Install the unit outside the hazardous area.

The unit has the protection rating IP20 according to IEC/EN 60529.

u

Only install and use the unit under operating conditions that do not exceed
soiling degree 2 according to IEC EN 60664-1.
In case of use under operating conditions with a higher degree of soiling, the
unit must be protected accordingly.

u

Make sure all circuits connected with the unit comply at least with overvoltage
category II according to IEC EN 60664-1.

u

Only supplies providing protection against electrical shock (SELV or PELV)
may be connected to supply modules.

u

The installation regulations according to IEC/EN 60079-14 must be complied
with,

4.1 Requirements for cables and connection cables

u

The permissible wire cross section must be adhered to. In case multi-wire
conductors are used, they have to be crimped with wire end ferrules.

u

Make sure only one conductor per connecting terminal is used.

u

Make sure the insulation of the conductor reaches all the way to the connecting
terminal.

u

The tightening torque for the screws of the connecting terminal must be
adhered to.

If the voltage exceeds 50 V AC:

1. Switch off the voltage.

2. Attach or remove the terminal blocks.

4.2 Requirements in case of use as associated equipment

Circuits with Ex i type of protection that have been operated with non-intrinsically
safe circuits must no longer be used as circuits with Ex i type of protection then.

The intrinsically safe circuits of the associated equipment may be routed into
hazardous areas.

u

Make sure the separation distances to all non-intrinsically safe circuits
according to IEC/EN 60079-14 are observed.

GB

Summary of Contents for N0537A

Page 1: ...Operating instructions Switching amplifiers N0537A N0538A N0539A 80299364 00 02 2021 GB...

Page 2: ...x certificate 4 3 4 Identification 4 4 Installation 4 4 1 Requirements for cables and connection cables 5 4 2 Requirements in case of use as associated equipment 5 4 3 Requirements for use with equipm...

Page 3: ...the corresponding applications and environmental conditions without any restrictions Only use the product for its intended purpose Intended use If the operating instructions or the technical data are...

Page 4: ...G group II category 1G 2G apparatus for gas atmosphere The requirements of the standards EN IEC 60079 0 2018 EN 60079 11 2012 EN 60079 15 2010 are met II 1 D group II category 1D apparatus for dust at...

Page 5: ...The permissible wire cross section must be adhered to In case multi wire conductors are used they have to be crimped with wire end ferrules u Make sure only one conductor per connecting terminal is u...

Page 6: ...ved proof of intrinsic safety 4 3 Requirements for use with equipment protection level Gc The unit may only be installed and operated if installed in a secondary housing that complies with the require...

Page 7: ...1 3 6 2 5 4 1 LED yellow Indication of the switching status output 1 output 2 lights when the corresponding output is switched the relay is en ergised 2 LED red Fault indication for input circuit 1 in...

Page 8: ...is always active S3 must be in position I When mechanical switches are connected the following applies Monitoring active for input circuit no 1 S3 must be in position I Without short circuit monitorin...

Reviews: