4: Selector switch S1 Programming the output function

S1 / S2 = 1: direct operation (output switches like input signal: IN =
ON 

 OUT = ON).

S1 / S2 = 2: inverted operation (output switches opposed to the in-
put signal: (IN = ON 

 OUT = OFF).

For single-channel units S2 has no function.

5: Selector switch S2

6: Selector switch S3 Setting for short circuit / wire monitoring

• When proximity sensors are connected monitoring is always

active. S3 must be in position I.

• When mechanical switches are connected the following applies:

– Monitoring active for input circuit no. 1; S3 must be in position

I.

– Without short circuit monitoring for input circuit no. 2 and S3

in position I.

– Without short circuit and wire monitoring for input circuit no. 3

and S3 in position II.

7 Maintenance, repair and disposal

The operation of the unit is maintenance-free.

Only the manufacturer is allowed to repair the unit.

u

After use dispose of the device in an environmentally friendly way in
accordance with the applicable national regulations.

Summary of Contents for N0537A

Page 1: ...Operating instructions Switching amplifiers N0537A N0538A N0539A 80299364 00 02 2021 GB...

Page 2: ...x certificate 4 3 4 Identification 4 4 Installation 4 4 1 Requirements for cables and connection cables 5 4 2 Requirements in case of use as associated equipment 5 4 3 Requirements for use with equipm...

Page 3: ...the corresponding applications and environmental conditions without any restrictions Only use the product for its intended purpose Intended use If the operating instructions or the technical data are...

Page 4: ...G group II category 1G 2G apparatus for gas atmosphere The requirements of the standards EN IEC 60079 0 2018 EN 60079 11 2012 EN 60079 15 2010 are met II 1 D group II category 1D apparatus for dust at...

Page 5: ...The permissible wire cross section must be adhered to In case multi wire conductors are used they have to be crimped with wire end ferrules u Make sure only one conductor per connecting terminal is u...

Page 6: ...ved proof of intrinsic safety 4 3 Requirements for use with equipment protection level Gc The unit may only be installed and operated if installed in a secondary housing that complies with the require...

Page 7: ...1 3 6 2 5 4 1 LED yellow Indication of the switching status output 1 output 2 lights when the corresponding output is switched the relay is en ergised 2 LED red Fault indication for input circuit 1 in...

Page 8: ...is always active S3 must be in position I When mechanical switches are connected the following applies Monitoring active for input circuit no 1 S3 must be in position I Without short circuit monitorin...

Reviews: