7.2.1 Adjustable parameters
Among others, the following parameters can be set via IO-Link�
A table of all adjustable parameters can be found at
Parameters for the receiver (O6E7xx)
Parameter
name
Values
Description
Standard
setting
SSC1 Param�
SP1
1 ��� 100
Setting switch point in step increment "1"�
After a teach process the resulting value is
displayed�
100
Teach SP1 TP1
1� Part of the teach sequence to set switch
point SP1 by teach on object� Both parts of
the teach sequence for TP1 and TP2 (TP =
teach point) have to be carried out.
N� A�
Teach SP1 TP2
2� Part of the teach sequence to set switch
point SP1 by teach without object� The
second part of the teach sequence has to
be carried out after the first part�
N� A�
TI Result�State - Idle
- SP1
Success
- Wait for
command
- Busy
- Error
- Custom
Teach-in status; after successful teach the
value "SP1 Success" is displayed�
N� A�
SSC1 Config�
Logic
High
active
Low active
Switch point logic, status for detected object
(High: light-on mode / normally open, Low:
dark-on mode / normally closed)
→
Data
sheet value
"Output
function"
SSC1 switch-on
delay
0 ��� 2
Start-up delay; step increment 0�1 s
0
SSC1 switch-off
delay
0 ��� 2
Switch-off delay; step increment 0�1 s
0
Excess gain
0 ��� 5
Excess gain at receiver�
N� A�
Number of
power cycles
0 ��� 65535
Number of switching operations (power up)
of the sensor
N� A�