It is recommended to follow the set up sequence below when configuring and installing a control
panel from new.
Note panels are usually supplied pre-configured so this many not be necessary, check
shipping documentation
Perform a sensor FIND and automatically install detector data. Engineers Menu .... Find Option
Perform a Relay FIND
With Sensors and Relays Installed download the panel setup to IGD’s Panel Seup App to configure
the system. It will be necessary to upload this once completed and re-start the controller for it to take
effect.
Allow the system to run for at least an hour to allow detectors to fully stabilise to the site conditions.
Detectors are supplied pre-calibrated. Follow the Bump Text video on the IGD online Academy to
check both detector calibration and to prove the system programmed cause and effect. Ensure all
interfaces to third party devices and systems function as required. Note that individual relays can be
directly energised and de-energised to aid checking
Should any detectors require re-calibration
Zero each connected detector. User Menu ZERO
Calibrate each detector. User Menu CALibrate
Ensure there are no indicated system errors in normal operation.
Note IGD calibration and gas adaptor kits are available and necessary to perform calibration and
bump testing. Record all results for traceability.
find sen
1 of 12
find rly
1 of 12
zero
1 of 15
cal
2 of 15
Putting Into Service
Note that this product should be supplied via a fused spur. Ensure cables used are suitable for both
their intended area of operation and load capability. This product should only be installed by a
competent person.
If you are uncertain how to zero/calibrate or locate your gas detectors and system components then
use IGD’s online training academy.
If your application is safety related you must ensure you are a competent person with demonstrable
training. If in doubt check with IGD for help and support.
Follow the 2-Wire Installation guide
This provides location as well as cabling/installation guidance.
Failure to observe correct installation can have an adverse affect on system operation
and performance
if you don't have a copy of this download it from www.internationalgasdetectors.com
To set alarm levels and programme the required cause and effect you will need to
access the controller using IGD’s Panel Setup App for Android. Download the Panel
Setup App from the Google Play Store to a suitable blue tooth enabled tablet or
Phone. Android 5 or later operating system and min 7” display recommended.
NOTE TOC-635 MICRO has a fixed controller setup based on detectors fitted and does
not have a WIFI/Bluetooth Interface. IGD Android software is not available for this model