21
UK
9.5.3 Set damping for the switching signal
►
Select [dAP] and set the damping constant in seconds
(
T
value: 63 %); setting range 0�000���4�000 s�
Damping [dAP] affects the switch point / process data flow (IO-Link
communication) and the display�
9.5.4 Set damping for the analogue output
►
Select [dAA] and set the damping constant (rise time 10���90 %) in
seconds; setting range 0�000���4�000 s�
Damping [dAA] only influences the analogue output / analogue
signal path�
9.5.5 Zero-point calibration
►
Select [coF] and set a value between -5 % and 5 % of the final value
of the measuring range (if PN2x69 and PN2x99 ±5 % of the measuring
span)� The internal measured value "0" is shifted by this value�
9.5.6 Reset all parameters to factory setting
►
Select [rES]�
► Press [●].
► Press [▲] or [▼] and keep pressed until [----] is displayed.
► Briefly press [●].
It is recommended to note down your own settings before carrying out a
�
The operating mode [CMPT] is also reset to the factory setting
([CMPT] = [2])�