13
UK
8.2 Menu explanation
SP1/rP1
Maximum / minimum value for system pressure, at which output 1 changes
its switching status�
OU1
Output function for OUT1:
• Switching signal for the limit values: hysteresis function [H ��] or window
function [F ��], normally open [� no] or normally closed [� nc] each�
• Diagnostic signal [dESI]�
OU2
Output function for OUT2:
• Analogue signal for the current system pressure: 4���20 mA [I], 20���4 mA
[InEG], 0���10 V [U], 10���0 V [UnEG]�
tCOF
Teaching zero-point calibration�
tASP
Teaching analogue start point for the system pressure: set value at which
4 mA / 0 V are output (20 mA / 10 V on [OU2] = [InEG] / [UnEG])�
tAEP
Teaching analogue end point for the system pressure: set value at which
20 mA / 10 V are output (4 mA / 0 V on [OU2] = [InEG] / [UnEG])�
EF
Extended functions / Opening menu level 2�
Uni
Standard unit of measurement for the system pressure�
SELd
Display mode:
• Pressure in the unit set in [Uni]�
• Pressure in % of the set scaling of the analogue output�
ASP
Analogue start point for the system pressure: measured value at which
4 mA / 0 V are output (20 mA / 10 V on [OU2] = [InEG] / [UnEG])�
AEP
Analogue end point for the system pressure: measured value at which
20 mA / 10 V are output (4 mA / 0 V on [OU2] = [InEG] / [UnEG])�
HI
Maximum value memory for the system pressure�
LO
Minimum value memory for the system pressure�
COF
Zero point calibration�
dS1
Switch-on delay for OUT1�
dr1
Reset delay for OUT1�
P-n
Output polarity for OUT1: pnp or npn�
dAP
Damping for the switching output (OUT1)�
dAA
Damping for the analogue output (OUT2)�
diS
Update rate and orientation of the display�
rES
Restore the factory setting�