DAISY CHAIN SPECIFICATION

© Copyright 2020, ILUMINAR Lighting

Subject to change without notice.

1-877-540-5588       

iluminarlighting.com                    

[email protected]

11

8.5A on 20A / 120V

Breaker Load: 42.5%

Do not Exceed 70%

Max Load for Breaker

9.72A on 20A / 208V

Breaker Load: 48.6%

Do not Exceed 70%

Max Load for Breaker

11.8A on 20A / 277V

Breaker Load: 59%

Do not Exceed 70%

Max Load for Breaker

10.92A on 20A / 277V

Breaker Load: 54.6%

Do not Exceed 70%

Max Load for Breaker

12.69A on 20A 480V

Breaker Load: 63.45%

Do not Exceed 70%

Max Load for Breaker

Breaker Needed 20A

Breaker Needed 20A

Breaker Needed 20A

Breaker Needed 20A

Breaker Needed 20A

Breaker Needed 20A

Hardwired Terminal 

Connection

8.5A

8.5A x 1 Fixtures = 8.5A on 20A / 120V = 42.5% Load

4.86A x 2 Fixtures = 9.72A on 20A / 208V = 48.6% Load

4.21A x 3 Fixtures = 12.63A on 20A / 240V = 57.8% Load

4.86A

4.21A

4.86A

4.21A

...

3.64A

2.95A

2.12A

3.64A

2.95A

2.12A

...

...

...

3.64A x 3 Fixtures = 10.92A on 20A / 277V = 54.6% Load

2.95A x 4 Fixtures = 11.8A on 20A / 277V = 59% Load

2.12A x 6 Fixtures = 12.72A on 20A / 480V = 63.6% Load

11.56A on 20A / 240V

Breaker Load: 57.8%

Do not Exceed 70%

Max Load for Breaker

120V Daisy Chain Up to 1 Fixtures

208V Daisy Chain Up to 2 Fixtures

240V Daisy Chain Up to 4 Fixtures

347V Daisy Chain Up to 7 Fixtures

277V Daisy Chain Up to 5 Fixtures

480V Daisy Chain Up to 9 Fixtures

70% Max Load for Circuit Breakers, limit is due to Inrush Current 

in High End Commercial LED Fixtures

70% Max Load for Circuit Breakers, limit is due to Inrush Current 

in High End Commercial LED Fixtures