18
9.4.3 Set switching limits for the window function
►
[ou1] /[ou2] must be set as [Fno] or [Fnc]�
►
Select [FH1] / [FH2] and set the upper limit value�
►
Select [FL1] / [FL2] and set the lower limit value�
FLx is always lower than FHx� The unit only accepts values which are lower
than the value for FHx�
9.5 User settings (optional)
9.5.1 Set delay time for the switching outputs
[dS1] / [dS2] = switching delay for OUT1 / OUT2�
[dr1] / [dr2] = reset delay for OUT1 / OUT2�
►
Select [dS1], [dS2], [dr1] or [dr2] and set a value between 0 and 50 s (at
0 the delay time is not active)�
A
B
Output function:
A:
B:
[Hno] / [Hnc]
dS
dr
FH
FL
A B
C D
Output function:
A:
B:
C:
D:
[Fno] / [Fnc]
dS
dr
dS
dr
P = system pressure; SP = set point; rP = reset point; HY = hysteresis;
FE = window; FH = upper value; FL = lower value�