background image

Calculation of Power Requirements

To determine the number of panels required for a given area, one must divide power

rating of the panels into the total power requirements of the area to be heated.
For large open space, fully heated, 100 watts per square metre is recommended. For

spot / zone heating 150 watts is recommended. For fully insulated, closed buildings

50 watts per square metre would be sucient.
Additional wattage maybe required when heating is used intermittently or when fast

warm ups times are required. Lastly remember that in a typical installation, the

panels are thermostatically controlled and so do not run continuously.

First Time Use

When using the panels for the rst time or after a long time period of non use, one

must allow additional time (sometimes up to several days) to heat up the fabric of

the building. Once the core of the building is warm and dry, future heating loads

will be greatly reduced.

Installation

The IHP range of infrared heater panels are a component part of a designed heating

system. To comply with Commission Regulation (EU) 2015/1188 Lot 20, this prod-

uct must be installed and controlled by an external timed thermostat control system.

The supplied product ex must be wired to this control system in accordance with

the manufacturer's instructions to achieve the minimium ecodesign requirement.
Considerations should be given to the addition of open window sensing, occupancy

sensing and out of building heating control systems such as a mobile phone applica-

tion or other device to further increase energy savings. There are many sophisticated

control systems available. Please contact us for assistance if required.

Step 1: Unpack heater, checking contents against the packing list. Remove

packing material from both ends of heater as per Fig. 3.

Table 1: Packing List

Item

Description

Qty

1.

Heater

1 pc

2.

Adjusting Brackets

4 pc

3.

Sliding Bracket

1 pc

4.

Fastener

1 set

5.

Owner's Manual

1 copy

Summary of Contents for MI1000

Page 1: ...ly and should be followed along with any other statutory obligations Do not attempt to open the heater contains no service able parts Attempting to do so will permanently damage the heater and void all warranties Do not operate this heater unless it is properly installed Do not get wet or install where it may fall into water e g bath basin Do not cover This accessory must be tted by a Competent pe...

Page 2: ...paces and even outdoors providing fresh clean heat akin to sunshine Problems associated with convection heating such as condensation temperature laying and dry stu y air are all but eliminated The HIxxxx is a medium intensity heater suitable for ceiling and wall mounting between 3 and 10 metres Key features of the heater include A highly thermally conductive aluminium emitting plate with a high em...

Page 3: ...arm and dry future heating loads will be greatly reduced Installation The IHP range of infrared heater panels are a component part of a designed heating system To comply with Commission Regulation EU 2015 1188 Lot 20 this prod uct must be installed and controlled by an external timed thermostat control system The supplied product ex must be wired to this control system in accordance with the manuf...

Page 4: ... both ends of heater Step 2 Plan your installation ensuring that the heater is at a height of at least 3m and is 200mm from walls Minimium bracket spacing should be determined from Figure 2 Figure 2 Heater and Bracket Positioning ...

Page 5: ...gure 3 Wall Ceiling Bracket Step 4 Assemble heater brackets and slide onto heater as illustrated Do not tighten wing nuts on heater Figure 4 Heater Brackets Step 5 Fix heater to ceiling wall brackets as illustrated This will typically require 2 people for the larger heaters Lastly tighten the wing nuts ...

Page 6: ... Size mm 680x250x145 1080x250x145 1580x250x145 2080x250x145 Net Weight 3 7kg 6 2kg 8 8kg 11 6kg Voltage 220 240VAC Rated Current 4 3A 7 8A 10 4A 13 9A Fuse Rating 5A 13A 13A N A Operating Temp 250 380 C Emitting Plate High emissivity coated Aluminium Heating Element Nichrome core embedded in ceramic substrate IP Rating IP54 To be installed by quali ed personnel only Does not come with plug ...

Page 7: ...ake no responsibility on scratches on face or back after the start of operation We will not assume liability for damages caused by kicks wrong handling humidity or by external treatment Customer Details Product Details Customer Name Product Address Serial No Install Date Email IMPORTANT Please register your purchase at http www infraredheaterpanels co uk page warranty registration Manufacturer s D...

Reviews: