6.1.2  Device-specific information

You will find the IODDs necessary for the configuration of the IO-Link unit and 

detailed information about process data structure, diagnostic information and 

parameter addresses at  www�ifm�com/gb/io-link� 

6.1.3  Parameter setting tools

You will find all necessary information about the required IO-Link hardware and 

software at  www�ifm�com/gb/io-link�

7  Parameter setting

Using an IO-Link capable parameter setting tool, the following options are avail-

able:

 - Reading current process values�
 - Reading, changing and saving current parameter settings and transmitting 

them to other units of the same type�

 

► Connect the unit via the IO-Link interface to a PC or PLC with suitable param-

eter setting software� 

ifm offers an IO-Link interface for the connection of the sensor via USB 

port�

7.1  Adjustable parameters

OU

Output function

Analogue output signal:

[I]:

4���20 mA

[Ineg]: 20���4 mA

ASP

Analogue start point 

for temperature

With setting [OU] = [I]:

Measured value at which the output signal is 4 mA�

With setting [OU] = [Ineg]: 

Measured value at which the output signal is 20 mA�

AEP

Analogue end point 

for temperature

With setting [OU] = [I]:

Measured value at which the output signal is 20 mA�

With setting [OU] = [Ineg]: 

Measured value at which the output signal is 4 mA�

Minimum distance between ASP and AEP = 5 °C or 9 °F�

COF

Zero-point calibra-

tion

Setting range: ± 10 K in steps of 0�1 K� The internal 

measured value "0" is shifted by this value�

Summary of Contents for TA1 Series

Page 1: ...Operating instructions Temperature transmitters TA1xxx TA2xxx 80269598 00 10 2017 UK ...

Page 2: ... IO Link 6 6 1 1 General information 6 6 1 2 Device specific information 7 6 1 3 Parameter setting tools 7 7 Parameter setting 7 7 1 Adjustable parameters 7 8 Operation 8 9 Technical data 8 10 Factory setting 8 1 Remark 1 1 Explanation of symbols Instructions Reaction result Designation of keys buttons or indications Cross reference Important note Non compliance can result in malfunction or interf...

Page 3: ... must only be carried out by qualified personnel authorised by the machine operator In order to guarantee the correct condition of the device for the operating time it is necessary to use the device only for media to which the wetted materials are sufficiently resistant Technical data The responsibility whether the measurement devices are suitable for the respective application lies with the opera...

Page 4: ...P 20 6 20 4 3 7 MAW initial value of the measuring range MEW final value of the measuring range ASP analogue start point AEP analogue end point Within the measuring range the output signal is between 4 and 20 mA If the tem perature value is outside the limits of the measuring range the following output signal is displayed Output signal at OU I Output signal at OU Ineg Temperature AEP 20 20 6 mA 4 ...

Page 5: ...s Make sure that the sensors are integrated into the system in accordance with 3A Tighten seals to defined torque and ensure seals are centered Use in hygienic areas to EHEDG Make sure that the sensors are integrated into the system in accordance with EHEDG 5 1 Units with G sealing cone type TA25xx About sensor installation conforming to 3A Insert PEEK sealing ring E43911 Carry out installation ac...

Page 6: ...4 wire unit Pin 1 L L Pin 2 Analogue signal for temperature Analogue signal for temperature Pin 3 L Pin 4 IO Link 6 1 IO Link 6 1 1 General information This unit has an IO Link communication interface which requires an IO Link capa ble module IO Link master for operation The IO Link interface enables direct access to the process and diagnostic data and provides the possibility to set the parameter...

Page 7: ...s of the same type Connect the unit via the IO Link interface to a PC or PLC with suitable param eter setting software ifm offers an IO Link interface for the connection of the sensor via USB port 7 1 Adjustable parameters OU Output function Analogue output signal I 4 20 mA Ineg 20 4 mA ASP Analogue start point for temperature With setting OU I Measured value at which the output signal is 4 mA Wit...

Page 8: ... 5 mA Uni Unit of measurement for the system temperature C or F 8 Operation After power on the unit is in the Run mode normal operating mode 9 Technical data Technical data and scale drawing at www ifm com 10 Factory setting Factory setting User setting OU I COF 0 0 FOU OFF Factory setting ASP and AEP and the units Uni Technical data at www ifm com More information at www ifm com ...

Reviews: