Figure 15

Optional Cast Facade installation

Install the Facade per instructions provided in 

Facade Kit (ordered separately - see 

Page 27

).

Framing, Facing And Mantel

The construction of the framing, facing, and 

mantel must be in accordance with the stan-

dards and the following illustrations (

Figures

 

16 and 17

):

A.  Frame the fireplace using 2” x  3” or heavier 

lumber.

B. WARNING:  Combustible materials can-

not be used in the space directly above 

the fireplace, except for the studs above 

the facade that support the facing and 

mantel.  This area must remain empty 

for a height of 6’8” (2,032 mm) mea-

sured from the base of the appliance.

C.  Frame the fireplace with vertical studs at the 

sides of the fireplace running from floor to 

ceiling (see 

Figure 16

). 

 If combustible facing 

is to be used, position the studs back, from 

the front edge of the fireplace (a space that 

is the thickness of the facing material, so 

that the facing can be installed flush with the 

fireplace facing).  Frame headers between 

the vertical studs only as follows:

•  Place 2” x 3”  or  2” x 4” headers, 

only along the upper part of the front, 

side and  back faces (some codes 

may require a 2” x 6” on an outside 

bearing wall).  Do not put wood or 

any combustible material within the 

area above the fireplace except on the 

front facing.

•  Place headers only as required to sup-

port the facing and mantel.

D. WARNING: The fireplace must not be in 

contact with any insulation or loose fill-

ing material. Cover the insulation with 

drywall panels around the fireplace.

HEARTH EXTENSION REQUIREMENTS

The WRT3920WS fireplace may be installed 

directly on a combustible floor. The supplied 

safety metal strip must be positioned as follows:  

One half under the front of the fireplace and the 

other half must extend on the floor over which 

the hearth extension will be built (see 

Figure 14

).

* The safety metal strip must cover the entire 

width of the fireplace
The combustible floor in front of the fireplace 

must be covered with at least a 1/2 inch of 

non-combustible material (tile, marble, stone, 

etc). See 

Figure 15

.

COLD CLIMATE INSTALLATIONS

Climates where temperatures will fall below 

32° F (0° C).

The heating performance of the appliance will 

vary depending upon the level of insulation, 

house design, how the appliance is operated, etc.
If this fireplace is being installed in a cold 

climate, it is especially important to seal all 

cracks around the fireplace and wherever cold 

air could enter the room with noncombustible 

material.  

Also, the outside air inlet duct should be wrapped with noncombustible insulation to minimize 

the formation of condensation. 
Do not place insulation materials directly against the chimney sections.  We recommend that 

you use the insulated wall radiation shield since it will maintain the home’s thermal barrier.  AC 

chimney is NOT recommended in very cold climates (in areas with temperatures below 32°F (-0°C).

WARNING: THE HEARTH EXTEN-
SION IS TO BE INSTALLED ONLY 
AS ILLUSTRATED.

Hearth extension of an elevated fireplace 

must respect the same minimal dimensions 

as a fireplace installed directly on the floor.

Figure 14 - Hearth Extension Requirements

The crack between the fireplace 

and the hearth extension must be 

sealed with a non-combustible ma-

terial such as sand-cement grout.

Safety Metal Strip

Hearth Extension Non-Combusti-

ble Finish Material

Floor

Fireplace

1/2”

13mm

u

 Elevated fireplace installations 

require a special “Z” Metal 

Safety Strips (field provided), 

in place of the safety metal strip 

shown above. The safety strip 

should extend the full width of 

the fireplace.  When more than 

one safety strip is used they must 

overlap by a minimum of 1”.

Platform

2”

Fireplace

Elevated Fireplaces

u

39” 

(990mm)

Min.

18”

Area where wood mantel 

can be installed

Non-Combustible Material

45 Deg.

4”

32-3/4”

17” Min.

Hearth

extension

(457mm)

Min.

(832mm)

Min.

(432mm)

(102mm)

Mantel

12” Max.

(305mm)

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

14

Summary of Contents for Superior Fireplaces WRT3920WS

Page 1: ...andapprovalsofthissystem and could result in an unsafe and potentially dangerous installation IHP wood burning fireplaces are designed for use as a supplemental heater They are not intended for contin...

Page 2: ...intended for use with a gas log set Do not use a fireplace insert or any other product with this fireplace unless it is specified by IHP for use with this appliance Failure to follow these instructio...

Page 3: ...length to be blown in front ofanopenflamewhenthewindow is opened Keep any combustible furniture materials or decorative pillows at least 48 1219 mm from the front fireplace opening WARNING Never leav...

Page 4: ...sthecatalyticcombustor Openingthe CAT bypass damper control increases the draft allowing the unit to achieve proper operating temperatures during a cold start up It also provides more draft to prevent...

Page 5: ...For instance a long chimney will necessitate closing the damper more To obtain the proper combustion closethedampercompletely then open it about 1 4 to 1 2 6 4mm to 13mm Two medium size pieces of woo...

Page 6: ...kesabout15 30minuteswiththeCATbypass opened to reach proper light off temperatures for the catalytic combustor Step 5 Set the primary control to the desired burn level The fireplace will automatically...

Page 7: ...ed to less than 20 Wood properly seasoned is then capable of generating the heat the stove was designed to provide Greenwooddoesnotburneasily Attemptingto burn green wood often results in a lot of smo...

Page 8: ...sweep and put the combustor back in place CATALYTIC COMBUSTOR This fireplace is designed with a catalytic com bustor which will reduce pollution emissions and creosote build up while improving therma...

Page 9: ...better seal and then retightening Catalyst Bypass linkage replacement see Figure 9B Toolsrequired 2 9 16 wrenches 2square drive bit driver Withcatalystbypassinclosedposition remove 2 baffle boards fr...

Page 10: ...ombustorProblem Thermal Cracking ThiscombustordoesNOTexperiencethermalcracking Notap plicable Appliestohoneycombcombustorsonly CombustorProblem CombustorPeeling ThiscombustordoesNOTexperiencecombustor...

Page 11: ...the ashes are cold 24 to 48 hours after the fire is out Do not leave the ashes in the house as they give off carbon monoxide and other toxic gases WARNING DisposalofAshes Ashesshould be placed in a st...

Page 12: ...e Replacement Parts Page 28 DO NOT OPERATE THE UNIT WITH CRACKED OR BROKEN GLASS Glass Cleaning TheWRT3920WSfireplaceisdesignedtokeeptheglasscleanundernormal operating conditions If the WRT3920WS fire...

Page 13: ...replace is determined by considering the location of windows doors and the traffic flow in the room where the fireplace is located allowing space in front of the unit for the hearth exten sion and the...

Page 14: ...must cover the entire width of the fireplace The combustible floor in front of the fireplace must be covered with at least a 1 2 inch of non combustible material tile marble stone etc See Figure 15 CO...

Page 15: ...phs are not to scale consult installation instructions Product designs materials dimensions specifications colorsandpricesaresubjecttochangeordiscontinu ance without notice Allframingdimensionscalcula...

Page 16: ...Side Figure 17 Figure 18 Insulated Chase Construction 7 Ft Min Attic Radiation Shield Roof Support Storm Collar Flashing Drywall or Any Rigid Material 2 x 4 1 2 Plywood 6 8 Min Firestop Floor Ceiling...

Page 17: ...mbustible Facing Drywall 2 x 3 Min Rock Board or Other Spacer Figure 22 A wall on off switch must be installed to control theblower Anoptionalheatswitchandvariable speed control are available see Page...

Page 18: ...ust be non combustible below this area u NOTES Seal the top and both sides of the roof flashing with waterproof caulk ing The gap between the vent pipe and a vertical firestop shall be sealed with non...

Page 19: ...the base of the fireplace C The fresh air must come from outside the house The air intake must not draw air from the attic basement or garage D The air intake should be installed where it is not likel...

Page 20: ...2 feet 3 7 m In altitude add 18 450 mm to the chimney for every 2 000 feet 600 m above sea level 6 All chimney installations must include at least one support Re ducing the amount of chimney weight on...

Page 21: ...the joint between the roof and the flashing with roofing pitch see Figures 34 and 35 For sloping roofs place the flashing under the upper shingles and on top of the lower shingles Nail the flashing to...

Page 22: ...b bob to line up the center of the hole Cut a hole for the chimney in the ceiling floor Frame this hole as described previously refer to section Chimney Instal lation Instructions 5 From below install...

Page 23: ...6 1 8 156 mm 11 280 mm 14 1 8 359 mm 16 7 8 429 mm 18 7 16 468 mm 23 584 mm 26 3 16 665 mm B 27 11 16 703 mm 33 1 2 851 mm 50 7 8 1292 mm 62 1 2 1588 mm 72 5 8 1845 mm 78 7 16 1992 mm 95 3 4 2432 mm...

Page 24: ...Insulated Wall Angel Wall Radiation Shield Insulated Available from Security Chimneys Available from DuraVent Security Chimneys RSM and RSMI30 RSMI45 Canada Only DuraVent 6DTC WTI and 6DTC S30 6DTC S...

Page 25: ...AND MULTIPLE TERMINATIONS For the purpose of this manual a chimney chase is considered a part of the chimney system rather than part of a building The termination must be placed a minimum of 18 460 mm...

Page 26: ...rily install the ASHT elbow on the top of the fireplace and using a level mark with an oval the location where the flue liner will enter the masonry chimney 2 In the middle of the oval drill a hole in...

Page 27: ...er EPA certification If installed this appliance no longer qualifies for EPA certification Check with local authorities having jurisdiction for requirements in your area Central Forced Air Kit Accesso...

Page 28: ...ription Part Cat No Andiron 2 pieces PR SR2875 Bottom refractory PR SR2825 Back refractory PR SR2826 Left side refractory PR SR2828 Right side refractory PR SR2827 Front refractory 2 pieces PR SR2829...

Page 29: ...nd PE Wall Band BM Supports Offset Support SO Roof Support ST Roof Brace BS2 Firestops Firestop 6BF Radiation Shield 6RS Insulated Attic Radiation Shield 6RSA2 Insulated Wall Radiation Shield 6RSM Ins...

Page 30: ...Relining A Masonry Chimney 6 Diameter Listed to ULC S635M UL 1777 and ULC S640M at 2100 F Description Cat Part No 6 Length 6 Dia 6LL6 6LL6 12 Length 6 Dia 6LL12 6LL12 24 Length 6 Dia 6LL24 6LL24 36 Le...

Page 31: ...E MANUEL D INSTALLATION LES COMPOSANTES UTILIS ES AVEC LE FOYER DOIVENT TRE HO MOLOGU ES VOIR LA LISTE DANS LE MANUEL D INSTALLATION REMPLACER LA VITRE AVEC UN VERRE C RAMIQUE DE 5mm D PAISSEUR POUR U...

Page 32: ...ct d damages repairs or inefficiency resulting from faulty installation or application of the Product IHP is not responsible for inadequate system draft caused by air conditioning and heating systems...

Page 33: ...l use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products with abnormal burning cha...

Page 34: ...See Page 28 for a complete replacement parts list Use only parts sup plied from the manufacturer Normally all parts should be ordered through your IHP distributor or dealer Parts will be shipped at pr...

Reviews: