SL-014 v1.6 Page4
Document Ref: SL-014 v1.6
Basic Specification
Features
Other I/O
Inputs
Measurement
Ranges, Based
on Sensor
Temperature
Usage
Humidity
Sealing
Mounting
Maximum Altitude
Weight
Power
Construction
Display
User
Outputs
Sounder 85dB @ 300mm (Mutable)
1 off RS485 Port Modbus in/out (PLUS only)
2 off Multi-Function Inputs mA or Digital (PLUS only)
6 User Defined Alarm Indication LEDs
Illuminated RGB Light Ring, Alarm, Fault, Menu etc
Up to 8 or 32 off Addressable Series Detectors or I/O Modules see feature table
Note external Booster PSU may be required
0-100 %LEL, 0-100% Vol, 0-25% Vol, 0-5pppm, 0-25ppm, 0-100ppm, 0-500ppm,
0-1000ppm, 0-5000ppm
-20 to +55 Deg C Full Specification.
Indoor use
20-90% RH Non-Condensing
IP54
Wall Mount
2000m
1.2Kg
110-230V AC 50/60Hz 57W (Full Load)
ABS
2 Lines x 8 Digit LCD Display
Multi-Colour Backlight (Red-Alarm, Yellow-Fault,
Blue-Normal)
IGD Jog Wheel Option Select, Alarm Reset, RGB
3 off SPCO Relays 4A Non-Inductive User
Configurable
1 off Fault Relay SPCO Relays 4A Non-Inductive
1 off Solid State Beacon Sounder Output
Additional Digital Inputs/Relay Outputs Can Be
Added To Highways if Required see feature table for
model differences
Detector Ports
Supported Detectors/Modules
On-Board relays
External Relays/SSR
Digital Inputs
WiFi Connectivity
Real Time Clock
RGB Display
Illuminated RGB Menu Wheel
6 Assignable Alarm LEDs
Sounder
Event Log Report
Beacon Sounder Output Port
Modbus Connectivity
Battery Backup Port
System Status Report
Calibration Status Report
TOC-635-PLUS
1
99
4
99
2
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
TOC-635-MICRO
1
8
2
24
0
NO
NO
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
Overvoltage
Catagory
Pollution Degree
OVC II