• System pressure above the measuring range:
-output signal > 20 mA if [OU2] = [I]�
-output signal between 4 and 3�8 mA if [OU2] = [InEG]�
• System pressure below the measuring range:
-output signal between 4 and 3,8 mA if [OU2] = [I]�
-output signal > 20 mA if [OU2] = [InEG]�
Voltage output
Factory setting
Measuring range scaled
P = system pressure, MAW = initial value of the measuring range, MEW = final value of
the measuring range
1
: [OU2] = [U];
2
: [OU2] = [UnEG]
The output signal is between 0 and 10 V ([OU2] = [U]) or between 10 and 0 V
([OU2] = [UnEG]) in the set measuring range�
It is also indicated:
• System pressure above the measuring range:
-output signal > 10 V if [OU2] = [U]�
• System pressure below the measuring range:
-output signal > 10 V if [OU2] = [UnEG]�