10.1 Read the set parameter values
►
Press [Mode/Enter] until the requested parameter is displayed�
►
Press [Set] briefly�
> The unit displays the corresponding parameter value for about 15 s� After
another 15 s the unit returns to the Run mode�
10.2 Fault indication
[OL]
Overload (presure above measuring range of the sensor)�
[UL]
Underload (pressure below measuring range of the sensor)�
[SC1]
Flashing: short circuit in the switching output 1*�
[SC2]
Flashing: short circuit in the switching output 2*�
[SC]
Flashing: short circuit in both switching outputs*�
*The output concerned is switched off as long as the short circuit exists�
10.3 Cleaning of the filter cover
If viscous and residues producing
media clog the filter cover of
the sensor (and thus reduce the
measuring accuracy slightly), you can
clean it�
►
Unscrew the filter cover (B) (use a
pair of pliers with plastic-covered
jaws for this)�
►
Clean the cover thoroughly�
A B
The vent (A) should only be cleaned by skilled personnel and with utmost care�
Possible medium residues must not be compressed and pressed into the vent�
This could clog the filter system and reduce the measuring accuracy of the
sensor�
►
Screw the filter cover again tightly�