• Installation, electrical connection, set-up, operation and maintenance of the unit
must be carried out by qualified personnel authorised by the machine operator.
• Protect units and cables against damage.
3 Functions and features
The pressure sensor detects the system pressure and converts it into an analogue
output signal.
3.1 Applications
• Type of pressure: relative pressure
Order number
Measuring range
Static pressure
resistance (max.
permissible pressure)
Bursting
pressure
psi
psi
psi
PT2415
0...100
250
2900
PT2424
0...200
580
6525
PT2494
-14,5...200
580
6525
PT2434
0...300
940
8700
PT2443
0...500
1450
11600
PT2402
0...1000
2500
13050
PT2432
0...3000
7250
14500
PT2400
0...5000
14500
24650
Avoid overload pressure exceeding the specified maximum permissible
pressure by taking appropriate measures.
The indicated bursting pressure must not be exceeded.
Even if the bursting pressure is exceeded only for a short time, the unit
may be destroyed.
ATTENTION: Risk of injury!
Pressure Equipment Directive (PED):
The units comply with the Pressure Equipment Directive and are designed
and manufactured for group 2 fluids in accordance with the sound
engineering practice.
Use of group 1 fluids on request!
The units are vacuum resistant.