SDGx50
Flow meter compressed air
16
u
Insert the measuring length so that the flow direction and the arrow (5) show in the same direction.
u
Insert the screws and tighten.
6.5 Inserting the sensor into the pipe section
1
2
3
u
Remove the protective cover from the measuring probe of the sensor
(1).
u
Insert the sensor into the measurement connection (2).
u
Align the sensor: parallel to the pipe section, connector in the
direction of the arrow on the pipe section.
u
Tighten the coupling nut (3). Tightening torque max. 50 Nm. When
doing so, keep the position of the sensor.