IHP Astra Fireplaces Altair 40DEN-B Operation Instructions Manual Download Page 36

Installation 

900697-00F  06/2019

Innovative Hearth Products
Altair™ Series Direct-Vent Gas Fireplaces

36

Vertical or Horizontal Venting Using Secure Flex

®

 Kits and Components

Secure Flex

®

 venting kits and components may be used in any other vent installation where rigid Secure Vent

®

 

(SV4.5) direct-vent components can be used. All restrictions, clearances and allowances pertaining to rigid vent 

also apply to flexible vent. Do NOT modify Secure Flex kits . Also, do NOT join separate sections of flex vent 

together. Secure Flex kits can be installed on the end of a Secure Vent (SV4.5) rigid vent run, provided that doing 

so does not violate any of the venting length, height, routing, horizontal to vertical ratio requirements, or clearance 

considerations detailed in this manual. When combined, a rigid vent should not be installed between two flexible 

vents.
Secure Flex kits come with an included adaptor that can be installed on the fireplace collar or the inclined channel 

end of the last Secure Vent (SV4.5) vent section in a rigid system in the exact same fashion as any other Secure Vent 

section. Align the dimpled end of the adaptor over the previously installed section or fireplace collar, adjusting the 

radial alignment until the four locking dimples of the adaptor are aligned with the inlets of the four incline channels of 

the last vent section or collar. Push on the adaptor until it is fully engaged, then twist the adaptor clockwise running 

the dimples down and along the incline channels until they seat at the end of the channels. 

Figure 28 - Flexible Vent Adaptor

Figure 29 - Flexible Vent

1.  Install the Inner Flex Pipe. 

a.  Install the small gear clamp loosely around the inner flexible vent, then push it back out of the way.
b.  Apply a bead of Mill-Pac Black (700° F) high temperature sealant (P/N 10K81) to the inner adaptor collar, 

approximately 1/2” from the end.

c.  Pull and extend the inner flexible vent. 
d.  Slide the inner flex vent over the adaptor collar at least 1-3/4”.
NOTE: Ensure the flex vent is free from damage or tears. 
e.  Slide the gear clamp down and tighten it fully to secure the flexible vent to the adaptor inner collar 

approximately 3/4” from the end of the flex.

f.  Install three (3) sheet metal screws 120° apart through the flexible vent and into the adaptor collar just below 

the gear clamp to provide additional security to the connection.

2.  Install the outer Flex Pipe. 

a.  Install the large gear clamp loosely around the outer flexible vent pipe, then push it back out of the way.
b.  Apply a bead of Mill-Pac Black (700 °F) high temperature sealant (P/N 10K81) to the outer adaptor collar. 

Cover to the grooves of the collar that extend approximately 1” from the end and to the flat surface, 

approximately 1-3/8” from the end.

c.  Pull and extend the outer flexible vent. 
d.  Slide the outer flexible vent over the adaptor collar. Ensure the flexible vent completely engages the adaptor collar 

1-3/4” from the end, and that it is free from damage or tears.

Apply ONLY MIL-PAC BLACK 

HIGH TEMPERATURE 

SEALANT (P/N 10K81) to 

the outside surface of both 

collars of the adaptor (fill the 

grooves of the outer collar to 

be covered by the flexible pipe) 

and slide the flexible vent over 

the inner and outer adaptor 

collars

NOTE: Outer vent pipe is pulled away 

to show inner vent pipe details.

Adaptor (SV4.5RF)

Attach adaptor to vent collar or Secure Vent sections

1-3/4” (44 mm) flexible 

vent and adaptor inner 

collar overlap

Securing screws 

in three (3) places 

through perforation 

and into the pipe

Gear clamps

Flexible vent

Flexible vent section

5” (127 mm) 

radius minimum

Shown here: 36” Flex Connector Kit 

(H7748) 

36” of flex with two adaptors for 

mating two rigid sections of vent 

together.

1-3/4” (44 mm) flexible 

vent and adaptor outer 

collar overlap

Securing screws 

in three (3) places 

through perforation 

and into the pipe

Summary of Contents for Astra Fireplaces Altair 40DEN-B

Page 1: ...les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installationetl entretiendoiventêtreassuréspar un installateur ou un service d entretien qualifié ou par le fournisseur de gaz INSTALLER Leave this manual with the appliance CONSUMER Retain this manual for future reference Installateur Laissez cette notice avec l appareil Consommate...

Page 2: ... CALIENTE CAUSARÁ QUEMADURAS USTED NUNCA DEBE TOCAR EL VIDRIO CALIENTE LOS NIÑOS NUNCA DEBE TOCAR EL VIDRIO L écran pare étincelles fourni avec ce foyer réduit le risque de brûlure en cas de contact accidentel avec la vitre chaude et doit être installé pour la protection Des enfants et Des personnes à risques Seproveeconesteaparatouna barreradeproteccion malla diseñadaparareducir el riesgo de quem...

Page 3: ...aduras graves si se toca Mantenga a los niños alejados de la chimenea en funcionamiento Supervise en forma cercana a los niños en cualquier cuarto donde haya una chimenea funcionando para impedir el contacto con el vidrio Mantenga la ropa mobiliario gasolina y otros líquidos inflamables alejados de la chimenea Aún después de haber apagado el gas las superficies de la chimenea permanecen extremadam...

Page 4: ...nwealth of Massachusetts 10 Cold Climate Insulation 10 Manufactured Home Requirements 11 Location 11 Vent Termination Clearances 12 Minimum Clearances to Combustibles 14 Wall Finishes Surrounds Mantels 15 Installation Preparation 15 Installation Installation Sequence 16 Construct the Fireplace Framing 16 Prepare the Fireplace Top Spacers 18 Route the Gas Supply Line to the Fireplace 18 Vent System...

Page 5: ...subir des brûlures s ils viennent en contact avec la surface chaude Il est recommandé d installer une barrière physique si des personnes à risques habitent la maison Pour empêcher l accès à un foyer ou à un poêle installez une barrière de sécurité cette mesure empêchera les tout petits les jeunes enfants et toute autre personne à ris que d avoir accès à la pièce et aux surfaces chaudes 7 Tout écra...

Page 6: ...ols is dangerous Improper installation or use of this appliance can cause serious injury or death from fire burns explosion or carbon monoxide poisoning CARBON MONOXIDE POISONING Early signs of carbon monoxide poisoning are similar to the flu with headaches dizziness and or nausea If you have these signs obtain fresh air immediately Turn off the gas supply to the appliance and have it serviced by ...

Page 7: ...te accessibility clearance for service and proper operation Never obstruct the front openings of the appliance These appliances are designed as supplemental heaters Therefore it is advisable to have an alternate primary heat source when installed in a dwelling Your gas appliance is covered by a limited lifetime warranty You will find a copy of the warranty accompanying this manual Please read the ...

Page 8: ...be kept clean Remarqué L installation et la réparation devrait être confiées à un technicien qualifié L appareil devrait faire l objet d une inspection par un technicien professionnel avant d être utilisé et au moins une fois l an par la suite Des nettoyages plus fréquents peuvent être nécessaires si les tapis la literie et cetera produisent une quantité importante de pous sière Il est essentiel q...

Page 9: ...re 2B The control valves have a 3 8 10 mm NPT thread inlet and outlet side of the valve Figure 1 Millivolt Gas Valve Ecoflow H I LO W H T P T H T P T PILOT P I L O T ON i t O F F IN OUT HI LO Variable Flame Height Adjustment Manifold Pressure Tap Inlet Pressure Tap Pilot Adjustment Screw Main Gas Control Knob OFF PILOT ON SIT Some parts have been removed for clarity 1 8 Inlet line gas pressure tes...

Page 10: ... additional requirements A hard wired carbon monoxide detector with an alarm and battery back up must be installed on the floor level where the gas fireplace is installed The carbon monoxide detector must comply with NFPA 720 be ANSI UL 2034 listed and be ISA certified A metal or plastic identification plate must be permanently mounted to the exterior of the building at a minimum height of eight 8...

Page 11: ...fireplaces are uniquely suited for installations requiring a utility shelf positioned directly above the fireplace Utility shelves like these are commonly used for locating television sets and decorative plants Be aware that this is a heat producing fireplace Objects placed above the unit are exposed to elevated temperatures Do not insulate the space between the fireplace and the area above it The...

Page 12: ...0 12 to 21 12 8 0 ft 2 44 m 12 X Roof pitch is X 12 2 ft minimum 2 ft minimum Lowest discharge opening H H minimum height from roof to lowest discharge opening of vent Horizontal overhang Vertical wall Vent termination Storm collar Concentric vent pipe Flashing 1 26 mm minimum clearance to combustibles TERMINATION HEIGHTS FOR VENTS ABOVE FLAT OR SLOPED ROOFS Table 6 Termination Heights for Vents a...

Page 13: ...ide corner 6 152 mm minimum 6 152 mm minimum H Clearance to each inside of center line extended above meter regulator assembly 36 910 mm within a height of 15 ft above the meter regulator assembly 36 910 mm within a height of 15 ft above the meter regulator assembly I Clearance to service regulator vent outlet 36 910 mm 36 910 mm J Clearance to nonmechanical air supply inlet to building or the com...

Page 14: ...materials However if installed on combustible materials such as carpeting vinyl tile or other combustible material other than wood flooring the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance Hearth Extension A hearth extension is not required with this fireplace If a hearth extension is used do not block the lower control compartment door ...

Page 15: ...end the use of high temperature paint rated 175 F or higher on the underside of the mantel INSTALLATION PREPARATION The fireplace is shipped with all gas controls and components installed and pre wired Before installing the fireplace follow these steps 1 Remove the shipping carton and retain the front of the carton used to protect the fireplace during construction 2 Remove the shipping pad exposin...

Page 16: ...ing Page 39 Gas Connection 14 Connect the Gas Line Page 40 15 Verify Proper Fireplace Operation Page 41 Finishing 16 Optional Install the Firebox Liners Page 42 17 Install the Logs Volcanic Stone and Glowing Embers Page 42 18 Install the Glass Door Page 42 19 Adjust the Air Shutter to Ensure Proper Flame Appearance Page 42 20 Install the Hood in Traditional Fireplaces Page 43 21 Reinstall the Incl...

Page 17: ...tal Termination Table 12 Fireplace Specifications Model A B C D door E F G H I J K 40 Models 37 1 8 943 33 1 4 845 27 1 4 692 37 3 8 949 40 1 4 1022 30 762 15 381 37 7 8 962 6 7 8 175 21 534 12 3 8 315 45 Models 37 1 8 943 33 1 4 845 27 1 4 692 42 3 8 1076 45 1 4 1149 35 889 17 1 2 445 42 7 8 1089 6 7 8 175 21 534 12 3 8 315 NOTE When finishing the area around the hood 5 8 clearance above hood is ...

Page 18: ...zing of Gas Line Properly size and route the gas supply line from the supply regulator to the area where the appliance is to be installed per requirements outlined in the National Fuel Gas Code NFPA 54 latest edition USA or CAN CGA B149 1 latest edition Canada The gas supply line should not be connected to the appliance until step 14 Connect the Gas Line Page 40 NOTE All fireplaces are factory equ...

Page 19: ...ion disc is still in the round cover Re move the flue plug from the top flue Step 5 Remove top flue cover plate and gasket from inside the fireplace 2 screws Separate and note metal side 2 and center 1 brackets Step 1 Remove two screws from the top and side of the unit Bend the side bracket securing tab over the edge of the unit and secure Secure bracket to the top through the clearance screw hole...

Page 20: ...e 17 Retain the panel and screw for later reinstallation 2 Slide the blower through the opening and position it with the bracket oriented to the front of the firebox and the blower discharge to the rear of the firebox Bend the two tabs in the firebox floor to secure the blower to the floor 3 Reinstall the blower cover panel and secure with the removed screw 4 Access the blower supply wiring throug...

Page 21: ... Secure the fireplace to the side framing members using the unit s nailing flanges one top and bottom on each side of the fireplace front Figure 11 Use 8d nails or the equivalent Figure 11 Nailing Flanges Side framing Unit nailing flange no clearance to combustible framing is required VENT SYSTEM PREPARATION 9 Select a Horizontal or Vertical Vent System 1 With the fireplace secured in the framing ...

Page 22: ...ld in place by friction Vent Restrictor with Horizontal Terminations When horizontally terminating a vent system with a vertical vent run up to 4 ft through an exterior wall no vent restrictor is required If installing more than 4 ft of vertical venting install the restrictor Figure 14 from inside or outside the unit in the inner fireplace collar The vent restrictor is held in place by friction Fi...

Page 23: ...ned spaces or where the vent run made up of fixed length pieces develops a joint in a undesirable location or will not build up to the required length The SV4 5LA Telescopic Vent Section has an effective length of from 1 1 2 to 7 38 to 178 mm The SV4 5LA is fitted with a locking inclined channel end identical to a normal vent section component and a plain end with three 3 pilot holes Slip the plai...

Page 24: ...3 465 38 75 0 0 0 0 10 10 69 5 75 0 0 0 2 0 2 475 5 39 625 0 1 0 0 10 11 73 5 6 125 1 0 0 2 0 3 480 40 1 1 0 0 10 12 79 5 6 625 0 1 0 2 0 3 492 41 1 0 1 0 10 12 81 6 75 0 0 0 1 1 2 499 5 41 625 0 0 0 1 10 11 91 5 7 625 0 0 2 0 1 3 504 42 1 0 0 1 10 12 93 7 75 0 0 0 0 2 2 511 5 42 625 0 0 0 0 11 11 97 5 8 125 1 0 0 0 2 3 520 5 43 375 0 2 0 1 11 14 103 5 8 625 0 0 0 3 0 3 531 44 25 0 2 2 0 11 15 108...

Page 25: ...I Z223 1 In Canada the current CAN CGA B149 1 installation code by major building codes Always consult your local codes for specific requirements A general guide to follow is the gas vent rule Table 6 The following figures and their associated vertical vent tables illustrate the various configurations that are possible for use with these fireplaces Secure Vent pipe is shown in these figures Secure...

Page 26: ...tic space is above the ceiling the firestop spacer must be installed on the top side of the joist Route the vent sections through the framed opening and secure the firestop spacer with 8d nails or other appropriate fasteners at each corner Remember to maintain 1 26 mm clearance to combustibles framing members and attic or ceiling insulation when running vertical chimney sections NOTE The gap betwe...

Page 27: ...nly and trim where necessary Seal the top and both sides of the flashing with waterproof caulking The flashing must overlap the roofing material along the bottom 11 Install the storm collar Install the storm collar supplied with the flashing over the vent flashing joint Figure 22 Loosen the storm collar screw Slide collar down until it meets the top of the flashing Tighten the adjusting screw Appl...

Page 28: ...NING Do NOT join separate sections of concentric flexible vent pipe Figure 24 Top Vent Straight Table 16 Rear Vent One 90 Elbow Ceiling firestop spacer SV4 5VF When using Secure Flex use ceiling firestop spacer SF4 5VF 60 ft 18 3 m maximum Ceiling firestop spacer SV4 5VF When using Secure Flex use ceiling firestop spacer SF4 5VF H V Install the U shaped vent restrictor in any vent run with more th...

Page 29: ...of vertical rise See Page 22 for more information If 20 ft of H horizontal vent run is needed then 4 ft straight section minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 ft of V vertical you are allowed 5 ft of H horizontal run up to a maximum horizontal run of 20 ft NOTE The vent system may have a maximum of three 3 90 elbows Minimum 6 ft of vertical ven...

Page 30: ...pace between the bottom of the horizontal run and the attic is provided so that blown in insulation does not contact the vent Figure 25 Typical Horizontal Vent Installation Support bracket spacing every 5 ft 1 52 m Firestop Spacer Vertical Vent Fireplace Vertical Rise Ceiling SV4 5E90 Elbow Support Brackets Building Support Framing Horizontal Inclined Run Termination Termination Exterior Wall SV4 ...

Page 31: ...terminus of the last section is within 7 178 mm to 11 1 4 286 mm inboard of the exterior surface to which the SV4 5HT 2 termination is to be attached Figure 27 If the terminus of the last section is not within this distance use the telescopic vent section SV4 5LA as the last vent section Table 20 lists the additional venting components needed in addition to the termination and adaptor for a range ...

Page 32: ...Square Termination into Exterior Finishing Material SV4 5HT 2 Square Termination Caulk Caulk Stucco Siding Interior Surface of Finished Wall Last Vent Section Use Telescopic Vent Section SV4 5LA If Necessary Maximum Extent of Vent Run Sections Relative to Exterior Surface of Framing Figure 26 Installing the Horizontal Termination Firestop Spacer SV4 5HF shown on the exterior side of the wall It ma...

Page 33: ...t surface and adjust the support straps as necessary NOTE SV4 5VF Secure Vent SF4 5VF Secure Flex firestop spacer must be used any time vent pipe passes through a combustible floor or ceiling SV4 5HF Secure Vent SF4 5HF Secure Flex firestop spacer must be used any time vent pipe passes through a combustible wall WARNING Do not join separate sections of concentric flexible vent together Table 21 Re...

Page 34: ...stop Spacer SF4 5VF When using Secure Flex use Wall Firestop Spacer SF4 5HF Wall Firestop Spacer SV4 5HF Ceiling Firestop Spacer SV4 5VF V H H1 When using Secure Flex use ceiling firestop spacer SF4 5VF When using Secure Flex use wall firestop spacer SF4 5HF Wall firestop spacer SV4 5HF Ceiling firestop spacer SV4 5VF H V H1 Table 25 Top Vent Two 90 Elbows H H1 Maximum V Minimum feet meters feet m...

Page 35: ...rticular range of exterior wall thicknesses If 20 ft of H horizontal vent run is needed then 4 ft minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 ft of V vertical you are allowed 5 ft of H horizontal run up to a maximum horizontal run of 20 ft 6 096 m When using Secure Flex use Ceiling Firestop Spacer SF4 5VF When using Secure Flex use Wall Firestop Spac...

Page 36: ...81 to the inner adaptor collar approximately 1 2 from the end c Pull and extend the inner flexible vent d Slide the inner flex vent over the adaptor collar at least 1 3 4 NOTE Ensure the flex vent is free from damage or tears e Slide the gear clamp down and tighten it fully to secure the flexible vent to the adaptor inner collar approximately 3 4 from the end of the flex f Install three 3 sheet me...

Page 37: ...lex termination and adaptor collars are a different circumference than Secure Vent collars Secure Flex vent has an longer center tube to improve ease of installation 12 Complete the Field Wiring CAUTION The ground supply lead must be connected to the wire attached to the green ground screw located on the outlet box see wiring diagrams Failure to do so will result in a potential safety hazard The a...

Page 38: ... opening and into the unit junction box 4 Connect the black power supply wire to the lower outlet s red pigtail lead Figures 32 33 Connect the white power supply wire to the outlet s common terminal 5 Connect the ground supply wire to the pigtail lead attached to the outlet s green ground screw Restrain the inlet power lead per NEC or local codes 6 If a wall mounted control switch is to be used mo...

Page 39: ...ations Figure 32 Burner 2 Pilot Thermocouple Ground Connector to Chassis Ground or Valve Body Not Polarity Sensitive VCS ECOEXTMOD Extension Module VCS ECOMODPVI Main Module On Off Brown Optional Hi Lo Blue Optional IPI Cont Pilot Yellow Learn Black Some Models Valve Safety Operator Optional Fixed Outlet Some Models MOTOR COMM 120 VAC 120 VAC POWER AUX LIGHTS WHITE RED WHITE BLACK GRAY BLACK MOTOR...

Page 40: ... gas piping within the home to prevent moisture and debris in the line from damaging the valve NOTE Secure all joints tightly using appropriate tools and sealing compounds ensure propane resistant compounds are used in propane applications Seal around the gas line to prevent cold air leakage Gas line holes and other openings can be caulked or stuffed with unfaced fiberglass insulation Figure 34 Co...

Page 41: ...g connection and then retest as described above 3 When the gas lines are tested and leak free rinse off the leak testing solution 15 Verify Proper Fireplace Operation 1 With the gas line installed inspect the system before closing the front of the unit 2 Follow the pilot lighting instructions Millivolt Systems Pages 64 65 Electronic Systems Pages 66 67 Ecoflow fireplaces NOTE When lighting the fir...

Page 42: ...ndicated by black puffs developing at the tips of very long orange flames Sooting results in black deposits forming on the logs fireplace inside surfaces and on exterior surfaces adjacent to the vent termination Sooting is caused by incomplete combustion in the flames and lack of combustion air entering the air shutter opening To achieve a warm yellow orange flame with an orange body that does not...

Page 43: ...Main Burner Shutter Opening Factory Setting 20 Install the Hood in Traditional Models NOTE Traditional models must have a hood installed prior to operation 1 Install the hood by sliding it into the slots on the lower edge of the cabinet top NOTE To install the non combustible finish material flush with the top of the hood the hood must be installed before installing the finish material If finish m...

Page 44: ...ure 40 Combustible Wall Framing Top Of Appliance 3 77 mm This Area Must Remain Clear of Combustible Materials 1 Min 26 mm 4 Clearance Minimum Hood Standoff Provides Space From Combustible Materials Stand Off Must Be Bent To Vertical Position Combustible Finished Wall Materials NOTE See Cold Climate Insulation on Page 10 and Vent Termination Clearances on Page 12 23 Attach the Safety in Operation W...

Page 45: ...ur éliminer la poussière et les traces degraisseoud huile Collezl étiquettesurleboîtier de la télécommande Figure B Choisissez la langue qui est principalement parlée dans la résidence du propriétaire En cas de doute collez l étiquette en anglais 3 Si vous ne trouvez pas les étiquettes veuillez appelerInnovativeHearthProductsouvotredistribu teurInnovativeHearthProductslocalpourrecevoir gratuitemen...

Page 46: ... flex not included Cat No Model Description H1968 SV4 5HT 2 Horizontal Square Termination with Firestop Spacer H2246 and Adaptor 74L61 H2152 SV4 5CGV 1 Vertical Termination Cap High Wind H8914 SV4 5TK90HT2 Horizontal Termination Kit HT 2 with 90 elbow Vent Sections Rigid 77L70 SV4 5L6 6 152 mm 77L71 SV4 5L12 12 305 mm 77L72 SV4 5L24 24 610 mm 77L73 SV4 5L36 36 914 mm 77L74 SV4 5L48 48 1219 mm 77L7...

Page 47: ...FKIT24S Square Term for flex with 24 610 mm compressed flex 77L90 SFKIT36S Square Term for flex with 36 914 mm compressed flex 77L91 SFKIT48S Square Term for flex with 48 1219 mm compressed flex 91L66 SFGC4 6 Gear Clamp 4 5 114 mm for flex 6 pack 91L67 SFGC7 6 Gear Clamp 7 5 190 5 mm for flex 6 pack Cat No Model Description 56L74 SFVT30 Vertical Termination for flex flat to 6 12 with flex adaptor ...

Page 48: ...tions du fabricant fournies avec la trousse Le fournisseur de service qualifié ayant réalisé l installation assume les responsabilités liées à la conversion In Canada The conversion shall be carried out in accordance with the requirements of the provincial authorities having jurisdiction and in accordance with the requirements of the CAN CGA B149 1 Installation code La conversion devra être effect...

Page 49: ...ffected by carbon monoxide than others including pregnant women people with heart or lung disease or anemia those under the influence of alcohol and those at high altitudes NOTE Do not place furniture or other combustible materials within 36 of the front of viewing area s NOTE Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or cl...

Page 50: ...ce versa Nettoyez soigneusement la plaquedurécepteurmuralpouréliminerlapoussière et les traces de graisse ou d huile Collez l étiquette sur la surface de la plaque du récepteur mural qui contrôle le foyer Figure A Choisissez la langue qui est principalement parlée dans la résidence du propriétaire 2 Repérezlatélécommandeetnettoyez lasoigneuse ment pour éliminer la poussière et les traces de graiss...

Page 51: ...a millivolt or electronic system Millivolt Fireplaces Figure 1 Page 9 Electronic Fireplaces Figure 2 Page 9 Familiarize yourself with the gas control valve and the lighting procedure Pages 64 67 Millivolt Fireplaces Detailed lighting instructions are found on Pages 64 65 Also millivolt fireplace lighting instructions are found on the pull out lighting instructions attached to the gas control valve...

Page 52: ...for more information Check the batteries if installed at least every three 3 months to ensure they are properly charged To light the fireplace in a power outage 1 Confirm that batteries are installed battery pack in the control compartment 2 Set the unit mounted switch or wall switch in the control compartment to the ON Position 3 The unit should spark at the pilot and light NOTE If there is no sp...

Page 53: ...cle startup i e the pilot and burner ignite but the burner extinguishes and reignites several times until the flue reaches the temperature for proper drafting To save energy switch to intermittent mode For a standing pilot that will help prevent glass door condensation and cycle startup switch to continuous mode NOTE Continuous mode is indicated by a pilot that comes ON and remains lit when the fi...

Page 54: ...of soot and or the colorless odorless toxic gas carbon monoxide CO NOTE It is important to ensure proper log placement per the manual when installing these units Verify pilot flame is not obstructed See Verifying Appliance Operation on Page 41 NOTE If applicable install the firebox liner before placing the stone Logs can be installed after the volcanic stone Installing the volcanic stone and glowi...

Page 55: ... Upper Left Rear Log 3 Upper Right Rear Log 4 Middle Left Log 5 Front Left Log 6 Front Right Forked Log 7 Upper Right Forked Log Catalog number for the entire set J8300 40 J8302 45 1 If necessary remove the glass door Pages 57 58 2 Position the rear log 1 Figures 51 on the two rear setting pins shown in Figures 50 Figure 49 Locate log setting pins Figure 50 Place log 1 3 Place the left rear log 2 ...

Page 56: ...n Figure 55 One foot will rest between the 2nd and 3rd bar from the left on the grate Figure 53 Place log 4 Figure 54 Place log 5 4 5 Figure 55 Place log 6 7 The front right forked log 6 will roll back onto log 4 Figure 56 It has a setting pin which should face out from the rest of the logs 8 The upper right forked log 7 is the final log in this process Figure 57 It rests on the 4th bar on the set...

Page 57: ...our réduire le risque de brûlure par le hublot chaude est fournie avec l appareil et doit être installé WARNING Do not operate appliance with the glass front removed cracked or broken AVERTISSEMENT Ne pas utiliser l appareil si le panneau frontal en verre n est pas en place est craqué ou brisé WARNING Any safety screen guard or barrier removed for servicing an appliance must be replaced prior to o...

Page 58: ...ly fasten the two 2 latches beneath the firebox floor to the door V flange 4 Install the barrier 5 Close the control compartment door Removing the glass door 1 Open the control compartment door in traditional models Page 40 NOTE If necessary remove the door and place it in a safe location for later reinstallation 2 Remove the barrier Place the barrier in a safe location for later reinstallation 3 ...

Page 59: ...inspections and cleanings should be performed by the homeowner NOTE Inspect exhaust termination for blockage or obstruction such as plants bird nests leaves snow debris etc NOTE Prior to the first use of the fireplace and each burn season and periodically during the burn season inspect the horizontal termination for debris such as bird nests leaves paper or branches Remove any items from the surfa...

Page 60: ...e brush e g paint brush Reinstalling the embers and logs Carefully follow the placement instructions Page 54 All logs should fit onto the corresponding pins and or log stoppers This will ensure proper flame and safe combustion NOTE Improper positioning of logs can create carbon build up and will alter the performance of the fireplace Replacing the logs If the logs become damaged and need replaceme...

Page 61: ...uction Look for any signs of dislocation of the vent components Fireplace Inspection Qualified Service Technician Perform the appropriate fireplace inspection procedure detailed in this manual Replacing Glowing Embers Homeowner Qualified Services Technician Remove the old glowing embers and vacuum the area Place new glowing embers Figures 48 49 Replacing Batteries Homeowner Qualified Services Tech...

Page 62: ...rmination Catalog Model Description H5820 4 5HTSK Termination Shroud 87L02 SV4 5HGS Termination Guard Deluxe Deluxe Termination Guard fits H1968 Termination Shroud fits H1968 Touch Up Paint Kits Repair minor scratches and discoloration of the fireplace black painted surfaces with the touch up paint kits Firebox Liner Kits Cat Model Description Used on F2908 EBLK40OTR S Old Town Red Ceramic Stacked...

Page 63: ... Low battery indicator Batteries included H8860 Model RC S 1 WS S TMR Wall Control Catalog Number 4 button timer with 30 60 120 OFF minutes Wall mounted Perfect for rental and resort applications Connects to wall switch wire H8863 Model WS S TMR OFF ON Wall Switch Kit Millivolt Models The OFF ON wall switch kit can be used to control the operation of the fireplace burner or blower Install the OFF ...

Page 64: ... gas supplier LIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE If the pilot will not stay lit after several tries turn the gas control knob to OFF and call your service technician or gas supplier 10 Turn gas control knob counterclockwise to ON 11 Close control compartment 12 If applicable Turn on all electrical power to the appliance 13 If applicable Set thermostat to desired setting Turn wall o...

Page 65: ...iatement un technicien qualifié ou le fournisseur de gaz Si la veilleuse ne reste pas allumée après plusieurs tentatives réglez la manette d admission du gaz à la position OFF et appelez un technicien qualifié ou le fournisseur de gaz 10 Tournez le bouton de réglage du gaz en sens inverse des aiguilles d une montre jusqu à sa position de marche ON 11 Fermer le compartiment de contrôle 12 Si applic...

Page 66: ...ch has been under water Copreci Gas Valve Switches Electronic Pilot Assembly 3 Turn off all electric power to the appliance if service is to be performed Note The control may have a battery backup remove batteries if installed 4 Close the main line gas shut off valve 1 STOP Read the safety information above on this label 2 Read the Care and Operation manual including the section on Remote Control ...

Page 67: ...IDIE NE LAISSEZ JAMAIS UN ENFANT DE TOUCHER LA VITRE L écran pare étincelles fourni avec ce foyer réduit le risque de brûlure en cas de contact accidentel avec la vitre chaude et doit être installé pour la protection Des enfants et Des personnes à risques Interupteurs Option Hi Lo MARCHE ARRÊT Option IPI Mode Intermittent Veilleuse Apprenez Quelques modèles Jaune Bleu Brun fil noir 1 ARRÊTEZ Lisez...

Page 68: ...ly following the lighting instructions a Defective pilot generator thermocouple Check pilot flame it must impinge on thermocouple Clean and or adjust pilot for maximum flame impingement on thermocouple Ensure that the connection between the valve and thermocouple are tight and secure 3 Pilot burning no gas to burner Valve knob ON and the standard burner OFF ON switch is ON NOTE If an optional wall...

Page 69: ...eck the gas supply and gas shutoff valves b Loose wires to the valve or ignition module Check control compartment for any obviously loose wiring call a service technician if necessary c Pilot flame is not engulfing the sensor Call a service technician d Obstructed vent system Call a service technician 4 Soot is present on the logs and glass a Excessive flame impingement on the logs Properly positi...

Page 70: ... Stopper Plug J7356 1 J7356 1 3 Burner Assembly Front F2921 1 F2921 1 Burner Assembly Rear F2919 1 F2920 1 Burner Rod F2924 1 F2924 1 3 8 Flare Tee F2923 1 F2923 1 Pilot Bracket F2922 1 F2922 1 Air Shutter Control Arm F2925 1 F2925 1 Grate Assembly F2926 1 F2926 1 Manning Glass Gasket F2116 1 F2116 1 Trim Kit Stainless F2469 1 n a n a Trim Kit Black F2471 1 n a n a Astria Badge logo J7593 1 J7593 ...

Page 71: ...e J7959 1 J7959 1 Wire harness Traditional Ecoflow J7956 1 J7956 1 Regulator Liquid Propane J7958 1 J7958 1 Regulator Natural Gas J7934 1 J7934 1 Ecoflow V Wire J7933 1 J7933 1 Ecoflow Remote wire harness F2690 1 F2690 1 Ecoflow RF Control Module F2694 1 F2694 1 Ecoflow Power Adaptor J7930 1 J7930 1 Ecoflow Battery Holder J7931 1 J7931 1 9 Ecoflow Wireless Wall Switch F2660 1 F2660 1 Switch Rocker...

Page 72: ...sque de dommages ou de blessures si les pièces ne sont pas installées conformément à ces schémas et ou si des pièces autres que celles spécifiquement approuvées avec cet appareil sont utilisées REPLACEMENT PARTS continued ON OFF HI LO Cat No Model Description F2644 Altair40DMN B 40 DV MV Black Interior NG F2645 Altair40DMP B 40 DV MV Black Interior LP F2646 Altair40DEN B 40 DV Elec Black Interior ...

Page 73: ... fire flood or acts of God b damages caused by abuse negligence misuse or unauthorized alteration or repair of the Product affecting its stability or performance The Product must be subjected to normal use The Product is designed to burn either natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive te...

Page 74: ... Date fireplace was Installed Type of gas fireplace uses Dealer name Innovative Hearth Products IHP reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information Printed in U S A 2016 Innovative Hearth Products P N 900697 00 Rev F 06 2019 1769 E...

Reviews: