5
UK
5 Electrical connection
► Connect the incoming AS-i line 1 to the terminals A+ and A- and the outgoing
AS-i line 2 to the terminals A+ and A-�
An additional AS-i power supply is required for the outgoing AS-i line 2�
Incoming and outgoing AS-i lines must not be connected to each other,
otherwise the electrical separation of the repeater is eliminated�
In case of AS-i lines longer than 100 m, the AS-i bus can be terminated� For
this purpose, connect T1 and T2 using the supplied link�
5.1 Terminal connection
A2- A2+ A2- A2+
A1+ A1- A1+ A1-
T1 T2
A2-: AS-i - line 2
A2+: AS-i + line 2
A2-: AS-i - line 2
A2+: AS-i + line 2
A1+: AS-i + line 1
A1-: AS-i - line 1
A1+: AS-i + line 1
A1-: AS-i - line 1
T1, T2 termination
6 Operation / LEDs
LED PWR 1 green: AS-i voltage 1 OK
LED TERM yellow: Termination active
LED PWR 2 green: AS-i voltage 2 OK