Up to 32 counters can be configured to measure the duration of exceeding the
limit and/or operating times�
The signals at the inputs are permanently picked up and continuously monitored
according to the set parameters�
With objects within the frequency range (imbalance, rolling element bearing ���) the
duplex mode is used for monitoring�
With objects within the time range (v-RMS, a-RMS and a-Peak) all 4 dynamic
inputs are monitored simultaneously and without interruption�
The two outputs OU1/2 can be used for alarms� The respective object states per
sensor are also indicated via the 4 sensor LEDs�
The system LED displays the operating status of the device�
Parameter setting of the monitoring tasks and alarming is effected by the VES004
software� The software allows to display and record the current measured values,
spectra and time signals (online data)�
Via the Ethernet interface of the device, networking is possible to visualise data
(measured values, alarm states, ���) in other systems (e�g� SCADA, MES, ����)�
Data (e�g� measured values, alarm states, limits, rotational speeds, timer readings,
���) is exchanged between the diagnostic electronics and the EtherNet/IP controller
via the EtherNet/IP ports�
6 Installation
► Mount the unit in a control cabinet with a protection rating of at least IP 54 to
ensure protection against accidental contact with dangerous contact voltages
and against atmospheric influence�
The control cabinet should be installed in accordance with local and national rules
and regulations�
► Mount the unit vertically on a DIN rail�
► Leave enough distance to neighbouring heat sources and between the unit and
the top or bottom of the control cabinet to enable air circulation and to avoid
excessive heating�
► Prevent penetration of conductive or other dirt during installation and wiring�
When preparing for cable installation, the local conditions and the corresponding
mounting regulations are very important� Cables can be installed, for example, in
cable ducts or on cable bridges�