background image

17

UK

•  Change from menu level 1 to menu level 2:

 

Touch [Mode/Enter] until [EF] is 

displayed�

Mode/

Enter

Set

 

Touch [Set] briefly� 

 

> The first parameter of the submenu is 

displayed (here: [Uni])�

If the menu level 2 is protected by an 

access code, "Cod1" flashes in the 

display�

 

Touch [Set] and keep it touched until 

the valid code no� appears�

 

Touch [Mode/Enter] briefly�

On delivery by ifm electronic: no access 

restriction�

Mode/

Enter

Set

•  Locking / unlocking

The unit can be locked electronically to prevent an unintentional operation�

 

Make sure that the unit is in the normal operating mode�

 

Touch [Set], 

 

additionally touch [Mode/Enter] and keep both buttons touched for 10 s�

 

> The LED for the current unit of measurement flashes, the current system pressure 

continues to be displayed� After 10 s the display goes out for approx� 1 s� 

 

Release [Mode/Enter] and [Set] again� Both buttons must be released within 4 s� 

If this does not happen, the unit remains unlocked�

 

> [Loc] is displayed, the unit is locked�

During operation the indicator LED for the display unit 

(→ 7 Operating and display 

elements) is flashing if you try to open the menu�
For unlocking:

 

Make sure that the unit is in the normal operating mode�

 

Touch [Set], 

 

additionally touch [Mode/Enter] and keep both buttons touched for 10 s�

 

> The LED for the current unit of measurement flashes, the current system pressure 

continues to be displayed� After 10 s the display goes out for approx� 1 s�

 

Release [Mode/Enter] and [Set] again� Both buttons must be released within 4 s�  

If this does not happen, the unit remains unlocked�

 

> [uLoc] is displayed, the unit is unlocked� 

On delivery: unlocked�

Summary of Contents for PG243

Page 1: ...UK UK Operating instructions Electronic manometer PG243 PG244 11386049 00 08 2020...

Page 2: ...lanation of the main menu 13 8 3 Menu structure level 2 extended functions 14 8 4 Explanation of the menu level 2 15 9 Parameter setting 16 9 1 General parameter setting 16 9 2 Configuration of the di...

Page 3: ...note Non compliance may result in malfunction or interference Information Supplementary note 9 5 Service functions 22 9 5 1 Read min max values for system pressure 22 9 5 2 Reset all parameters to fac...

Page 4: ...for its intended purpose Functions and features Only use the product for permissible media Technical data If the operating instructions or the technical data are not adhered to personal injury and or...

Page 5: ...ice is removed it can become unusable When the damping device is removed the unit can no longer be used under UL conditions If you have any questions please contact ifm electronic s sales specialists...

Page 6: ...ally open OU1 Hno fig 1 Hysteresis function normally closed OU1 Hnc fig 1 First the set point SP1 is set then the reset point rP1 with the requested difference Window function normally open OU1 Fno fi...

Page 7: ...ameter AEP defines at which measured value the output signal is 20 mA 4 mA at InEG Minimum distance between ASP and AEP 25 of the final value of the measuring range Factory setting Measuring range sca...

Page 8: ...the extended display range The zero point calibration COF influences the calibration of the curve of measured values Recommendation set COF to 0 9 4 1 COF then calibrate the curve of measured values A...

Page 9: ...uitable for process connections with cylindrical pipe thread e g flat seals or double edge sealing rings 2 Installation with sealing tape Insert the unit and the sealing tape into the process connecti...

Page 10: ...equipment must be adhered to Voltage supply according to EN 50178 SELV PELV Disconnect power Connect the unit as follows OUT1 positive switching OUT1 negative switching Pin 1 Ub Pin 3 Ub Pin 4 OUT1 Bi...

Page 11: ...s Trend display rising pressure or falling pressure 3 Indicator LEDs LED 1 system pressure of the digital display in bar mbar LED 2 system pressure of the digital display in MPa kPa LED 3 LED 4 LED 5...

Page 12: ...ouch buttons are activated simply by touching deactivated by releasing the touch button The touch button must be completely covered to be activated Slow covering e g liquid flows over the display does...

Page 13: ...mally open no or normally closed nc OU2 Output function for OUT2 Analogue signal for the current system pressure 4 20 mA I 20 4 mA InEG tCOF Teach zero point calibration tASP Teach analogue start poin...

Page 14: ...14 8 3 Menu structure level 2 extended functions 1 Change to the main menu...

Page 15: ...d value at which 20 mA is provided 4 mA if OU2 InEG HI Maximum value memory for system pressure LO Minimum value memory for system pressure COF Zero point calibration dS1 Switch on delay for OUT1 dr1...

Page 16: ...5 s setting value is changed step by step by touching briefly several times or continuously by touching permanently Mode Enter Set Numerical values are incremented continuously To reduce the value let...

Page 17: ...lashes the current system pressure continues to be displayed After 10 s the display goes out for approx 1 s Release Mode Enter and Set again Both buttons must be released within 4 s If this does not h...

Page 18: ...dicator LEDs remain active even if the display is deactivated Select LED and set the display function for the digital display and LED ring SPRP One LED on the LED ring indicates the set point and a se...

Page 19: ...uch Mode Enter until tASP appears Touch Set and keep it touched Current setting value flashes Release Set when the display stops flashing New setting value is displayed Touch Mode Enter briefly The cu...

Page 20: ...sure that no pressure is applied to the system Touch Mode Enter until tCOF appears Touch Set and keep it touched The current offset value in flashes briefly The current system pressure is displayed R...

Page 21: ...and AEP in the system Select CAL Touch Set briefly CP1 is displayed Touch Set for 5 s The pressure measured by the unit is displayed Touch Set until the set reference pressure is indicated measured p...

Page 22: ...ation functions and provides output signals according to the set parameters Operating indicators 7 Operating and display elements Reset the lag indicator if LED HInd or LInd Touch Set for 1 second The...

Page 23: ...no OU2 I SP1 25 0 VMR rP1 24 9 VMR ASP tASP 0 VMR AEP tAEP 100 VMR COF tCOF 0 0 dS1 0 0 dr1 0 0 P n pnp dAP 0 06 dAA 0 03 Uni MPa kPa SELd P dis d2 LED SPRP the indicated percentage of the final value...

Reviews: