20
10.2 Settings for volumetric flow monitoring
►
Select the operating mode [ModE] first before doing all the other settings
For the operating modes GAS and LIQU, the flow values are set in the unit
defined in [uni]�
►
If necessary, change the unit before setting the flow values�
For the operating mode REL the unit % is always used�
10.2.1 Define the operating mode
►
Select [ModE] and define the operating mode: REL, GAS, LIQU�
A medium and an internal pipe diameter must be entered for the
operating modes LIQU and GAS�
When the factory setting is changed (ModE = REL), the unit displays
[≡≡≡≡] to force these entries:
►
Press [
●
]�
> [MEdI] is displayed�
►
Define medium�
> [diA] is displayed�
►
Define the internal pipe diameter in mm or inch�
The operating mode REL requires a flow adjustment
�
A change of the operating mode leads to a restart of the unit�
The settings are saved in the respective operating mode,
i�e� after a change of the operating mode the settings are not
lost�
Menu INI:
[ModE]
10.2.2 Define the internal pipe diameter
►
Select [diA] and define the internal pipe diameter:
SAxx04: 15���400 mm
SAxx14 0,6���16 inch
[diA] is only available if the operating mode GAS or LIQU is selected�
Menu INI:
[diA]