4  Functions

Current output 4...20 mA 

(PT24xx)

P = system pressure, MEW = final value of the measuring range
In the measuring range the output signal is between 4 and 20 mA.

If the system pressure is above or below the measuring range, the analogue output 

behaves, without achieving the accuracy, as follows:
•  System pressure above the measuring range: 20...25 mA.
•  System pressure below the measuring range: 4...3 mA.

5  Installation

Before installing and removing the unit: make sure that no pressure is 

applied to the system.

 

Insert the unit in a ¼-18 NPT process connection.

 

Tighten firmly. Recommended tightening torque: max. 50 Nm. 

Depends on lubrication, seal and pressure load!