.
Operating indicators → 7 Operating and display elements.
10.1 Read set parameters
►
Press [●].
►
Press [▲] or [▼] until the requested parameter is displ
ayed.
►
Briefly press [●].
o
The unit displays the corresponding parameter value for approx. 30 s; then it changes
to the process value display.
10.2 Self-diagnosis / error indications
The unit has many self-diagnostic options.
It monitors itself automatically during operation.
Warnings and faults are displayed (even if the display is deactivated), in addition they are
available via IO-Link.
Display Status-
LED
OUT1
Status-
LED
OUT1
Error type
Corrective measures
none
Supply voltage too low
►
Check / correct the supply voltage
SC
flashes flashes
Excessive current at
switching outputs OUT1 +
OUT2 *
)
►
Check switching outputs for short-
circuit or excessive current; remove
the fault.
SC1
flashes
Excessive current at swit-
ching output OUT1 *
)
►
Check switching output OUT1 for
short-circuit or excessive current;
remove the fault.
SC2
flashes
Excessive current at
switching output OUT2*
)
►
Check switching output OU2 for
short-circuit or excessive current;
remove the fault.
CLoc
Parameter setting locked via
pushbuttons, para-meter
setting is active via IO-Link
communication (→ 9.1)
►
Wait until parameter setting via
IO-Link is finished.
SLoc
Setting buttons locked via
parameter software. Para-
meter change is rejected (→
9.1).
►
Unlocking only possible via IO-
Link interface / parameter software.
OL
Process value too high.
(measuring range exceeded)
►
Check / reduce system pressure /
select unit with corresponding
measuring range.
UL
Process value too low (value
below measuring range)
►
Check / increase system pressure
/ select unit with corresponding
measuring range.
Measuring range
*) The respective output remains deactivated as long as the excessive current / short circuit
continues.