9.3 Configure display (optional)
►
Select [diS] and set the update rate and orientation of the display:
-[d1]: update of the measured values every 50 ms�
-[d2]: update of the measured values every 200 ms�
-[d3]: update of the measured values every 600 ms�
-[rd1], [rd2], [rd3]: display as for d1, d2, d3; rotated by 180°�
-[OFF] = the measured value display is deactivated in the Run mode�
The LEDs remain active even if the display is deactivated�
Error messages are displayed even if the display is deactivated�
Even with unsteady pressure characteristics [d1] provides optimum
readability; the corresponding algorithms are stored�
9.4 Set output signals
9.4.1 Set output functions
►
Select [ou1] and set the switching function:
-[Hno] = hysteresis function/normally open,
-[Hnc] = hysteresis function/normally closed,
-[Fno] = window function/normally open,
-[Fnc] = window function/normally closed,
-[OFF] = output off�
Parameter [OFF] is only available in operating mode 3 ([CMPT] = [3])�
►
Select [ou2] and set the function:
-[Hno] = hysteresis function/normally open
-[Hnc] = hysteresis function/normally closed
-[Fno] = window function/normally open,
-[Fnc] = window function/normally closed,
-[OFF] = output off�
Parameter [OFF] is only available in operating mode 3 ([CMPT] = [3])�
9.4.2 Set switching limits for the hysteresis function
►
[ou1] / [ou2] must be set as [Hno] or [Hnc]�
►
Select [SP1] / [SP2] and set the value at which the output switches�
►
Select [rP1] / [rP2] and set the value at which the output is reset�
rPx is always smaller than SPx� The unit only accepts values which are lower
than the value for SPx�