background image

7

 

 

 

 

Automatic air release valves 

 

In order to ensure that no air clogs occur in the outdoor circuit system and that the heat pump 

does  not  signal  an  alarm  as  a  result,  it  is  necessary  to  install  automatic  air  release  valves  on  the 
outdoor circuit. The air release valves must be installed at the highest points of the circuit. 

 

Outdoor circuit pump 

 

The outdoor circuit pump is included in the heat pump set and is installed in the device at the 

factory.  The  Grundfos  UPM3  pump  (see,  Annex  No  2)  is  the  most  commonly  used  for  the  outdoor 
circuit,  and  the  UPMXL  heat  pumps  with  a  capacity  of  more  than  11  kW  (see,  Annex  No  2).  The 
circulation  pump  is  controlled  by  the  central  processor  while  maintaining  optimal  flow.  The  control 
system monitors the operation of the circulation pumps and a warning is received in  the event  of a 
deviation. 

 

INTERNAL CIRCUIT 

 

To avoid gas formation, it is recommended not to use galvanised pipe systems. 

 

WARNING! 

The area of the domestic hot water tank heat exchanger must correspond to the capacity of 
the heat pump. The water capacity must be such that the heat output of the heat pump is 
transmitted as efficiently as possible. 

NOTE 

Integrate the hot water tank into the heat pump system to match the heating system scheme 
you have selected (see, pages 14-17). 

 

Heating system filling 

 

Set  the  pressure  of  the  heating  circuit  in  the  expansion  vessel  to  1.5  bar.

  Usually  the 

replenishment of the heating circuit is stationary, pre-connected to the water inlet, in which case the 
replenishment takes place individually according to the system. If the filler in the heating circuit is not 
water,  then  the  system  is  filled  with  the  appropriate  liquid.  As  an  additional  protection  against 
freezing,  in  some  cases  the  water  in  the  heating  system  may  be  mixed  with  glycol,  however,  this 
concentration should not exceed 15%. In this case, the efficiency of the heat pump decreases. 

 

Summary of Contents for Aleut Series

Page 1: ...INSTALLATION MANUAL IGLU Aleut Series...

Page 2: ...lling 8 THERMAL INSULATION 9 ELECTRICAL CONNECTION WORKS 9 Temperature sensors 10 Characteristics of temperature sensors NTC 10K 10 Phase sequence relay 10 Control panel 11 START OF OPERATION 11 HEAT...

Page 3: ...iler 28 Technical data of IGLU Aleut 11 WT fixed capacity heat pump with boiler 29 Technical data of IGLU Aleut 13 WT fixed capacity heat pump with boiler 30 Technical data of IGLU Aleut 18 WTI heat p...

Page 4: ...tall the devices Treat all constituents responsibly The heat pump may only be used for its intended purpose which means heating domestic hot water preparation coolinstr The device can only be operated...

Page 5: ...vice and its components may only be carried out by qualified specialists heating refrigeration coolant technicians and electricians WARNING Observe the safety signs on and inside the device WARNING Th...

Page 6: ...OUTDOOR CIRCUIT Installation and filling The outdoor circuit can be vertical boreholes or horizontal The horizontal circuit must be installed below the freezing zone depending on the ground of the ins...

Page 7: ...RCUIT To avoid gas formation it is recommended not to use galvanised pipe systems WARNING The area of the domestic hot water tank heat exchanger must correspond to the capacity of the heat pump The wa...

Page 8: ...e system The presence of air in the system produces corrosive products such as magnetite or sediment Magnetite has an abrasive effect that is especially enhanced in pumps valves or eddy flow component...

Page 9: ...ecial means of thermal insulation in accordance with current standards The main normative document which defines the requirements for thermal insulation is Order No 1 245 of the Minister of Energy of...

Page 10: ...5 0 262 20 0 96360 60 0 2490 140 0 232 15 0 72502 65 0 2084 145 0 206 10 0 55047 70 0 1753 150 0 183 5 0 42158 75 0 1481 155 0 163 0 0 32555 80 0 1256 160 0 145 5 0 25339 85 0 1070 165 0 130 10 0 1987...

Page 11: ...ce with the requirements of this operating manual the electrical installation works have been properly performed the heating circuit has been flushed and properly filled all valves and shut off device...

Page 12: ...r to vandens vo tuvas V sinimo vo tuvas NO5 C4 C5 C3 NO3 Boilerio teno rel NO5 C5 NC5 COM DI1 A1 13 KU1 13 14 Operatoriaus panel CAN RJ COM P1 P2 X1 1 X1 2 X1 6 X1 5 X1 4 X1 3 M M2 M M3 KM1 A2 F1 14 X...

Page 13: ...omatinio jungiklio Kambario temp daviklio gnybt rinkl s Boilerio temp daviklio gnybt rinkl s Kabelinis latakas Element tvirtinimo plok t Heat pump inlet from a separate circuit breaker Neutral termina...

Page 14: ...mperature medium The manufacturer recommends the use of underfloor heating for this connection method Each heat pump has the ability to connect to the Internet so you can see the heat pump settings an...

Page 15: ...l flowing from the outdoor circuit during the warm season The outdoor circuit cannot be used for cooling and heating at the same time Each heat pump has the ability to connect to the Internet so you c...

Page 16: ...nk up to 30 of the heating circuit can be closed at the same time Variable capacity heat pumps do not require buffer capacity Each heat pump has the ability to connect to the Internet so you can see t...

Page 17: ...Variable capacity heat pumps do not require buffer capacity For fan radiators additional pipes must be laid from the outdoor circuit to which they will be connected via a three way valve The outdoor c...

Page 18: ...essure bar 45 Heating system Rated flow DT 7K m3 h 1 00 1 50 2 00 2 00 2 20 Min flow temperature C 15 Max flow temperature C 60 Max permissible operating pressure bar 4 0 Connection Cu mm 28 Power net...

Page 19: ...Rated flow DT 7K m3 h 1 00 1 50 2 00 2 00 2 20 Min flow temperature C 15 Max flow temperature C 60 Max permissible operating pressure bar 4 0 Hot water tank volume l 200 Capacity material Stainless s...

Page 20: ...85 1 32 4 43 Compressor power 60 rps kW 13 00 2 84 4 58 Compressor power 85 rps kW 18 60 4 32 4 31 Compressor Type Scroll Mass of refrigerant R410A kg 2 20 Maximum pressure bar 45 Heating system Hot...

Page 21: ...5 64 Tj 7 C Pdh 5 72 kW Tj 7 C COPd or PERd 5 71 Tj 12 C Pdh 5 81 kW Tj 12 C COPd or PERd 5 85 Tj Tiv bivalent temperature mode Pdh kW Tj Tbiv bivalent temperature mode COPd or PERd Tj operating limi...

Page 22: ...2 C Pdh 7 92 kW Tj 12 C COPd arba PERd 5 84 Tj Tbiv bivalent temperature mode Pdh kW Tj Tbiv bivalent temperature mode COPd arba PERd Tj operating limit temperature Pdh kW Tj operating limit temperatu...

Page 23: ...2 C Pdh 9 82 kW Tj 12 C COPd arba PERd 5 85 Tj Tbiv bivalent temperature mode Pdh kW Tj Tbiv bivalent temperature mode COPd arba PERd Tj operating limit temperature Pdh kW Tj operating limit temperatu...

Page 24: ...j 12 C Pdh 11 87 kW Tj 12 C COPd arba PERd 6 08 Tj Tbiv bivalent temperature mode Pdh kW Tj Tbiv bivalent temperature mode COPd arba PERd Tj operating limit temperature Pdh kW Tj operating limit tempe...

Page 25: ...j 12 C Pdh 14 05 kW Tj 12 C COPd arba PERd 6 24 Tj Tbiv bivalent temperature mode Pdh kW Tj Tbiv bivalent temperature mode COPd arba PERd Tj operating limit temperature Pdh kW Tj operating limit tempe...

Page 26: ...71 Tj 12 C Pdh 5 81 kW Tj 12 C COPd arba PERd 5 85 Tj Tbiv bivalent temperature mode Pdh kW Tj Tbiv bivalent temperature mode COPd arba PERd Tj operating limit temperature Pdh kW Tj operating limit te...

Page 27: ...74 Tj 12 C Pdh 7 92 kW Tj 12 C COPd arba PERd 5 84 Tj Tbiv bivalent temperature mode Pdh kW Tj Tbiv bivalent temperature mode COPd arba PERd Tj operating limit temperature Pdh kW Tj operating limit te...

Page 28: ...79 Tj 12 C Pdh 9 82 kW Tj 12 C COPd arba PERd 5 85 Tj Tbiv bivalent temperature mode Pdh kW Tj Tbiv bivalent temperature mode COPd arba PERd Tj operating limit temperature Pdh kW Tj operating limit te...

Page 29: ...5 89 Tj 12 C Pdh 11 87 kW Tj 12 C COPd arba PERd 6 08 Tj Tbiv bivalent temperature mode Pdh kW Tj Tbiv bivalent temperature mode COPd arba PERd Tj operating limit temperature Pdh kW Tj operating limit...

Page 30: ...5 98 Tj 12 C Pdh 14 05 kW Tj 12 C COPd arba PERd 6 24 Tj Tbiv bivalent temperature mode Pdh kW Tj Tbiv bivalent temperature mode COPd arba PERd Tj operating limit temperature Pdh kW Tj operating limit...

Page 31: ...Tj 12 C Pdh 12 80 kW Tj 12 C COPd or PERd 5 71 Tj Tbiv bivalent temperature mode Pdh kW Tj Tbiv bivalent temperature mode COPd or PERd Tj operating limit temperature Pdh kW Tj operating limit tempera...

Page 32: ...PM3 K FLEX AS 25 75 180 UPM3 K FLEX AS 25 75 180 IGLU Aleut 9 WT 9 KW UPM3 K FLEX AS 25 75 180 UPM3 K FLEX AS 25 75 180 IGLU Aleut 11 WT 11 KW UPM3 K FLEX AS 25 75 180 UPMXL 25 125 180 PWM IGLU Aleut...

Page 33: ...33 Annex No 3 UPM3 K FLEX AS 25 75 180 characteristic UPM3 K FLEX AS 25 75 180 electrical parameters 1 x 230 V 50 60 Hz Speed P1 W I1 A Min 2 0 04 Max 60 0 58 Dimensions of the UPM3 circulation pump...

Page 34: ...o 4 UPMXL GEO 25 125 180 PWM 1 x 230 V 50 60 Hz characteristics UPMXL GEO 25 125 180 PWM electrical parameters 1 x 230 V 50 60 Hz Speed P1 W I1 A Min 3 0 06 Max 180 1 4 Dimensions of the UPMXL circula...

Page 35: ...inan io glikolio pajungimo atvamzdis E i einan io glikolio pajungimo atvamzdis F G angos elektrini pajungim kabeliams Where A supply heating water connection nozzle B nozzle of heating water supplied...

Page 36: ...Annex No 6 Design dimensions of the heat pump from the front Design dimensions of the heat pump from the top 120cm 180cm 62cm 62cm 5cm 5cm 62cm 62cm 80cm 80cm 62cm 80cm 80cm 5cm 62cm 62cm 120cm 180cm...

Page 37: ...__________________________________________ _____________________________________________________________ _____________________________________________________________ _________________________________...

Reviews: