DAISY CHAIN SPECIFICATION
© Copyright 2020, ILUMINAR Lighting
Subject to change without notice.
1-877-540-5588
iluminarlighting.com
11
8.5A on 20A / 120V
Breaker Load: 42.5%
Do not Exceed 70%
Max Load for Breaker
9.72A on 20A / 208V
Breaker Load: 48.6%
Do not Exceed 70%
Max Load for Breaker
11.8A on 20A / 277V
Breaker Load: 59%
Do not Exceed 70%
Max Load for Breaker
10.92A on 20A / 277V
Breaker Load: 54.6%
Do not Exceed 70%
Max Load for Breaker
12.69A on 20A 480V
Breaker Load: 63.45%
Do not Exceed 70%
Max Load for Breaker
Breaker Needed 20A
Breaker Needed 20A
Breaker Needed 20A
Breaker Needed 20A
Breaker Needed 20A
Breaker Needed 20A
Hardwired Terminal
Connection
8.5A
8.5A x 1 Fixtures = 8.5A on 20A / 120V = 42.5% Load
4.86A x 2 Fixtures = 9.72A on 20A / 208V = 48.6% Load
4.21A x 3 Fixtures = 12.63A on 20A / 240V = 57.8% Load
4.86A
4.21A
4.86A
4.21A
...
3.64A
2.95A
2.12A
3.64A
2.95A
2.12A
...
...
...
3.64A x 3 Fixtures = 10.92A on 20A / 277V = 54.6% Load
2.95A x 4 Fixtures = 11.8A on 20A / 277V = 59% Load
2.12A x 6 Fixtures = 12.72A on 20A / 480V = 63.6% Load
11.56A on 20A / 240V
Breaker Load: 57.8%
Do not Exceed 70%
Max Load for Breaker
120V Daisy Chain Up to 1 Fixtures
208V Daisy Chain Up to 2 Fixtures
240V Daisy Chain Up to 4 Fixtures
347V Daisy Chain Up to 7 Fixtures
277V Daisy Chain Up to 5 Fixtures
480V Daisy Chain Up to 9 Fixtures
70% Max Load for Circuit Breakers, limit is due to Inrush Current
in High End Commercial LED Fixtures
70% Max Load for Circuit Breakers, limit is due to Inrush Current
in High End Commercial LED Fixtures
!
!