21
UK
10.2.3 Configure the analogue output for flow (OUT2)
►
Select [ASP2] and set the flow value at which the output signal is 4 mA�
►
Select [AEP2] and set the flow value at which the output signal is 20 mA�
[ASP2] and [AEP2] are only available if the operating mode GAS or
LIQU is selected�
Main menu:
[ASP2]
[AEP2]
10.2.4 Carry out the flow adjustment
1� High-flow adjustment:
►
Switch on the supply voltage�
►
Activate the maximum flow in the installation�
►
Select [t�HGH] and press [
●
]�
> [tch] is indicated�
► Keep [▲] or [▼] pressed.
> [----] is displayed�
►
Briefly press [
●
]�
> Display [donE]: adjustment successful�
Display [FAIL]: repeat the adjustment�
> The unit defines the existing flow as maximum flow (final value of the
measuring range = 100 %)�
►
Briefly press [
●
]�
2� Low-flow adjustment:
►
Switch on the supply voltage�
►
Activate the minimum flow in the installation�
►
Select [t�LOW] and press [
●
]�
> [tch] is indicated�
► Keep [▲] or [▼] pressed.
> [----] is displayed�
►
Briefly press [
●
]�
> Display [donE]: adjustment successful�
Display [FAIL]: repeat the adjustment�
> The unit defines the existing flow as minimum flow (0 %)�
►
Briefly press [
●
]�
[t�HGH] and [t�LOW] are only available if the operating mode REL is
selected�
Main menu:
[t�HGH]
[t�LOW]