47
TAG PLATE
20mm Plastic Conduit Mounted
Using Metal Saddles and Fixings
as Required to be Compliant
With BS7671 amendment 3 Reg
521.11.201
Note Conduit Size Large Enough
For One FP200 Cable Run and
Accessory Cable Type 4502 FE
DO NOT Attempt to Enlarge
20mm Entries, This Will
Invalidate Warranty and
Damage Enclosure Sealing.
Tag Plate Available as an
Option to Match Control
Panel Screen Display
Location Tags. If
Required Order as TOC-
TAG-A and supply Table
of Required Tag
Descriptions
Gas Detectors Mounted Above/Below Dado Style Wall Trunking
System.
Ensure Segregation From Mains Cabling. Ensure Cable is Only Run
in Trunking Data Compartments. Where Other Cables Use This
Compartment Ensure They Are Only Data Cables. Do Not Run Any
Mains Powered Loads Through The Data Section of the Trunking
Preferred Cable Type 2
Core FP200 Min
1.5mmSQ, Check Cable
Sizing to IGD Guide
Installation to be in Accordance with BS6761 amendment 3 Reg 521.11.201,
BS EN 7671:2008, BS EN 50174-2, BS EN 6701:2016 and BS6739:2009
Typical Room Installation Scheme E onto Dado Trunking Systems