4  Functions and features

The unit detects the hydrostatic pressure and converts it into an analogue output 

signal. The output signal changes in proportion with the level of the tank.

Applications

•  Liquids.

• 

Tanks, containers, wells, streaming water, drill holes, wastewater plants.

Pressure Equipment Directive (PED): 

 

The units comply with the Pressure Equipment Directive and are designed 

and manufactured for group 2 fluids in accordance with the sound 

engineering practice. Use of group 1 fluids on request!

5  Installation

 

Place the unit in the tank such that it is as close as possible to the tank bottom 

(→ Fig. 1). For fixing with cable clamp fastener → Fig. 2.

A

1

2

 

► For viscous media: unscrew and remove the protective cap (A). 

 

► In order to prevent or reduce oscillating movements of the unit: 

unscrew the protective cap (A), screw the additional weight (order no. 

E30402) to the unit.

The unit operates on the principle of relative pressure. A capillary tube ensures 

pressure compensation. It is inserted through the connection cable. 

 

Make sure that the capillary tube is not blocked. If necessary, install a filter 

element (order no. E30400). Or use the splitter box with ventilation (order no. 

E30401) for the electrical connection.

Summary of Contents for PS3 Series

Page 1: ...Installation instructions Submersible pressure transmitter PS3xxx PS3xxA PS4xxx 14014571 05 06 2017 UK ...

Page 2: ...r its intended purpose Functions and features Only use the product for permissible media Technical data If the operating instructions or the technical data are not adhered to personal injury and or damage to property may occur Contents 1 Preliminary note 2 1 1 Symbols used 2 2 Safety instructions 2 3 Items supplied 3 4 Functions and features 4 5 Installation 4 5 1 Requirements for the mounting loc...

Page 3: ... the unit may be destroyed CAUTION risk of injury For submersible pressure transmitters PS3xxA Adhere to the remarks for safe use in hazardous areas ATEX operating instructions 3 Items supplied For the measuring range and the cable length please refer to the data sheet of the corresponding submersible pressure transmitter The submersible pressure transmitters PS3xxA are approved for use in hazardo...

Page 4: ... 5 Installation Place the unit in the tank such that it is as close as possible to the tank bottom Fig 1 For fixing with cable clamp fastener Fig 2 A 1 2 For viscous media unscrew and remove the protective cap A In order to prevent or reduce oscillating movements of the unit unscrew the protective cap A screw the additional weight order no E30402 to the unit The unit operates on the principle of r...

Page 5: ...nstall the units near strong sources of electromagnetic interference e g transmitters radio equipment or if necessary use a sheath current filter 6 Electrical connection The unit must be connected by a qualified electrician The national and international regulations for the installation of electrical equipment must be adhered to Voltage supply to EN 50178 SELV PELV For submersible pressure transmi...

Page 6: ... unit After use dispose of the unit in an environmentally friendly way in accordance with the applicable national regulations 8 Scale drawing PS3xxx 27 147 PS3xxA PS4xxx 9 Technical data For the measuring range the permissible overload pressure and the bursting pressure please refer to the data sheet of the corresponding submersible pressure transmitter ...

Page 7: ...7 UK More information at www ifm com ...

Reviews: